| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹49.9 LAccepted-AOC 1202 SAI PROVISO DHNISHT PLOT NO 72 73 SECTOR 20 KOPARKHAIRANE NAVI MUMBAI | THANE | MAHARASHTRA | 400601 | L1 | Accepted-AOC Being Lowest Tenderer | |
| 2 | L2₹56.1 L+₹6.2 L (12.4%)Rejected-Finance SHOP NO 10 BMC SHOPPING CENTRE MITHA NAGAR GOREGAON WEST MUMBAI 400 104 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400104 | L2 | Rejected-Finance Being other than Lowest tenderer | |
| 3 | L3₹59.9 L+₹9.9 L (19.9%)Rejected-Finance | L3 | Rejected-Finance Being other than Lowest tenderer |
Tender Value
₹49.5 L
EMD Value
₹98,000
Closing Date
15 Aug 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Lt Col NG Rajesh Singh GE NW KUNJALI
GARRISON ENGINEER NW KUNJALI DR HOMI BHABHA ROAD NAVY NAGAR COLABA MUMBAI 400005
8460 ADDITION/ ALTERATION IN BOARD ROOM AT HQ WNC AT NAVAL DOCKYARD MUMBAI PROVISION OF AFDS SYSTEM FOR BLDG NO 196 208 NEW COY UNDER NAVAL DOCKYARD
2022_MES_538897_1
8460/E8
Open Tender
Civil Works
Item Rate
183 days
GE (NW) KUNJALI
AS PER TENDER DOCUMENTS
7 documents required · 7 mandatory
₹500
Yes
GE (NW) KUNJALI
₹98,000
Yes
13 Oct 2022
18 Jul 2022
17 Aug 2022
25 Jul 2022
15 Aug 2022
1 Aug 2022
18 Jul 2022 - 25 Jul 2022
Amount
S&F LED recess mounted type fitting 36W 2'x2' CRCA LED Slim panel COLOR CHANGING REMOTE CONTROLLED with recess mounting, powder coated white CRCA full glow LED panel including control gear and lamp complete all as directed and specified by Engr-in-Charge.
M & L for point wiring with FRLS PVC insulated unsheathed multi stranded copper conductor cable of 1.5 sqmm size 1100 volts grade drawn through and including non metalic rigid PVC casing and caping not less than 25mm width with all accessories fixed on wall including FRLS PVC insulated, unsheathed multistranded copper conductor cable of size 1.5 sqmm as earth continuty conductor connecting to common earth dolly and PVC moulded box ISI marked for having the switches, switch sockets regulator etc complete all as specified for following:-
One light point controlled by one switch
One 5 Amps switch socket combination on independent board
M & L for taking down exisitng PVC/ Modular switch/ socket board and refxing the same after wooden panel fixing.
M & L for point wiring with FRLS PVC insulated unsheathed multi stranded copper conductor cable of 2.5 sqmm size 1100 volts grade drawn through and including non metalic rigid PVC casing and caping not less than 25mm width with all accessories fixed on wall including FRLS PVC insulated, unsheathed multistranded copper conductor cable of size 2.5 sqmm as earth continuty conductor connecting to common earth dolly and PVC moulded box ISI marked for having the switches, switch sockets regulator etc complete all as specified for following:-
One 5 pin, 15 Amps switch socket combination on same board
Supply and fix switch piano, modular type 1 way 6 Amps 1 module 240 volts flush type matching existing pattern
Supply and fix switch piano, modular type 1 way 16 Amps 1 module 240 volts flush type matching existing pattern
Supply and fix modular socket 6 Amps 2/3 pin 240 volts Ac combined 2 module all as specified and directed by Engr-in-Charge matching existing pattern
Supply and fix modular socket 16 Amps 2/3 pin 240 volts Ac combined 2 module all as specified and directed by Engr-in-Charge matching existing pattern
Supply and fix ceiling rose surface bakelite three terminal of size 60x50 mm,240 Volts AC complete matching existing pattern
Supply , fixing, testing in repairs of JEF ECO SAFE Maintenance Free Grounding Solution set comprising of High tensile low carbon steel rod of 3 Mtr length & 25 mm dia with 250 micron ( averaSchneider ) molecularly bonded copper on the outer surface to confirm with requirements of UL467 along with Back-fill compound strictly be a Carbon based conductive concrete type which has a resistivity of less than 0.12 Ohm Mtr as per Clause 14.5D of IEEE : 80 standard. Back-fill compound should be electronically conductive ( Like in metals ) and should not depend on moisture for conduction. JEF Powerfill Loresco compound shall be supplied in 50 Pound Bag. ( 1 Bag of 50 Pounds required per earthing set). Back-fill comound should be environment friendly, should solidify when mixed with water and set like concrete and should not leach / diffuse into the ground. A suitable earth terminaton clamp should also be supplied along with the set alongwith earth pit weatherproof incl all as specified . Note : Back-fill compund shall not be mixed with any soil while pouring in the bore hole.
M & L for 4mm GI wire earth continuity conductor or main earthing lead fixed to wall or buried in ground and fixed to panel/transformer alongwith 20mm GI pipe light grade for protection.
Dismantling of Wall and ceiling boards (fibre, pulp, insulation, etc.) or insulation boards/slabs/blankets, any thickness, including cover fillets.
M&L for POP false ceiling using 600 x 900 x 12 mm thick plaster of paris with gypsum binder sheet decorative type and necessary provision for concealed type light fittings, fixed on 22 gauge GI channel grid work main joist of size 50 x 25 mm spaced at 750 mm centre, secondary joist of size 75x20 mm fixed to main joists spaced t 900 mm suspended to roof members using 25 x 25 x 2 mm GI angles and fasteners @ 1.2 m C/C including decorative design/pattern all as specified and directed Engr-in-Charge.
M&L for false ceiling made out of 600 x 600 x 4 to 6 mm thick ceiling board/tiles deep panel suspensor system made out of powder coated GI sheet main tee of size 23.50 x 40 x 0.63 mm and cross tee of size 23.50x23.50x0.63 mm and angle size 19x19x0.63 mm including 3 mm GI wire for suspending holts necessary washers nut/cleats/pin hook etc for securing frame work to ceiling to the snap grid including provn of necessary holes/cutting for providing light/far as required including making necessary recesses/projected pattern complete all as spoecified and as directed.
Taking down chowkats or frames but n exc 1.5 sqm each but with shutters (without taking off shutters from the frame)
Taking down chowkats or frames exc 1.5 sqm but n exc 4 sqm each but with shutters (without taking off shutters from the frame)
Taking down cement plaster on brick/ surfaces built in cement mortor including raking out joints, hacking for key scrubbing down with water upto G plus 4th floor of bldg incl scaffolding etc complete all as specified and directed by EIC.
M&L for rendering 15mm thick in CM 1:4 on fair faces of brick work or concrete surfaces finishing using waterproofing compound the surface fair and even all as specified and directed. (Note : Integral water proofing compound shall be measured and paid seperately).
Supply only Integral water proofing compund
M & L for preparation applying two coats of plastic paint over a coat of primer complete all as specified and as directed
M&L for applying 1 to 2mm thick wall care putty on wall (JK Birala Wall care Putty) on old/new plaster surface as all specified and directed by Engr-in-Charge
M&L for preparing and applying two coat of synthetic varnish over wood filler to Surfaces of any description, over 10cm in width or girth all specified and directed by Engr-in-Charge.
M & L for preparation and applying Three coats of French polishing on surfaces of any description, width or girth including cleaning and preparing the surface including a coat of wood filler on new works complete all as specified and as directed.
S&F 3 mm thick aluminium composite panel cladding plain of approved colour/shade to beam/column/slab incircular/rectangular shape inbcluding cutting, notching, bending to shape as required jointing with silicon gel of approved colour & aluminum tubular hallow section 25 x 25 mm not exceeding 900 mm C/C on exceeding column/beam/slab to hold APC cladding etc (Note : colour/pattern of ACP sheet shall be approved by GE).
S&F for hego/pergo 8mm thick wooden flooring including spung/polythene. All as specified and directed.
M&L for pine wood wall panelling 12 mm thick fixed with grueing/screws to timber frame work. All as specified and directed.
S&F 12mm thick, toughened glass for door shutters, partitions, shelves etc with and including fitting and fixtures such as glass handles ss studs (600 mm long), fittings for door pivots etc complete all as specified and directed by Engr-in-Charge.
Hacking out old broken glass ( any thickness, size, quality or description ) from wooden or stone, concrete or brick surrounds, glazed with putty or fixed with beads complete all as specified and directed.
S & F Solar control film 25 micron reflective type sticked to glass panes as per instructions of manufacturers
Removing of bldg material exc. 5 km but n exc.15 km and depositing where directed all as specified and directed by Engr-in-Charge.
S&F in repair double action floor spring hydraulically regulated made up of minimum 1.25 mm thick aluminium ally sheet foundation box, main body with stainless steel cover, governing pivot made of bras, other parts made of mild steel heavy duty and fixed complete all as specified and as directed
M&L for perporated vinayle graphics stickers having departmental logos engraving on glass. Complete all as specified and directed.
Supplying installation, Testing & Commissioning of Microprocessor based 2 loop capacity , Networkable analogue addressable type fire alarm control panel with min.600 character LCD display, The panel should be equipped with sufficient numbers of loop with up to 10 to 15% spare capacity with each loop shall have a capacity of minimum 99 detectors and 99 analog addressable devices in one loop. Four access levels, capable of taking Flash Scan devices, flash EPROM sufficient numbers of programmable relay controls for controlling AHUs, pressurization fans, ventilation fans at fire pump room, monitoring of fire sprinkler and fire hydrant pump, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and then be capable of operating the system for 2 hours during an emergency conditions as required. and panels shall have provision of intigraton with BMS System.(UL/EN Approved) as per tender specificaiton.Panel shall be integrated with respective to the zoning of PA System so that incase of fire so PA System shall automatically come in announcement mode as per tender specificaiton. Make : Honeywell/Siemens/Bosch/Morley
LANDLINE FIRE ALARM AUTO DIALER WITH sms and Memory Available To Store 10 Phone Numbers dialling facility to reach the fire brigade to get the intimation about the location of the area Builtin Emergency Speech Dialer with 8 Numbers & 1/ 2 Messages,NO/NC contacts for both fire and fault, Automatic changeover arrangement to standby supply with battery charger with low battery indication,Fault/ failure indication such as MAINS FAIL, short, open, Battery FAIL etc,Micro-Controller Based System,Both Dialling Modes Can Be Used (Pulse/Tone),Recorded Message Playback Speaker Provision Available complete all as specified and as directed. Make : Agni/Ravel/Atss
Supplying installation, Testing & Commissioning of Microprocessor based Repeater Networkable analogue addressable type fire alarm control panel with min.600 character LCD display,Four access levels, capable of taking Flash Scan devices, flash EPROM sufficient numbers of programmable relay controls for controlling AHUs, pressurization fans, ventilation fans at fire pump room, monitoring of fire sprinkler and fire hydrant pump, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and then be capable of operating the system for 2 hours during an emergency conditions as required. and panels shall have provision of intigraton with BMS System.(UL/EN Approved) as per tender specificaiton.Panel shall be integrated with respective to the zoning of PA System so that incase of fire so PA System shall automatically come in announcement mode complete all as specified and as directed.
Supply, Installation, testing and commissioning addressable Manual call point(Pull down/Break Glass Type). The device shall have an LED which shall blink in normal state and get steady on activation to monitor the health status of the device and shall be underwritters laboratories listed, semi flush type complete all as specified and directed. Make : Honeywell/Siemens/Bosch/Morley
Supplying installation, Testing & Commissioning of Addressable monitor modules for Sprinkler Flow Switch and Door Holders as per tender specification. Make : Honeywell/Bosch/Morley/Siemens
Supply fix and commissioning and test of addressable electronic hooter with built in amplifier unit with two tone generator of 100 meter range complete all as specified and directed. Make : Honeywell/Siemens/Bosch/Morley
Supplying installation, Testing & Commissioning of Analog addressable Multi Criteria (Optical +thermal) detector with mounting based LED for AFC(Above Celling & below celling .) as per tender specificaiton all as specified and directed. Make : Honeywell/Bosch/Morley/Siemens
Supplying installation, Testing & Commissioning of Conventional Beam detector complete as required for hall & indoor open area. All as specified and directed. Make : Honeywell/Siemens/Morley/Siemens
Supplying installation, Testing & Commissioning of Addressable control modules for AHU, Access control Integration & stairs Pressurization Fan Hooters / Sounders / Strobes etc.all as specified and directed. Make : Honeywell/Siemens/Morley/Siemens
Supply and fix fault isolator module with automatic resetting arrangement complete all as specified and directed. Make : Honeywell/Edward/Bosch/Morley/Siemens
Supply & laying PVC FRLS armoured cable 1.5sq mm solid copper conductor 6 core, XLPE Insulated, Extruded PVC sheathed, galvanized steel strip, electric power cables (heavy duty) 1100 Volts grade, laid in duct / along pole/wall etc including makingconnection complete and making good the distrubed surface matching with existing surface complete all as directed. Make of wire : Polycab/ Havells/ Gloster Note : 1. The cost of Al thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it. Make; Polycab/ KEI/RR.
Supplying installation, Testing & Commissioning of Response indicator for Above celling detectors & Cabin Detectors Make : Honeywell/Bosch/Morley/Siemens
Supplying installation, Testing & Commissioning of The GUI based main network software must be capable of graphically representing each facility being monitored with floor plans and icons depicting the actual locations of the various systems; and / or sensors’locations. The GUI software shall be located in control room in one of the blocks and shall monitor all the blocks panel connected with each other. Along with workstation as per tender specificaiton.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .