Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹73.9 LAccepted-Finance | ₹73.9 L | L1 | Accepted-Finance OK L1 |
| 2 | L2₹81.7 LAccepted-Finance JALARAM MARKET SHOP NO 6 JAWAHAR ROAD AMRAVATI | AMRAVATI | AMRAVATI | MAHARASHTRA | ₹81.7 L | L2 | Accepted-Finance OK L2 |
| 3 | L3₹86.2 LRejected-Finance | ₹86.2 L | L3 | Rejected-Finance OK L3 |
| 4 | L4₹88.8 LRejected-Finance | ₹88.8 L | L4 | Rejected-Finance OK L4 |
| 5 | L5₹1.0 CrRejected-Finance | ₹1.0 Cr | L5 | Rejected-Finance OK L5 |
Tender Value
₹99.9 L
EMD Value
₹99,900
Closing Date
7 May 2026, 11:00 amClosed
Executive Engineer MIDC E AND M
Jog Center MIDC Office 4th Floor Wakadewadi Pune
Yogewadi Manerajuri Industrial Area Providing power supply arrangement in Yogewadi Manerajuri Industrial Area
2026_MIDC_1297284_1
18/2026
Open Tender
Electrical Works
YOGEWADI
As per NIT
3 documents required · 3 mandatory
₹11,800
₹99,900
12 Jun 2026
22 Apr 2026
8 May 2026
22 Apr 2026
7 May 2026
29 Apr 2026
22 Apr 2026 - 26 Apr 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Providing power supply arrangement in Yogewadi-Manerajuri Industrial Area | |||||
| 1.01 | Non-sealed transformer (SS-TR-NSL)
Supplying, installing, testing & commissioning 3 phase, 11/0.433 kV, 50 Hz., 200 kVA, Mineral oil immersed and naturally cooled outdoor type, copper wound Non-sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 40? by thermometer in oil and 45? by the resistance method in winding at full load rating, using type A winding insulation (kraft paper) with HV tapping (with off load tap changer)off load +2.5 to -5 in steps of 2.5%, having 4 number of tap positions, with standard accessories complete with test certificate with losses below 780 Watts at 50% load, 2300 Watts at 100% load as per IS:1180 (part 1) : 2014 , with necessary permissions of Electrical Inspector, as per specification no SS-TR-NSL. | - | each | - | - |
| 1.02 | Supplying and erecting rolled steel joist (girder) pole 100 x 116 mm (23 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ | - | Meter | - | - |
| 1.03 | Supplying and erecting V cross arm with ISM channel of 75x40x6mm for 11kV HT OH line with arrangement to fix insulator at 45mm from the end & horizontal distance between insulators 1220mm bent at angle of 60 degree keeping base 305mm and the total vertical height of V cross arm as 460mm, and fixed on pole with MS clamp of 80x10 mm, nut bolts, washers complete as per specification no. OH-PL/VCA | - | each | - | - |
| 1.04 | Supplying and erecting 75x40 x6mm with 4.4mm thick web and 7.3mm thick flange channel (top pin) with clamp of suitable length so as to maintain vertical clearance of 1065mm for 11kV, 1320mm for 22kV between insulators for erection of top pin insulators complete as per specification no. OH-PL/VCA | - | each | - | - |
| 1.05 | Supplying & erecting single pole cut point channel set of for 11kV HT OH line two channel of size 100x50x6mm 1.6m long having stud angle of size 50x50x6mm 1.5m long with necessary clamps, nut bolts etc. complete as per drawing. | - | each | - | - |
| 1.06 | Supplying & erecting inline cut point end pole D. P. Structure for 11/0.415 kV, 200 KVA Transformer with R.S.J. Pole 2 Nos. of size 100 x 116 mm x 11 Mtr. Long with suitable Distribution Box of C.R.C.A. Sheet 16 SWG with 4 Pole MCCB 400 Amps as incomer & 6 Nos. 200 Amps Kitkat / MCCB for out going circuits. Transformer D.P. Structure includes the A. B. Switch 200 Amps, D.O. fuse Set & L.A. Set. 2 Nos.Top channel of size 100 mmx 50 mm for erection of A.B. Switch & 2 Nos. Base channel of size 100 mm x 50 x mm for erecting Transformer. Channel of size 75 x40 mm for erecting D.O. Fuse Set, L.A., A.B. Switch handle etc.Angle of size 50 x 50 x6 mm for erecting Distribution Box , Transformer Belt etc.as per drawing (min.176 Kg. iron work ) with necessary clamps, Nut-bolts. V cross arm, top clip, insulators etc. complete with caution board & barbed wire.D.P. Structure shall be erected in c.c. foundation complete. | - | each | - | - |
| 1.07 | Supplying and erecting bracket for guarding of HT OH Line, made from channel iron 1600mm in length and 75x40x6mm. erected on pole complete as per specification no. OH-PL/VCA | - | each | - | - |
| 1.08 | Supplying and erecting all aluminum alloy conductor (AAAC) 55 mm2. complete as per MSEDCL‘s specification | - | Kilo meter | - | - |
| 1.09 | Supplying and erecting porcelain disc type insulator 45KN with necessary hardware suitable for 11kV line, complete as per specification no. OH-INS/DI | - | each | - | - |
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.06 MB
ItemSpecification.pdf
Tender Documents • 0.04 MB
BOQ_2228428.xls
BOQ • 0.35 MB
TenderDocument.pdf
Tender Documents • 0.44 MB
Download all tender documents and submit your bid