Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Accepted-Technical | Accepted-Technical Offer as per NIT |
| 2 | Accepted-Technical POWER HOUSE ROAD NEAR OLD FISH MARKET BEGUSARAI BIHAR 851101 | BEGUSARAI | BIHAR | 851101 | Accepted-Technical Offer as per NIT |
| 3 | Accepted-Technical 18 2ND FLOOR EZRA STREET KOLKATA KOLKATA WEST BENGAL 700001 | KOLKATA | WEST BENGAL | 700001 | Accepted-Technical Offer as per NIT |
Tender Value
Refer Docs
EMD Value
₹30,000
Closing Date
23 Jul 2026, 3:00 pmClosed
GM, KTPS
Administrative Building, KTPS PO Mecheda Dist Purba Medinipur Pin 721137
Procurement and retrofitting of 415 Volt Air Circuit Breakers at different locations of EMOPH Department.
2026_WBPDC_1029607_1
WBPDCL/KTPS/NIT/E3968/26-27
Open Tender
Miscellaneous Goods
Buy
90 days
KTPS
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹30,000
Yes
Administrative Building, KTPS
29 Sept 2026
25 Jun 2026
27 Jul 2026
25 Jun 2026
23 Jul 2026
9 Jul 2026
2 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | AIR CIRCUIT BREAKER,3P, 1600A,415V, 50HZ
Additional Data:
Procurement, Supply, Retrofitting, Testing and Commissioning of
415V, 1600A, 3P, 50 HZ Air Circuit Breakers at KTPS,
WBPDCL.
Make: Siemens / ABB / Schneider / L&T / BCH / Havells /
C&S.
Specifications:-
1)Standard: IS 13947-2 or IEC 60947-2
2)ROHS Compliant: Yes
3)Rated Impulse withstand Voltage# Power circuit: 12 KV
4)Rated Impulse withstand Voltage # Auxiliary circuit: 4 KV
5)Rated Insulation Voltage: 1000 V
6)Ambient Temp. Operation: 65 deg. C
7)Frequency: 50HZ
8)Utilization Category: B
9)Protection Level: IP 20
10)Over Voltage Category: IV
11)Pollution Degree: III
12)Reversible Power feed: Yes
13)Rated Current: 1600A @50 deg C
14)No. of Poles: 3 Pole
15)Type: Electrical Draw out(EDO) Type
16)Rated short time withstand Capacity: 65 KA for 1 sec
17)Rated Breaking Capacity: 65 KA
18)Rated making capacity: 143 KA
19)Closing Time: 60 ms (max)
20)Opening time: 40 ms (max)
21)Mechanical Life span: 20000 Operations
22)Electrical Life span: 7000
23)Shunt coil: Required
24)Closing Coil Required
25)Provision of coil supervision:
a) Pre-close trip circuit supervision
b) Post close trip circuit supervision
26)Spring charge motor Voltage: 240 V AC/DC
27)Control voltage: 240 V AC/DC | 8 | NO | - | - |
stage.html
html • 0.02 MB
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.95 MB
BOQ_2528611.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .