| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.5 LAccepted-AOC | L1 | Accepted-AOC Being L1 Bidder | |
| 2 | L2₹15.8 L+₹32,890.50 (2.12%)Rejected-AOC | L2 | Rejected-AOC Being L2 Bidder | |
| 3 | L3₹16.2 L+₹66,702 (4.30%)Rejected-Finance KALIKAPUR MATHPARA BOLPUR BIRBHUM | BOLPUR | BIRBHUM | WEST BENGAL | L3 | Rejected-Finance Being L3 Bidder |
Tender Value
Refer Docs
EMD Value
₹34,490
Closing Date
24 Jan 2025, 1:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer, Birbhum Electrical DivisionPWD
Office of the EXECUTIVE ENGINEER P.W.DTE. Birbhum Electrical Division P.O. Suri,Dist Birbhum, Pin 731101
Implementation and execution of Electrical works for CFC of Santiniketan Goods Cluster Industrial Co Operative Society Ltd. at Fuldanga, P.O Santiniketan, PS Santiniketan, Block BolpurSriniketan, Dist Birbhum
2025_WBPWD_797236_1
BIRED/143/e-NIQ(1st call) of 2024-2025
Open Tender
ELECTRICAL WORKS ORG
Fixed-rate
45 days
Bolpur
Please refer Tender documents.
4 documents required · 4 mandatory
₹34,490
Executive Engineer, Birbhum Electrical DivisionPWD
2 May 2025
8 Jan 2025
27 Jan 2025
8 Jan 2025
24 Jan 2025
10 Jan 2025
10 Jan 2025
Amount
Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board with top cover plate and 2 no. suitable size “Ph & N” copper bar & earthing attachment fixed on wall incl. mending good damages to original finish. [1. (e)/E-24] Average run 10 mtr
Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 6A 3 pin Modular type plug socket & switch (Brand approved by EIC) on 4 Module GI switch board with 3/4 Module top cover plate on wall incl. necy. connection making earthing attachment, painting and mending good damages to building works. i) On Board
ii) Average run 7.5 mtr
Supply & Fixing 240 V, 4 nos. 6 A, 3 pin Modular type plug socket with 4 nos. 6A Modular type switch (Brand approved by EIC), 16A Modular switch type DP MCB (C-Curve) and Indicator without plug top on 2 row 18 Module GI Modular type switch board with 2 row 18 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [12/E-18]
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc [9b/ E-18] Power Plug
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket with 20/25A Modular switch (Brand approved by EIC) type SP MCB (C-Curve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.[16/ E-19]
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy.connections with PVC Cu wire and earth continuity wire etc. [5.a./E-17]
Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Brand approved by EIC) & necy. Connections. [ 5.b/ E-17]
Supplying & Fixing 2 Module GI/ PVC Modular Switch Board of the following sizes complete with top cover plate flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works. [2a/E-17]
Supply & Fixing 240 V 6 A Modular type switch (Brand approved by EIC) on existing GI Modular type switch board having top cover plate and making necessary connections as required. [3.a/E-17]
Supply & Fixing 240 V, 25A Modular starter (Brand approved by EIC) on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. [Make - Legrand ] i) 12 Way Enclosure (upto 160A)
ii) 8 Way Enclosure (upto 160A)
Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for 12way / 8way TPN DB vertical enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts bolts etc incl. provision for earthing attachment. [16/D-12]
Supplying and fixing double-door Horizontal TPN MCB Distribution Board with IP-42/43 protection, concealed in wall as per GS. 8 Way [ Legrand ]
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall as per GS. 2+14Way [ Legrand ]
Supplying and fixing MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment.4 Way .
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection. i) 63A DP
ii) 63 A FP
Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection. [Make-Legrand) [10 /D-8] i) 63A FP
ii) 125A FP
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS [Make-Legrand/ Schneider/Siemens /ABB/L&T) i) 6-32 A SP
ii) 6-32 A TP
iii) 63 A TP
Supply of 2/4 Core XLPE Insulated & Sheathed Armoured Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [ Make : Havells/ Polycab /RR kabel/ Gloster] i) 2 Core 6 Sq. mm
ii) 4core 35Sqmm
iii) 4core 70Sqmm
iv) 4core 150Sqmm
Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting [ 2(b) /F1] [for 2core 6Sqmm]
Laying of cable from 3/3½ core 35 sqmm to 50 sqmm on wall/ surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting. [ 2(c) /F1] [ for 4core 35Sqmm]
Laying of cable above 3½ core 50 sqmm and upto 3½ core 90 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting. [ 2(d) /F1] [ for 4core 70Sqmm]
Laying of one No. cable above 35 sqmm and upto 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed. [1.b/F-2]
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : i) 2 Core 6 Sq. mm
ii) 4core 35Sqmm
iii) 4core 70Sqmm
iv) 4core 150Sqmm
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials. i) 2 Core 6 Sq mm
ii) 4core 35Sqmm
iii) 4core 70Sqmm
iv) 4core 150Sqmm
Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. With 25x25x3mm angle iron support. [34.(a)/D-14] i) 200x50x1.25mm (18SWG)
ii) 300x50x1.25mm (18SWG)
Supply & Fixing of perforated GI cable tray bend with perforation not more than 17.5% suspended from ceiling with two nos. suspenders & 25x25x3mm angle iron for supporting the cross member incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. i) 300x50x1.25mm (18SWG)
ii) 200x50x1.25mm (18SWG)
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required i) 2 x 22/0.3 (1.5 sqmm)
ii) 2x(2.5 sqmm)+1x(1.5 sqmm)
iii) 2x(4 sqmm)+1x (2.5 sqmm)
iv) 2x(6 sqmm)+1x(4 sqmm)
v) 2 x 84/0.3 (6 sqmm)
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 25mm size PVC rigid conduit 'FR' HMS (Precision make) incl. necy. fittings as required i) 4 x 36/0.3 (2.5 sqmm) + 2 x 22/0.3 (1.5 sqmm) ECC
ii) 4 x 56/0.3 (4 sqmm) + 2 x 36/0.3 (2.5 sqmm) ECC
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 32mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required. 4x126/0.4 (16 sqmm) + 2 x 84/0.3 (6 sqmm) as ECC
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. i) 1.5 Sq mm
ii) 2.5Sq mm
iii) 4Sq mm
iv) 6Sq mm
v) 16Sqmm
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc. [10/E-18]
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire. [ 21 (a) / C-3 ]
Fixing only exhaust fan after making holes in wall as per GS. (9") [ 28(a)/C-4 ]
Fixing only exhaust fan after making holes in wall as per GS. (18") [ 28(d)/C-4 ]
Supply & Fixing GI sheet (20SWG) metal Cowl with MS flat iron frame & GI wire mesh on wall with necy. bolts & nuts (6 mm dia x 62 mm long) i) 230 mm Exhaust fan (9")
ii) 450 mm Exhaust fan (18")
Supply of ceiling fans(1200 mm Sweep) complete with all accessories having the following Model / Cat No. ( Make -Crompton Aura /Orient Gratia)
Supply of 230 mm 1370 RPM Exhaust fans complete with all accessories ( Make -EPC )
Supply of 450 mm 920 RPM Exhaust fans complete with all accessories ( Make -EPC )
Fixing only single/twin florescent light fitting complete with all accessories Directly on wall/ceiling as per GS. [14(d)/C-2]
Fixing only single/twin fluorescent light fitting complete with all accessories directly on wall/ceiling with HW block and ceiling plates, nipples etc. as required
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.[ 17/C-2 ]
Fixing only outdoor / street light type fluorescent light fitting complete with all accessories to be fixed /projected from the wall of the building incl. making holes to building, S&F 40 mm dia GI pipe (ISI-Medium) 1.50 mts. average length, with GI socket at one end and thread at the other end & suitable bend to house the fitting & making necy. connections with S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages towall and painting [19/C-3]
S& erection of 80mm dia, 1.5 mtr long G.I. pipe (ISI-M) with base plate in CC foundation with approved paint including providing muffing 0.45x0.45x0.3mtrs above roof level with neat cement finish.
Supply & Fixing single arm bracket of 1500mm long made by 40mm dia MS pipe incl. 100mm sleeve, CI pole cap, Through bolt etc & painting.
S&F Street light/Outdoor light/Compound Light Timer DB(Water Proof) in wall incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment and febricated with following items as per instructions of EIC i) 250mm x250mm x100mm water proof SMC encloser ---- 1No(Sintex make) ii) 240 V, 6-32 A SPMCB of breaking capacity 10KA & ''C'' Charecteristic -- 01 no(Legrand) iii) 240V , 2P, Power Contractor with accessories ----- 01 no(L&T MNX-22) iv) Astronomical time switch --- 01no(Astro Mini Cat no.T2DDT7) v) Toggle switch for manual/auto operation --- 01no. vi) 63A 2 pole terminal studs & neutral links- 1 no. vii) Necessary connection by copper wire.
S/F 200mmx250mmx100mm SMC loop box with hinged type single door fixed on pole by welding two number 40mm X6mm MS flat on r pole & the loop box fixed with this flat by four number suitable size nut bolts./ on wall by four number fastner. And also S&F of 2 way terminal block & one number 6A SPMCB for easy connection of existing out going cables to compound light with necessary inter connection as per direction of E.I.C. (Make-Sintex)
Supply of 4 Ft. 20 Watt single/twin LED light fitting for indoor application,complete with all accessories & Lamps having Single LED fittings (Philips cat No TMC 502 1XT-LED 22W ) with 1no.18W Master LED tube 1200mm 18W865 T8 I – 2100lm (PC body with heat sink)(Philips) similar specification of Crompton/ Havells/ Bajaj].
Double LED fittings (Philips cat No TMC 502 2XT-LED 22W ) with 2nos 18W Master LED tube 1200mm 18W865 T8 I – 2100lm (PC body with heat sink) (Philips) similar specification of Crompton/ Havells/ Bajaj].
Supply & Fixing of 12W LED lamp to the lamp point. [PHILIPS make] [NS]
Supply and delivery of LED Street Light(230vac, 60 W, 130 Lumen/Watt, 6500K, IP 66, THD<10%, bult in ,CRI>80%, ) with all necessary connection.[Make: PHILIPS cat no.BRP501 LED078 CW R5C PSU S1 V1similar specification of Crompton/ Havells/ Bajaj]. .
Supply and delivery of LED Street Light(230vac, 120 W, 130 Lumen/Watt, 6500K, IP 66, THD<10%, bult in ,CRI>80%, ) with all necessary connection.[Make: PHILIPS cat no.BRP503 LED156 CW R5C PSU S1 V1 / similar specification of Crompton/ Havells/ Bajaj].
Excavation of soil for installation of Earth Electrode and filling & ramming. (b) For Morrum Soil
Earthing with 65 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 No. 50 mm x 6 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F suitable heavy type heat shrinkable PVC sleeve to cover 50 mm x 6 mm GI flat, to an average depth of 3.65 Mts.
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos.12 mm dia holes on the GI pipe
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 65 mm x 8 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required
LT Distribution Panel SITC of floor mounted Indoor type extensible cubical MV switchboard, fabricated by CPRI approved panel maker having compartmentalized design, fabricated out of 14 SWG ( 2.0 mm ) nominal thickness CRCA sheet steel for framework and covers, and 3 mm nominal thickness for gland plates, including cleaning and finishing complete with 7 tank process, with short circuit withstand capacity of 31 MVA for one second, front openable, hinged, single shuttered, single door, with locking arrangement, good quality dust, damp and vermin proof rubber gaskets, solid connections from main busbars to switchgears & Switchgear to cable alley with required size of copper busbars, and control wiring using 2.5 sq. mm of RYB colour coded FRLS PVC Insulated Copper conductor single core cables and copper cable lugs. 1 no. of 50 mm x 6 mm GI earth strip for earthing, both side cable alleys, cable gland plates in two halves, dinrail for mounting switchgear, metering arrangements, drilling holes, detachable gland plates/knockout plates, providing 50 mm x 50 mm x 5 mm nominal thickness MS angle iron support for MCBs alongwith horizontal/vertical intermediate MS flat members for stiffening, mounting on MS channel iron framework 100 mm x 50 mm x 5 mm (9.2 kg/metre) for floor mounting of MV panel, providing MS plate, suitable for bottom/ top cable entry, grouting in ground, powder coating, providing and fixing the following switchgear and measuring instruments, earthing, cartage from fabricator's premises to site of work etc. as required.[ MCCBs will be ABB / Legrand/ Siemens/ Schneider Make. All the other accessories will be Legrand/Siemens/L&T Make and as per manufacurers standard ].
BUSBAR S&F 99.9% - 99.5% electrolytic tinned copper (Type test Certificate should be produced by manufacturer) semi soft, tined electroplated with heat srinkable PVC sleeve 4 Bar Bus Bar of Proper Size mounted on non-hygroscopic porcelain insulator/hylam sheet having sufficient di-electric strength duly wrapped with colour PVC sleeves (Red, yellow, blue & black) for phases & neutral identification & all connection made with required size cu bars (considering current density1.6A/Sqmm). i) 400A -1 Set INCOMER Supply & fixing of 250A and 415V, 4 pole 50 kA (Uimp=8KV), Ics= 100% Icu MCCB with microprocessor based release (LSIGN) having adjustable O/L (0.4 to 1x In or better), Adjustable S/C (1/1.5 - 8/10 Ir), Inbuilt Instantaneous protection, Adjustable E/F , Adjustable neutral protection at 50%, 100% and, There should be indication for trip cause, Both side spreader link, extended rotary handle. There should be LED indicating lamp for showing On, OFF, TRIP & R,Y,B, indication on the panel door etc. - 1 Set
OUTGOING i) Supply & fixing of 125A and 415V, 4 pole 36 kA MCCB with thermal magnetic release Both side spreader link, extended rotary handle. etc. - 4 Set ii) Supply & fixing of 63A and 415V, 4 pole 36 kA MCCB with thermal magnetic release Both side spreader link, extended rotary handle. etc. - 2 Set METERING Supply & Fixing 3 phase 415V Multifunction Meter of 0.5S accuray, capable of display 3 phase parameters at a time with LCD disply & folowing parameters can be measured V, A, F, kW, KVA, kVAr, kWh, kVAh, kVArh, PF, Phase angle, THD, Events, Neutral current, Max Demand(with RTC) Supply & Fixing of following : i) 200/5/1 CT - 3 nos. ii) 6 A TPMCB - 1 no. iii) 6 A SPMCB - 1 no.
Supplying and fixing 415 V 250A Four Pole MCCB of Breaking capacity 35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting with both side spreader link in water proof SMC box of size 700mmX480mmX210mm (sintex make GSJB 7450) by two number 50mm X6mm MS flat iron frame grouted on wall and necessary connection
S& Drawing 4X 70Sqmm (360/0.5) copper flexible wire through 50mm dia steel reinforced pvc flexible conduit.
S&F 50mm dia pvc flexible conduit gland.
S&F long barrel 70Sqmm ring / pin Copper socket.
E.I.Work for AC S&F 3-phase AC Control Box(Water Proof) fixed on wall incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment and febricated with following items as per instructions of EIC i) 200mm x250mm x100mm water proof SMC encloser ---- 1No(Sintex make) ii) 240 V, 6 A SPMCB of breaking capacity 10KA & ''C'' Charecteristic -- 01 no(Legrand) iii) 240V , 3P, Power Contractor with accessories ----- 01 no(L&T MX 12) iv) 63A 4 pole terminal studs & neutral links- 1 no. v) Necessary connection by copper wire.
S & Drawing 4 x 36/0.3 (2.5 sqmm) + 2 x 22/0.3 (1.5 sqmm) ECC through 25mm steel reinforced pvc flexible conduit.
S & F 25mm PVC flexible conduit pipe gland .
N.B: i) Payment will be made after availability of fund from concern Department. ii) Payment will be made as per P.W.D norms.
AJOY KUMAR DAS (BID ID -6025177)
PAL ELECTRICAL (BID ID -6020333)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .