GE NW KARANJA
NAVAL STATION KARANJA, URAN, RAIGAD, MAHARASHTRA
REPAIR REPLACEMENT AND IMPROVEMENT OF EXISTING LT PANEL SUB PANEL CONTROL CABLES DBS MCCBS MCBS CONTACTOR TIMER VOLTMETER AMMETER ARMOURED CABLE AND EARTHINGS WITH CONNECTED ACCESSORIES AND ALLIED WORKS OF E/M-II AC PLANT INSTALLATION UN
2026_MES_769989_1
8333/E8
Open Tender
Civil Works
270 days
GE NW KARANJA
Class D and above and category b (i)
8 documents required · 8 mandatory
₹500
Yes
GE NW KARANJA
₹98,000
Yes
5 Jun 2026
5 Jun 2026
29 Jun 2026
5 Jun 2026
27 Jun 2026
20 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, commissioning and testing of factory made, CPRI type tested, indoor, cubical compartmental type HVAC Panel in replacement of HVAC Panel DBM 16 AC plant suitable size, having both sides openable with hinged double doors & locking arrangement and IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete with accessories as and as directed by Engineer-in-charge, Make: CPRI approved panel builder. The HVAC Panel shall comprising of the following provisions:-
Bus bar Chamber:
INCOMER:-
[i] 01 Set (3L + N) of copper bus bar of rated capacity 320 Amp, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection Incoming:[ii] 250 A, 415 V, Ics = 100% Icu = 26 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having thermal magnetic based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos.
[ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Run hrs. On hrs & interupts01 Nos.
[iii] LED phase indicators (Red, Yellow, Blue) - 01 Set
Outgoing:
[i] 100 A, 415 V, Ics = Icu = 16 kA, conforming to IEC 60947- 2, 50 Hz, FP MCCB with adjustable thermal settings & fixed magnetic settings with compression lug connectors and thermal magnetic trip unit (TMD)- 03 Nos. [for chillers] | 1 | Each Job | - | - |
| 1.01 | BoQ Serial Item No.1.00 Contd -
[ii] 63 A, 415 V, Ics = Icu = 16 kA, conforming to IEC 60947- 2, 50 Hz, FP MCCB with adjustable thermal settings (0.70- 1 X In) & fixed magnetic settings with compression lug connectors and thermal magnetic trip unit (TMD)- 01 Nos. [for AHU]
[iii] 25 A, 415 V, Ics = Icu = 16 kA, conforming to IEC 60947- 2, 50 Hz, FP MCCB with adjustable thermal settings & fixed magnetic settings with compression lug connectors and thermal magnetic trip unit (TMD)- 02 Nos. [for condenser pump]
(iv) 20 A, 415 V, Ics = Icu = 16 kA, conforming to IEC 60947- 2, 50 Hz, FP MCCB with adjustable thermal settings & fixed magnetic settings with compression lug connectors and thermal magnetic trip unit (TMD)- 03 Nos. [for Cooling tower & 02 Spare]
(v) Fully automatic DOL starter, complete with contactors, push button, LED type indicators, auto/manual selector switch, overload protection, current sensing type single phase preventer complete with all accessories and wiring etc-total 01 Nos. (Cooling tower motor capacity 3 HP - 01 Nos)
(vi) Fully automatic Star Delta Starter, complete with contactors, push button, LED type indicators, auto/manual selector switch, overload protection, current sensing type single phase preventer complete with all accessories and wiring etc-total 02 Nos (condenser pump capacity 5 HP - 02 No)
[vii] LED phase indicators (Red, Yellow, Blue)- 8 Set , [viii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Run hrs. On hrs & interupts10 Nos. | - | - | - | - |
Supply, installation, commissioning and testing of factory made, CPRI type tested, indoor, cubical compartmental type HVAC Panel in replacement of HVAC Panel DBM 17 AC plant suitable size, having both sides openable with hinged double doors & locking arrangement and IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete with accessories as and as directed by Engineer-in-charge, Make: CPRI approved panel builder. The HVAC Panel shall comprising of the following provisions:-
Bus bar Chamber:
INCOMER:- [i] 01 Set (3L + N) of copper bus bar of rated capacity 320 Amp, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection Incoming:[ii] 250 A, 415 V, Ics = 100% Icu = 26 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having thermal magnetic based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Run hrs. On hrs & interupts01 Nos. [iii] LED phase indicators (Red, Yellow, Blue) - 01 Set
Outgoing:
[i] 125 A, 415 V, Ics = Icu = 16 kA, conforming to IEC 60947- 2, 50 Hz, FP MCCB with adjustable thermal settings & fixed magnetic settings with compression lug connectors and thermal magnetic trip unit (TMD)- 02 Nos. [for chillers] | 1 | Each Job | - | - | |
| 2.01 | BoQ Serial Item No.2.00 Contd -
[ii] 63 A, 415 V, Ics = Icu = 16 kA, conforming to IEC 60947- 2, 50 Hz, FP MCCB with adjustable thermal settings (0.70- 1 X In) & fixed magnetic settings with compression lug connectors and thermal magnetic trip unit (TMD)- 01 Nos. [for AHU]
[iii] 40 A, 415 V, Ics = Icu = 16 kA, conforming to IEC 60947- 2, 50 Hz, FP MCCB with adjustable thermal settings & fixed magnetic settings with compression lug connectors and thermal magnetic trip unit (TMD)- 02 Nos. [for condenser pump]
(iv) 20 A, 415 V, Ics = Icu = 16 kA, conforming to IEC 60947- 2, 50 Hz, FP MCCB with adjustable thermal settings & fixed magnetic settings with compression lug connectors and thermal magnetic trip unit (TMD)- 03 Nos. [for Cooling tower & 02 Spare]
(v) Fully automatic DOL starter, complete with contactors, push button, LED type indicators, auto/manual selector switch, overload protection, current sensing type single phase preventer complete with all accessories and wiring etc-total 01 Nos. (Cooling tower motor capacity 3 HP - 01 No.)
(vi) Fully automatic Star Delta Starter, complete with contactors, push button, LED type indicators, auto/manual selector switch, overload protection, current sensing type single phase preventer complete with all accessories and wiring etc-total 02 Nos. (condenser pump capacity 10 HP - 02 No)
[vii] LED phase indicators (Red, Yellow, Blue)- 8 Set
[viii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Run hrs. On hrs & interrupts 8 Nos. | - | - | - | - |
Supply, installation, commissioning and testing of factory made, CPRI type tested, indoor, cubical compartmental type HVAC Panel in replacement of HVAC Panel HTL 05 AC plant suitable size, having both sides openable with hinged double doors & locking arrangement and IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete with accessories as and as directed by Engineer-in-charge, Make: CPRI approved panel builder. The HVAC Panel shall comprising of the following provisions:- Bus bar Chamber:
INCOMER:-
[i] 01 Set (3L + N) of copper bus bar of rated capacity 320 Amp, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection Incoming:[ii] 250 A, 415 V, Ics = 100% Icu = 26 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having thermal magnetic based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos.
[ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Run hrs. On hrs & interupts01 Nos.
[iii] LED phase indicators (Red, Yellow, Blue) - 01 Set
Outgoing:
[i] 100 A, 415 V, Ics = Icu = 16 kA, conforming to IEC 60947- 2, 50 Hz, FP MCCB with adjustable thermal settings & fixed magnetic settings with compression lug connectors and thermal magnetic trip unit (TMD)- 03 Nos. [for chillers] | 1 | Each Job | - | - | |
| 3.01 | BoQ Serial Item No.3.00 Contd -
[ii] 63 A, 415 V, Ics = Icu = 16 kA, conforming to IEC 60947- 2, 50 Hz, FP MCCB with adjustable thermal settings (0.70- 1 X In) & fixed magnetic settings with compression lug connectors and thermal magnetic trip unit (TMD)- 01 Nos. [for AHU]
[iii] 25 A, 415 V, Ics = Icu = 16 kA, conforming to IEC 60947- 2, 50 Hz, FP MCCB with adjustable thermal settings & fixed magnetic settings with compression lug connectors and thermal magnetic trip unit (TMD)- 02 Nos. [for condenser pump]
(iv) 20 A, 415 V, Ics = Icu = 16 kA, conforming to IEC 60947- 2, 50 Hz, FP MCCB with adjustable thermal settings & fixed magnetic settings with compression lug connectors and thermal magnetic trip unit (TMD)- 03 Nos. [for Cooling tower & 02 Spare]
(v) Fully automatic DOL starter, complete with contactors, push button, LED type indicators, auto/manual selector switch, overload protection, current sensing type single phase preventer complete with all accessories and wiring etc-total 01 No. (Cooling tower motor capacity 3 HP - 01 No.)
(vi) Fully automatic Star Delta Starter, complete with contactors, push button, LED type indicators, auto/manual selector switch, overload protection, current sensing type single phase preventer complete with all accessories and wiring etc-total 02 Nos. (condenser pump capacity 5 HP - 02 No)
[vii] LED phase indicators (Red, Yellow, Blue)- 8 Set
[viii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Run hrs. On hrs & interupts10 Nos. | - | - | - | - |