Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.4 LAccepted-AOC 58 CHANDRALOK BLDG MAYO HOSPITAL ROAD NAGPUR 440018 | NAGPUR | NAGPUR | MAHARASHTRA | 440018 | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹17.2 L+₹2.4 L (16.4%)Rejected-AOC 21 GURUKRIPA PATIL LAYOUT GOPLA NAGAR NAGPUR 440022 | NAGPUR | NAGPUR | MAHARASHTRA | 440022 | L2 | Rejected-AOC Not the Lowest bidder | |
| 3 | L3₹23.2 L+₹8.4 L (57.0%)Rejected-AOC | L3 | Rejected-AOC Not the Lowest bidder |
Tender Value
Refer Docs
EMD Value
₹60,000
Closing Date
30 Jul 2021, 12:00 pmClosed
CWE NAGPUR
Commander Works Engineers Bldg No. P-9, Sitabuldi Fort, Nagpur-440 001 Pin-900419, C/o 56 APO
REWIRING OF CERTAIN BLDGS AND CONNECTED ITEMS IN GRC AND SUPPLY DEPOT AREA UNDER GE KAMPTEE.
2021_MES_456586_1
84714/E8
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
GE KAMPTEE
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE KAMPTEE
₹60,000
Yes
24 Aug 2021
2 Jul 2021
31 Jul 2021
2 Jul 2021
30 Jul 2021
16 Jul 2021
2 Jul 2021 - 10 Jul 2021
Amount
Taking down point wiring with aluminum conductor cable of light point fan & socket light & power complete including light fittings any type switches, sockets, ceiling rose, switch boards, bell/buzzer, bell push, tube light fitting, regulator etc, and making good to the disturbed surfaces of walls/ floor etc to match with existing surfaces including white washing/colour washing/ distemper to match with existing wall/floor/ceiling finishes complete all as specified and directed.
Taking down sheet metal enclosure DB, MCB, main switch etc and making good disturbed surfaces to match with existing surfaces complete all as specified and directed.
Taking down sub main wiring of any size/ capacity complete all as specified and making good disturbed surfaces to match with the existing surfaces complete all as specified and directed.
M&L point wiring 1100 volt grade single core FRLSH PVC insulated and unsheathed cable with multistranded copper conductor 1.50 sqmm drawn in and including electrical grade PVC conduit not less than 20mm dia with IS 9537 (Part-III) 1983 marked medium grade PVC caping casing on surface of wall/ceiling including FRLSH PVC insulated unsheathed earth wire with multistranded copper conductor of size 1.50 sqmm pressed steel modular boxes sunk on wall for mounting of modular switches, switch sockets, fan regulator etc including modular cover with frame any size complete all as specified and making good disturbed surfaces for one light point controlled by one, one way switch. Note :- Cost of cable provided from sub main DB to respective switch board in rooms shall be included in the quoted point wiring rate. All switches, fan, sockets, ceiling roses and holders shall be connected to common earth dolly.
All as per item No 4 above but One ceiling/exhaust fan point controlled by one switch and regulator complete all as specified and directed.
All as per item No 4 above but One 3 pin 5 amp socket out point on the same board with other switches complete all as specified and directed.
All as per item No 4 above but One 3 pin 5 amps socket out let point on independent board complete all as specified and directed.
All as per item No 4 above but One bell/buzzer point controlled by one bell push complete all as specified and directed.
M&L point wiring 1100 volt grade single core FRLSH PVC insulated and unsheathed cable with multistranded copper conductor 1.50 sqmm drawn in and including electrical grade PVC conduit not less than 20mm dia with IS 9537 (Part-III) 1983 marked medium grade concealed on surface of wall/ceiling including FRLSH PVC insulated unsheathed earth wire with multistranded copper conductor of size 1.50 sqmm pressed steel modular boxes sunk on wall for mounting of modular switches, switch sockets, fan regulator etc including modular cover with frame any size complete all as specified and making good disturbed surfaces for one light point controlled by one, one way switch. Note :- Cost of cable provided from sub main DB to respective switch board in rooms shall be included in the quoted point wiring rate. All switches, fan, sockets, ceiling roses and holders shall be connected to common earth dolly.
All as per item No 9 above but One ceiling /exhaust fan point controlled by one switch and regulator complete all as specified and directed.
All as per item No 9 above but One 3 pin 5 amp socket out point on the same board with other switches complete all as specified and directed.
All as per item No 9 above but One 3 pin 5 amps socket out let point on independent board complete all as specified and directed.
All as per item No 9 above but One bell/buzzer point controlled by one bell push complete all as specified and directed.
All as per item No 9 above but wiring with 2.5 sqmm multi stranded cable and earth wire with copper conductor of size 2.5 sqmm for 15 amps power point complete all as specified and directed.
All as per item No 9 above but wiring with 4.0 sqmm multi stranded cable and earth wire with copper conductor of size 4.0 sqmm for 15 amps power point complete all as specified and directed.
M&L for sub main wiring with two single core PVC FR LSH insulated unsheathed stranded copper conductor and earth wire 1100 volt grade and drawing into PVC conduit not less than 20 mm medium grade concealed in wall of size 2x2.5 Sqmm with earth wire of 1x2.5 Sqmm complete all as specified and directed. Note :- Accessories for point/sub main wiring like PVC junction box, bend, Tee, elbow shall be of same make.
All as per item No 16 above but 2x4.0 Sqmm with earth wire of 1x4.0 Sqmm complete all as specified and directed.
All as per item No 16 above but 2x 6.0 Sqmm with earth wire of 1x6.0 Sqmm complete all as specified and directed.
All as per item No 16 above but 4x 6.0 Sqmm with earth wire of 2x6.0 Sqmm complete all as specified and directed.
All as per item No 16 above but 4x 10 Sqmm with earth wire of 2x10.0 Sqmm complete all as specified and directed.
Supply and fix ceiling rose surface type 2/3 terminal 5 amps complete all as specified and directed.
S&F Bell ding dong, AC 230 volts, single phase complete all as specified and directed.
Supply and fix lamp holder insulated body with back plate for angle/ batten fitting complete all as specified and directed.
Supply and fix Modular switch one way 6A, 1 module complete all as specified and directed.
Supply and fix Modular switch one way 16A, 1 module complete all as specified and directed.
Supply and fix Modular bell push 6A, 1 module complete all as specified and directed.
Supply and fix Modular Socket 6A 2/3 pin combined 2 module complete all as specified and directed.
Supply & Fix Modular Socket 6A/ 16A 2/3 pin combined 2 module complete all as specified and directed.
Supply and fix Modular Fan step regulator,120 watt 2 module complete all as specified and directed.
Supply and Fix Highly durable surface mounted 18/20 watts LED batten/surface constructed of fire retardant engineering grade extruded aluminium body 100 lumen per watt, min 2000 lumen and decorative end cap complete with driver including 3 core 1.0 sqmm copper conductor cable for connection and accessories complete all as specified and directed. Make:- CG LDL-20-CDL /Bajaj /Philips /Luker /Halonix.
Supply & fix light fitting 9W bulk head luminaries with lamp holders etc complete with all accessories and including connecting up with twin core twisted flexible cable suitable size of 230V, 50HZ complete all as specified and directed. Make: CG LBHP-10-CDL/ Philips/ Wipro/ Luker/ Halonix / Bajaj.
Supply & fix fittings with surface mount LED down lighters 12 W including driver with rated voltage 240 V , 50 Hz complete all as specified and directed. Make: CG LCDEP-12-CDL/ Philips/ Wipro/Luker / Bajaj.
Supply and fix Energy efficient surface mounted 2'X2' grid Ceiling LED fitting 36/40 W rated voltage 240 V, 50Hz combination with profiled and flat diffuse complete all as specified and directed. Make : CG LCTLRF6-36-CDL/ Philips/ Wipro/ Luker / Halonix / Bajaj.
Supply and fix LED baton fitting 2' length including drivers having energy consumption, 10/11W ,230 V ,50Hz, 6500K, not less than 800 lumen prewired, complete all as directed by the Engineer-in-Charge. Make : CG LDL-10-CDL/ Philips/ Wipro/ Luker/ Halonix / Bajaj.
Supply and fix building security light LED 25 W with Lumen O/P 1800 with driver with rated voltage 240 V, 50Hz,including mounting GI (made out of 25 mm dia light grade pipe 0.8 m bent two shape including FI clamps nut bolts etc complete all as specified and directed. Make : CG LSTS-25-CDL-M/ Philips/ Wipro/ Luker / Bajaj.
Supply and fix light fitting LED 36W suspended from ceiling including transparent suspension wires, bracket etc and connecting 3 core cable 240V 50Hz complete all as specifed and directed. Make: CG LCLP54-36-CDL / Philips / Wipro / Bajaj.
Supply and Fix LED post top light fitting 40W with all fixing accessories fitted on pilar or poles complete all as specified and directed. Make: CG LPTO-40-CDL /Philips/ Wipro / Bajaj.
Supply and fix electronic LED driver with thermal, short circuit & overload protection for LED 2'x2' grid ceiling light 36/40 W with rated voltage 240 V, 50Hz complete all as specified and directed.
Supply and fix electronic LED driver with thermal, short circuit & overload protection for LED security light 18-25 W with rated voltage 240 V, 50Hz complete all as specified and directed.
Supply and fix electronic LED driver with thermal, short circuit & overload protection for LED down lighter 12 W with rated voltage 240 V, 50Hz complete all as specified and directed.
M&L for cutting & taking out the existing Modular metal flush box with modular cover plate with frame 3 module with switches / sockets and replacing with the following items complete all as specified and directed. Note:- The disturbed surfaces of wall for concealing box wiring shall be made good by applying cement plaster, putty and colour wash etc matching with the existing surfaces. The rate shall be deemed to include the cost of making good. Switches, sockets, regulators etc to be measured and paid separately.
All as per item No 41 above but Modular metal flush box with modular cover plate with frame 4 module complete all as specified and directed.
All as per item No 41 above but Modular metal flush box with modular cover plate with frame 6 module complete all as specified and directed.
Supply and fix sheet metal enclosure single pole & neutral for 240 volts 4/6 way with 200 Amp rated bus bar flush /surface mounting double door, complete all as specified and directed.
Supply and fix sheet metal enclosure single pole & neutral for 240 volts 8 way with 200 Amp rated bus bar flush /surface mounting double door complete all as specified and directed.
Supply and fix sheet metal enclosure triple pole & neutral for 415 volts 4 way with 200 Amp rated bus bar flush /surface mounting double door complete all as specified and directed.
Supply and fix sheet metal enclosure vertical triple pole & neutral(VTPN) with MCCB 63 amps for 415 volts 4 way with 200 Amp rated bus bar flush /surface mounting double door complete all as specified and directed.
Supply and fix MCB single pole 240 volt 6 to 40 amps 10 KA breaking capacity, 'C' series complete all as specified and directed.
Supply and fix MCB single pole and neutral 240 volt 6 to40 amps 10 KA breaking capacity, 'C' series, complete all as specified and directed.
Supply and fix MCB triple pole and neutral 415 volt 40 to 60 amps 10 KA complete all as specified and directed.
M&L for earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground (earth plate not less than 2.25mtr deep below normal ground level) with top edge of the plate not less then 1.50 mtr. below the normal ground level connected to galvanized earth lead wire 4.00 mm dia by means of bolts nuts check nuts & washer of galvanized iron or steel all as shown in electrical plate No 5 connected to earthing test point all as specified and testing on completion including the material and labour for:- (a) Excavation and earth work or drilling hole for electrode in any type of soil (b) PCC pit in cement concrete (1:2:4) type B-1 (c) Pre cast RCC cover with suitable handle 40mm thick in PCC (1:2:4) reinforced with welded steel wire fabric weighting not less than 1.87 Kg/sqmm (d) Funnel with watering pipe of GI 20mm nominal bore medium grade and Aluminum lugs etc all as specified. (e) 15mm nominal bore medium grade GI protection pipe up to 7.50 meter long for protection of earthing lead. (f) Requisite quantity of charcoal and common salt. (g) Connection to earthing test point and testing on completion.
NOTE:- SCHEDULE OF CREDIT (Amount shall be deducted offline from the total quoted amount to workout the net contract sum to be considered for acceptance.) [(-) Rs.37,585.00.00]
Asha Enterprises
MVN Enterprises
Bidder Name
Paragon Electrotechnics
MVN Enterprises
Asha Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .