Construction of External Electrical Work at National Law University, Odisha.
NBCC/SBG/OD/CG/NLUO/NIT/23-24/17
NBCC/SBG/OD/CG/NLUO/NIT/23-24/17
Open Tender-Domestic
Electrical Work
Patiala, Punjab
₹11,800
₹5.4 L
29 Jan 2024
15 Jan 2024
29 Jan 2024
29 Jan 2024
14 Mar 2024
PROJECT NAME:- NATIONAL LAW UNIVERSITY, AT CUTTACK
DSR20 DESCRIPTION
A. 11KV H.T. PANEL
11kV Single HT Panel Board Used for Isolation Located Near
Meter Room (In Indoor Cubical)
Design, Manufacture, Supply at site, inspection of
Consultant's/client at Factory at your cost,Receiving, unloading
& shifting to Sub-Station, storing, inspection of
Consultant's/client at site, handling, installing in correct
aligned position, on existing foundation, testing and
commissioning of 11KV, 50Hz, in extensible type Indoor
Cubical (IP 4X As per IS 3427:1969/IEC 298), free standing
metal clad vaccum circuit breaker HT switchgear including
suitable raiting protection relays, indications, push buttons,
Toggle Switch copper busbars, Door earthed, Handle For
breaker Spring Charging, etc. as per the requirement detailed
in BOQ / SLD and engineer incharge etc. complete as required.
The Panel shall be fabricated with CRCA sheet steel enclosure
used for Side Sheet, Partition, removable Top/Bottom, Doors
Sheet 2mm and 3mm for Removable Gland Plate & Base
Frame. The Panel Shall be electro static powder coating paint
(80-100 micron) with RAL 7035 Shade
630A, 11kV, Isc 21kA for 3Sec., TP Electrically operated
horizontal draw type Vacuum cicuit braker with, Auxilary
contact minimum 4NO+4NC, 240V AC spring charge motor,
trip free, dust & vermin proof, 24V DC Closing & Tripping Coil,
Safety Shutter. Confirming to IEC 62271-100
Bus Bars- 60 x 10 Copper (3 Phase) + 30 x 6 Copper (Earth)
Anti Pumping Relay, Master Trip Relay & Trip circuit
supervision relay.
Power Pack Input - 220V AC input and Output-24V DC with
battery back for minimum 4/5 operation of circuit breaker.
A set of breaker ON / OFF / Trip / DC control supply / Trip
circuit healthy / Spring Charged & R, Y, B phase indication LED
Emergency trip push button
Limit switches with 2NO + 2NC breaker auxiliary contacts
Control:- T-N-C ( Trip, Neutral, Close ) breaker control switch
with indication arrangement.
All control wiring with protection & test terminal block as
required. The Control wiring sizes- 2.5 Sqmm, for Phases +
Neutral + DC Control circuit + CT wire and PT Wire 1.5 Sqmm
& Earth 4.0 Sqmm Cu Flexible.
100 Watts Strip heater, auxilary Supply- 110 Volts AC with
thermostat range - minimum 02 - 105 Degree celsius Stem
type for moisture absorption.
Suitable for connection to 3C x 240 sq.mm. Cross linked
polythelene(XLPE) 11kV cables or as called for.
Danger Plate, LED bulb with holder connected to a toggle
switch for each door open
11kV SINGLE PANEL BOARD (FOR ISOLATION CIRCUIT) - AS
DESCRIBED ABOVE.
2 11kV THREE HT Panel Board. (In Outdoor Cubical)
Design, Manufacture, Supply at site, inspection of
Consultant's/client at Factory at your cost,Receiving, unloading
& shifting to Sub-Station, storing, inspection of
Consultant's/client at site, handling, installing in correct
aligned position, on existing foundation, testing and
commissioning of 11KV, 50Hz, In extensible type Outdoor
Cubical (IP: 5X As per IS 3427:1969/IEC 298), free standing
metal clad vaccum circuit breaker HT switchgear including
suitable raiting protection relays, indications, push buttons,
Toggle Switch copper busbars, Door earthed, Handle For
breaker Spring Charging, etc. as per the requirement detailed
in BOQ / SLD etc. complete as required. The Panel shall be
fabricated with CRCA sheet steel enclosure used for Side
Sheet, Partition, removable Top/Bottom, Doors Sheet 2mm
and 3mm Removable Gland Plate & Base Frame. The Panel
Shall be electro static powder coating paint (80-100 micron)
with RAL 7035 Shade
Digitally signed by Rakesh
DSR20 DESCRIPTION
630A, 11kV, 21kA for 3Sec., TP Electrically operated
horizontal draw type Vacuum cicuit braker with, Auxilary
contact minimum 4NO+4NC, 240V AC spring charge motor,
trip free, dust & vermin proof, 24V DC Closing & Tripping Coil,
Safety Shutter. Confirming to IEC 62271-100
Bus Bars- 60 x 10 Copper (3 Phase) + 30 x 6 Copper (Earth)
Current Transformer - 3Nos. Resin Filled Nylon 66 Casing
double wound Single Phase CT for 1000KVA Transformer. BIL :
Suitable for Altitude of Less than 1000Meter, Core-1 :15 VA,
Class 0.5 For Metering and Core- 2:15 VA, Class- 5P10 For
protection. CT Ratio
Potential transformers- 3Nos. Single Phase, Epoxy resin cast
drawout type, PT Ratio 11KV / (Root 3) /110VAC / (Root 3)
ratio class 0.5 accuracy, minimum 200 VA burden, feeder
connected HV fuse on primary side and MCB on secondary
110Volts Tri-Vector Meter with Import/Export, Demand &
RS485 Port Similar to Enersol make Model Number TVMR 5105
IDMT self power relay with 3 elements for over current (50-
200%) and 1 element for earth fault protection (10-40%)
Anti pumping relay-VAA11, Master Trip relay-VAJH 13, Trip
circuit supervision relay & Non Communicable Numercial relay
A set of breaker R, Y, B phase indication LED lamps with
control Fuse/MCB
Emergency trip push button
Limit switches with 2NO + 2NC breaker auxiliary contacts
Control:- T-N-C ( Trip, Neutral, Close ) breaker control switch
with indication arrangement.
OUTGOING- 2 Nos
630A, 11kV, 21kA for 3Sec., TP Electrically operated
horizontal draw type Vacuum cicuit braker with, Auxilary
contact minimum 4NO+4NC, 240V AC spring charge motor,
trip free, dust & vermin proof, 24V DC Closing & Tripping Coil,
Safety Shutter. Confirming to IEC 62271-100
Bus Bars- 60 x 10 Copper (3 Phase) + 30 x 6 Copper (Earth)
Current Transformer - 3Nos. Resin Filled Nylon 66 Casing
double wound Single Phase CT for 1000 KVA Transformer. BIL
: Suitable for Altitude of Less than 1000Meter, Core-1 :15 VA,
Class 0.5 For Metering and Core- 2:15 VA, Class- 5P10 For
protection. CT Ratio
110Volts Multi-Functional Meter
IDMT self power relay with 3 elements for over current (50-
200%) and 1 element for earth fault protection (10-40%)
Anti pumping relay-VAA11, Master Trip relay-VAJH 13, Trip
circuit supervision relay & Non Communicable Numercial relay
3 Nos. Auxiliary relays for transformer faults WTI, OTI and
8 window annunciator with hooter.
(2 Window for over Current & Earth fault)
(2 Window for OTI alarm & Trip)
(2 Window for WTI alarm & Trip)
(2 Window Bucholz alarm & Trip)
Emergency trip push button
Limit switches with 2NO + 2NC breaker auxiliary contacts
Control:- T-N-C ( Trip, Neutral, Close ) breaker control switch
with indication arrangement.
GENERAL COMMON FOR WHOLE PANEL
Power Pack Input - 110V AC, Output-24V DC with Battery back
up of minimum 4 operation of circuit breaker. The Power pack
shall connected on output of PT or Auxilary transformer shall
All control wiring with protection & test terminal block as
required. The Control wiring sizes- 2.5 Sqmm, for Phases +
Neutral + DC Control circuit + CT wire and PT Wire 1.5 Sqmm
& Earth 4.0 Sqmm Cu Flexible.
Digitally signed by Rakesh
DSR20 DESCRIPTION
TVSS 6 Mode with Fuse protection
A set of breaker ON / OFF / Trip / DC control supply / Trip
circuit healthy / Spring Charged with control fuse/MCB
100 Watts Strip heater, auxilary Supply - 110 Volts AC with
thermostat range - minimum 02 - 105 Degree celsius Stem
type for moisture absorption.
Suitable for connection to 3C x 240sq.mm. Cross linked
polythelene(XLPE) 11kV cables or as called for.
Danger Plate, LED bulb with holder connected to a toggle
switch for each door open
MR 11kV THREE PANEL BOARD - AS DESCRIBED ABOVE. Set 1.00 1500000.00 1500000.00
B. TRANSFORMERS
11kV/0.433kV ONAN WITH OFF LOAD TAP CHANGER WITH
BUCHHOLZ, OTI , WTI RELAYs
Design, Manufacture, Supply at site, inspection of
Consultant's/client at Factory at your cost,Receiving, unloading
& shifting to Sub-Station, storing, inspection of
Consultant's/client at site, handling, installing in correct
aligned position, on existing foundation, testing and
commissioning of 1000kVA continuous duty cycle,
11kV/0.433kV, 3 phase, 50Hz, Dyn-11 vector group, step
down, outdoor type, copper wound, ONAN type transformers
with Off Load Tap changer & with all fixing accessories
including complete as per specifications. Tap changing range
shall be +5% to -10% in steps of 2.5%. Class 'A' of
Thermal insulation Suitable for Ambient temperature 45 º C.
Maximum winding temprature 105º C
The Following Fittings Shall Be provided with all required
accessories:- Rating & Terminal Marking Plate, Earthing
Terminals, Lifting Lugs For Main Tank & Top Cover, Filter Valve
, Drain Cum Sampling Valve, Thermometer Pocket, Dial Type
Oil Temperature Indicator, Air Release Plug, Silica Gel
Breather, oil conservator, Explosion Vent, Inspection Cover,
Arcing Horn, Radiators Mounted on Tank, 4 Nos. bi-directional
Rollers, First Filling of Transformer Oil as per IS:335, Magnetic
Oil Level Gauge, Buchholz Relay, Oil Temperature Indicator,
Winding Temperature Indicator, Marshalling Box, Epoxy
Bushing, PU Paints, Palm, LV Bus Bar, Radiator Valves, Cable
Box on LT side & Cable Box on HT side. Transformer shall
Compliance to IS:1180 Level-1 & IS:2026 all parts latest as
on date whichever is higher. complete with all accessories
The transformer shall be delivered along with after complete
factory tests and temprature rise test, Operational &
MR Maintenance manual and test certificate of unconditional Set 2.00 2000000.00 4000000.00
guaranteed against manufacturing defects for a period of 18
months from the date of supply.
C. DIESEL GENERATORs
1 DIESEL GENERATOR SET-200kVA
Providing, Installing, Testing and Commissiong of 'Silent Type'
Diesel Generating set alongwith Prime Power Rating 200KVA
as per CPCB 4+ , 415 volts at 1500 RPM, 0.8 lagging power
factor at 415V suitable for 50 Hz, 3 phase system & for 0.80
Load Factor and consisting of the followings:
i. Diesel Engine:
Diesel engine 4 stroke radiator Cooled, electric start, of
suitable BHP at 1500 RPM suitable for above output of
alternator at 50 Degree C, 50% RH & at 1000 Meter MSL and
conforming to BS 5514, BS 649, IS 10000, capable of taking
10% over loading for one hour after 12 hours of continous
operation. The engine will be fitted complete with electronic
Governer and all the required accessories.
Engine mounted Instrument Panel fitted with and having digital
display for following:
(i) Start-stop switch with key
(ii) Water temperature indication
(iii) Lubrication oil pressure indication
(iv) Lubrication oil temperature indication
(v) Battery charging indication
(vi) RPM indication
(vii) Over speed indication
(viii) Low lub. Oil trip indication
Digitally signed by Rakesh
DSR20 DESCRIPTION
(ix) Engine Hours indication
(x) Engine protection unit and sensors for winding & bearing
temperature monitoring
(xi) 400Amp, 4P MCCB for isolation
iii. Alternator
Synchronous alternator rated at 200KVA, 415 volts at 1500
RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor
at 50 Degree C, 50% RH & at 1000 Meter MSL. The alternator
shall be having microprocessor based controller with BMS
compatibility, SPDP enclosure, brushless, continuous duty,
self-excited and self-regulated through AVR conforming to IS:
4722/BS 2613 suitable for tropical conditions and with class-
F/H insulation.
Cable termination Box suitable to receive 1No. 3.5 core x 240
Sqmm XLPE Al. Ar. Cable.
iv. Base Frame & Foundation:
Both the engine and alternator shall be mounted on suitable
base frame made of MS channel with necessary reinforcement
which shall be installed on suitable cement concrete foundation
and antivibration mountings arrangement as per
recommendations of manufacturer.
v. Fuel Tank: (Internal)
Daily service fuel tank of suitabe capacity as per manufacture
standard fabricated out of minimum 1.5/2 mm thick
M.S./CRCA sheet complete with all standard accessories and
fuel piping between fuel tank and diesel engine with MS class
'C' pipes of suitable dia. Complete with valves, level indications
& accessories as required as per specifications.
vi. Exhaust System:
Dry exhaust mainfold with hospital exhaust silencer.
vii. Starting System:
DC starting system comprising of starter motors: voltage
regulator and arrangement for initial excitation complete 12V
with suitable nos. of batteries with suitabe capacity as per
manufacture standard SMF lead acid type as required as per
specifications.
Accoustic for weather and noice proof enclosure with
arrangement for fresh air intake for cooling of the engine &
viii. MR alternator, extraction, discharging hot air in to the atmosphere Set 1.00 1400000.00 1400000.00
as per CPCB-II norm & technical specifications.
2 DIESEL GENERATOR SET-400kVA
Providing, Installing, Testing and Commissiong of 'Silent Type'
Diesel Generating set alongwith Prime Power Rating 400 KVA
as per CPCB 4+, 415 volts at 1500 RPM, 0.8 lagging power
factor at 415V suitable for 50 Hz, 3 phase system & for 0.80
Load Factor and consisting of the followings:
i. Diesel Engine:
Diesel engine 4 stroke radiator Cooled, electric start, of
suitable BHP at 1500 RPM suitable for above output of
alternator at 50 Degree C, 50% RH & at 1000 Meter MSL and
conforming to BS 5514, BS 649, IS 10000, capable of taking
10% over loading for one hour after 12 hours of continous
operation. The engine will be fitted complete with electronic
Governer and all the required accessories.
Engine mounted Instrument Panel fitted with and having digital
display for following:
(i) Start-stop switch with key
(ii) Water temperature indication
(iii) Lubrication oil pressure indication
(iv) Lubrication oil temperature indication
(v) Battery charging indication
(vi) RPM indication
(vii) Over speed indication
(viii) Low lub. Oil trip indication
(ix) Engine Hours indication
(x) Engine protection unit and sensors for winding & bearing
temperature monitoring
iii. Alternator
Digitally signed by Rakesh
DSR20 DESCRIPTION
Synchronous alternator rated at 400KVA, 415 volts at 1500
RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor
at 50 Degree C, 50% RH & at 1000 Meter MSL. The alternator
shall be having microprocessor based controller with BMS
compatibility, SPDP enclosure, brushless, continuous duty,
self-excited and self-regulated through AVR conforming to IS:
4722/BS 2613 suitable for tropical conditions and with class-
F/H insulation.
Cable termination Box suitable to receive 2No. 3.5 core x 240
Sqmm XLPE Al. Ar. Cable.
iv. Base Frame & Foundation:
Both the engine and alternator shall be mounted on suitable
base frame made of MS channel with necessary reinforcement
which shall be installed on suitable cement concrete foundation
and antivibration mountings arrangement as per
recommendations of manufacturer.
v. Fuel Tank: (Internal)
Daily service fuel tank of suitabe capacity as per manufacture
standard fabricated out of minimum 1.5/2 mm thick
M.S./CRCA sheet complete with all standard accessories and
fuel piping between fuel tank and diesel engine with MS class
'C' pipes of suitable dia. Complete with valves, level indications
& accessories as required as per specifications.
vi. Exhaust System:
Dry exhaust mainfold with hospital exhaust silencer.
vii. Starting System:
DC starting system comprising of starter motors: voltage
regulator and arrangement for initial excitation complete 12V
with suitable nos. of batteries with suitabe capacity as per
manufacture standard SMF lead acid type as required as per
specifications.
Accoustic for weather and noice proof enclosure with
arrangement for fresh air intake for cooling of the engine &
viii. MR alternator, extraction, discharging hot air in to the atmosphere Set 2.00 2800000.00 5600000.00
as per CPCB-II norm & technical specifications.
3 D.G. EXHAUST PIPE
Supplying and fixing of exhaust gas piping for horizontal &
Vertical run of suitable dia. for following rating D.G. Set welded
black MS, 'B' Class pipe conforming to IS:3589 cut to required
lengths and installed with necessary bends, supports and
clamps, anti-vibration mountings, the work include necessary
cladding of exhaust pipe work using wiremesh, 50mm thick
Loosely bound resin(LBR)mattress / mineral wool/ Rockwool,
density not less than 150kg/m and aluminium cladding
(0.6mm thick min.) for temperature up to 450 ° C, complete
portion complete as required as per specifications.
Note- Contractor / Vendor to check the diameter of the
exhaust pipes w.r.t. back pressure calculations & confirm the
exhaust pipe sizes & suggest changes if required. This is to be
done before supply of material / at the time of tendering. The
contractor to measure actual pipe lengths as per site
conditions & then confirm the suitability of pipe dia meters
supported by back pressure calculations.
4 INSULATION OF SILENCER
Supplying and fixing of insulation around the silencer including
necessary cladding work using wiremesh, 50mm thick Loosely
bound resin(LBR)mattress / mineral wool/ Rockwool, density
not less than 150kg/m and aluminium cladding (0.6mm thick
min.) for temperature up to 450°C, complete portion complete
as required as per specifications.
5 CORRUGATED BELLOW
Supplying & fixing of Stainless Steel Expansion Joints,
Corrugated bellow of following dia meter to fit in exhaust pipe.
Digitally signed by Rakesh
DSR20 DESCRIPTION
6 STRUCTURE FOR EXHAUST PIPING
Providing, febrication & fixing for MS support structure
including civil foundation for exhaust fume pipes upto 30m
high from ground level and from DG Sets (Exhaust pipe to be
measured and paid for separately) along horizontal and
vertical runs as per soil testing as per the soil test report and
monkey ladder upto the height (In case of when exhaust pipe
far from the building) including cutting, welding etc and
applying two coats of red oxide and two coats of synthetic
a MR enamelled paint of colour and shade as directed by Engineer/ Kg 20000.00 205.00 4100000.00
Client/ Authority. The design of the support structure shall be
done by the D.G. Manufecture/contractor and shall be as per
CPCB norms-II including 300MM Long lightning arrestor on
top, 20x3 mm G.I. down strips mount on insulator and aviation
light including wiring and connections from near by D.B..
Design shall be got approved from the Engineer/ Client/
Authority before execution as required.
Note: The quantity taken is tentative actual shall be checked
by a civil/ Structure engineer.
7 EXTERNAL FUEL TANK
Supply and installation of day oil tank of 990 liter capacity
fabricated out of 2.5mm thick M.S. sheet complete with all
standard accessories and fuel piping between fuel tank and
MR diesel engine with M.S. class 'C' pipe of suitable dia complete Set 3.00 48000.00 144000.00
with valves, oil level indications & accessories as required as
per specification.
TOTAL CARRIED SUMMARY
D. SAFETY EQUIPMENTS
Providing & fixing in position 1000 mm wide , Electrical
Insulating Mats as per IS 15652:2006, 2mm thick, suitable
1 MR upto 3.3 KV , fire retardant, no effect of acids, alkalies and RM 20.00 1250.00 25000.00
transformer oils, moisture proof, high tensile strength and
texture finish / cloth impression (Anti slip , marking on top) .
Providing and fixing M.V. danger notice plate of 200 mm X 150
2 2.21 mm, made of mild steel, at least 2 mm thick, and vitreous Nos. 5.00 269.00 1345.00
enameled white on both sides, and with inscription in single
red colour on front side as required.
Supply and fixing of Shock treatment chart duly mounted on a
3 MR wooden frame with glass on, as required in 2 languages (Hindi Each 1.00 350.00 350.00
Providing and fixing H.T. danger notice plate of 250 mm X 200
4 2.22 mm, made of mild steel, at least 2 mm thick, and vitreous Each 5.00 292.00 1460.00
enameled white on both sides, and with inscription in single
red colour on front side as required.
TOTAL CARRIED SUMMARY
E. EARTHING SYSTEM
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm
thick including accessories, and providing masonry enclosure
1 5.4 with cover plate having locking arrangement and watering pipe Set 29.00 7472.00 216688.00
of 2.7 Meter long etc. with charcoal/ coke and salt as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm
thick including accessories, and providing masonry enclosure
2 5.6 with cover plate having locking arrangement and watering pipe Set 11.00 13838.00 152218.00
of 2.7 Meter long etc. with charcoal/ coke and salt as required.
Providing and fixing 50 mm X 6 mm copper strip in 40 mm dia
3 MR G.I. pipe from earth electrode including connection with brass Meter 66.00 2945.00 194370.00
nut, bolt, spring, washer excavation and re-filling etc. as
Providing and fixing 50 mm X 6 mm G.I. strip in 40 mm dia
4 MR G.I. pipe from earth electrode including connection with G.I. Meter 143.00 1145.00 163735.00
nut, bolt, spring, washer excavation and re-filling etc. as
Providing and fixing 32 mm X 6 mm G.I. strip in 40 mm dia
5 MR G.I. pipe from earth electrode including connection with G.I. Meter 231.00 930.00 214830.00
nut, bolt, spring, washer excavation and re-filling etc. as
Digitally signed by Rakesh
DSR20 DESCRIPTION
Excavation for earthing Pit in soft soil, depth upto 3.6 m
MR/ including dressing of sides lift up as required, including getting
6 REFER out the excavated soil, refilling with sand and or good soil after cum 52.00 654.00 34008.00
14.4 laying of earthing pit material etc, ramming, watering and
disposal of surplus excavated soil as directed.
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia
7 5.1 G.I. pipe from earth electrode including connection with brass meter 33.00 1551.00 51183.00
nut, bolt, spring, washer excavation and re-filling etc. as
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia
8 5.11 G.I. pipe from earth electrode including connection with G.I. meter 33.00 706.00 23298.00
nut, bolt, spring, washer excavation and re-filling etc. as
Providing and fixing 6 SWG dia G.I. wire on surface or in
recess for loop earthing as required.
TOTAL CARRIED SUMMARY
F. M.V. PANELs
Design, Manufacture, Supplying, Transport to the site,
Receiving, Unloading, Shifting to Sub-Station at various
locations, handling, assembling, installation in correct aligned
position, grouting with dash fasteners, GI nuts-bolts, testing
and commissioning of the following bolted fabricated in
compartmentalized (Form-3B construction) conform to IS:
8623/1993, Suitable for 415V, 3Phase, 4 Wire 50 Hz Ac
supply, are housed in design from CRCA sheet steel of 2mm
thick for frame work and door covers, 3mm thick for gland
plate, i/c cleaning & finishing complete, having extensible type
1 bus bars of high conductivity, SMC bus bar supports, the
maunfacturer shall be certified from CPRI for short circuit
withstand capacity of min. 70kA for 1 Sec., fabrication shall be
done in transportable sections and all front and back doors
shall be hinged type and earth with frame, Entire panel shall
have a common earth bar as specified below at the rear with 2
Nos. earth stud each side, bus bars and control wiring with
suitable size of FRLS PVC insulated copper conductor cable,
cable alleys, cable gland plates in two half, i/c providing
following switch gears :-
The Bus bars will be Copper purity 99.9% / electrolytic grade
E91 Aluminium duly sleeved with Helogen Free heat shrink
coloured Insulated tube confirming to IEC 60684-3-247
Standard. The powder coating (70-80micron as per IS:13871
for indoor and 100-120 micron for outdoor), include one size
higher terminal block in cable alley and interconnecting wires
between bus bars and terminals via MCB.
General Notes for site visit report for Panels before submitting
The Manufacturer must visit the site before submitting GA
drawings and submit a report consisting following:
i. Possible height for Panel.
ii Possible width for Panel
iii Back access will be possible or not.
iv Cable entry will be from top or bottom.
If entry from bottom whether MS. Stand is required or not.
If the panel is wall mounted whether the wall is available or
Path for movement of transportation of panel is possible or not
vii i.e length, width etc. and the transportation sections shall be
designed accordingly.
Sufficient space available at front & back after door opening.
ix Sufficient height available above panel for cable drop.
x Actual floor to floor height for rising mains.
Also, refer to General Notes and Specifications for Panels/
All Panels shall be considered Indoor type unless specified.
Digitally signed by Rakesh
DSR20 DESCRIPTION
The degree of protection for all indoor type panels shall be of
IP:52 ("5" Indicates Dust Protected limited ingress of dust
permitted. Will not interefere with operation of the equipment
and "2" indicates protection against vertically falling drops of
ii water with enclosure tilted upto 15 deg from vertical.) and all
outdoor type panels shall be of IP:55 ("5" indicates Dust
Protected limited ingress of dust permitted. Will not interefere
with operation of the equipment and "5" indicates protection
against jets of water)
Provide thermostat controlled panel mounted heavy duty
iii exhaust fan in each Vertical for all Main L.T Panel and
Capacitor Panels. For all other panels a proper ventilation
louvers shall be provided.
Fully automtic control thermotate with strip heater shall be
iv provide in each Bus-Bar alley and relay compartments to
control the humidity
Contractor to submit manufacturer's selection charts from
approved list of make along with each component part
v number, Discrimination check certificate throughout the HV/MV
network, insulation material & corners cover on bus-bars for
Contractor shall submit a set of handing over document
consisting operational and maintenance manuals, installation
guidelines of all product's along with data sheets come with
vi product, GA drawings with wiring diagram and product part
code etc. shall be arranged and also place a laminated copy in
a pocket inside the respective panel body.
If mentioned fault rating of bus-bar and circuit breaker is
unavailable consider next available upside rating
viii Mimic diagram shall be provided on all panels.
It is recommonded that only one make of switchgear to be
used in a board / Panel.
All live accessible parts shall be shrouded and all equipment
shall be finger touch proof. SMC shrouds busbar supports shall
x be used. Padlocking facility shall be provided on all MCCB
feeders doors and switch handles shall be locakble in OFF
Equipments will be offered for following routine test only:- i).
Check of Bill of Materials as per approved drawing, ii). Visual
xi and Dimensional Check, iii) Functional Check, iv) HV/Megger
test as per relevant IS, v) Busbar Density and Conductivity
test, vi) Powder Coating thickness test
Third Party test report as required by the consultant/ Client/
xii PMC from the one of the selected vendors from approved list
of make for IP rating, IS/ IEC Compliance and CPRI
Compliance tests etc.
Minimum/Maximum Operating height- 300/1800 respectively
Sealing Arrangement:- PE Foam Rubber/ Neoprene Rubber
Bus Bars Supports - Non-Hygroscopic, Non Carbonising,
Corrosinn Resistant, SMC Supports
1 Set of connector (Phase+Neutral) shall be provided in cable
xvi alley for all outgoing with interconnection wires between MCB
All electrical panel shall have two nos. common G.I. earth bar
of 50X6mm for the panels having incomer fault of 50kA and
rest all with 32X6mm or as specified conductor throughout of
xvii the panel lenght as per the fault kA rating of main Incomer, at
the rear and for wall mounted panel with 2Nos. earth stud at
top one at each side.
Bottom base channel of MS section not less than 100mmx
xviii 50mmx50mmx 5mm thick for Main L.T. Panel and capacitor
panels and 40mmx25mmx25mmx 5mm thickplates for all floor
mounted MDB/MCC and SDBs etc.
All outdoor use panel shall have bottom base stand of
xix minimum 600mm or as mentioned below with M.S. angle iron
32mmx 32mmx6mm with fixing arrangement in RCC
No derating shall be applicable upto ambient temp. 50ºC for all
breakers and selected components.
Digitally signed by Rakesh
DSR20 DESCRIPTION
Each door other than bus bar section shall be 2 numbers wing
xxi knob cabinet cam lock with master key lock made of zinc alloy
powder coated housing, handle and chrome plated cylinder
Minimum Air Clearances between bus bars; (Calculation with
xxii required supporting document shall be submitted by Panel
manufecturer along with GA diagram).
P-P=32mm, P-N=32mm,P-E=26mm and N-E=26mm
Panel Power and control Wiring all FRLS PVC insulated min.
conductor to be used as follows:
AC voltage circuit-1.5 sqmm Red,Yellow,Blue &Black
Current circuit-1.5 sqmm Red,Yellow,Blue &Black
AC Control circuit-1.5 sqmm White for Phase & Black for
DC Control circuit-2.5 sqmm Grey
Power circuit- Red,Yellow,Blue for Phase &Black for Neutral
xxiv Phase-Neutral Terminology:
TP: Three Phase
TPN: Three Phase and Neutral (Neutral shall be Half of Phase
TP+2N: Three Phase and Neutral (Neutral shall be 200% of
Phase Capacity)
4P: Three Phase and Neutral (Neutral shall be 100% of Phase
Labelling- Computerised Laminated Aluminium Name Plate
xxv with White letters on Blue/Black Background For Each Feeder
and Panel Itself.
The treatment of Panel Shall be Fully automatic 9-tank process
for metal treatment which consists of Solvent/ Alkaline
xxvi Degreasing, Water Rinsing, De- Rusting, Water Rinsing,
Passivation, Phosphating, Water Rinsing, Activation and Drying
A separate compartment for Minimum 20% spare space of
xxvii Panel shall be provided for outgoings in future and busbars
shall be drilled accordingly.
During inspection of the panel, the manufacturer of major
xxviii products shall be available at factory to validitate that the used
products are original. Certification shall be given by OEM's on
their company letter head.
All incoming/outgoing MCB shall be mounted on din channel
xxix inside closed chambers shall have Acrylic sheet infront and
front door should be a glass for see thru.
In Meter boards all copper flexible wiring shall be provied with
xxx suitable copper lugs and ferruling at both ends and earthing
shall be provided for individual meter with 2.5sqmm green
insulated wire.
Earthing of rising main mounted meter boards shall be
xxxi connected with rising main earth bar by 2Nos. 20x3 mm GI
Light and 1 No.16A power socket will be provided in each
compartment of the panel.
a) INCOMING
INCOMER-1 :(FROM TRANSFORMER)
2 No. 1600 Amps 4P EDO type Air circuit breaker in-built
battery backup micro-processor LCD Display based releases
for O/L,S/C,I/G&E/F of fault breaking capacity 50KA.
INCOMER-2 :(FROM TRANSFORMER)
2 No. 1600 Amps 4P EDO type Air circuit breaker in-built
battery backup micro-processor LCD Display based releases
for O/L,S/C,I/G&E/F of fault breaking capacity 50KA.
1 No. 1600 Amps 4P EDO type Air circuit breaker in-built
battery backup micro-processor LCD Display based without
protection releases of fault breaking capacity 50KA.
Electrical & Mechanical interlocking between each Incomers
and buscouplers as shown in SLD.
b) METERING, INDICATIONS AND RELAYS:
Transformer Incomer
1 Set. of R/ Y/ B phase indicating lamp with control HRC Fuse.
Digitally signed by Rakesh
DSR20 DESCRIPTION
1 Set of ON/OFF/TRIP/TCH/TCS Indicating lamps with control
MCBs (Incomer ACBs) .
1 no. Power Quality Multi Function Meter with Max Demand
iii) controller with RS485 with Nylon CT's / control MCB's.
1Set of Single Phase Preventor for each Transformer incomer
iv) with indicator for trip and hooter for alarm including control
1Set of Phase Reversal relay for each Transformer incomer
v) with indicator for trip and hooter for alarm including control
1 Set of 3 Phase microprocessor Based Under & Over Voltage
vi) Relay with time delay setting, including control MCBs.
1 No. of Automatic phase correction relay in incoming supply
c) TVSS & BUSBARS SECTIONS
BUSBAR-1&2:-2000Amps TP+50%N, 50kA, 500volts grade
busbar chamber of suitable length with Aluminium busbars
mount on SMC supports. All interconnections shall be as
follows; a). Upto 63A, FRLS PVC insulated copper flexible
colour coded wires b). 64Amp to 200Amp Copper Bus-bars and
c). 201Amp and above Aluminium Bus-bars , current density of
bus-bars shall not be less than 1 Amps/sq.mm for Aluminium
and 2 Amps/sq.mm for copper cross sectional area of Bus Bar.
Each Bus Section with 1 No Surge protection device Type 1 (
Class B),true status indication, 7 Mode, spark gap type suitable
for 10/ 350 µ s surge,Voltage Protection level Up < 4.0kV,
Operating Temperature -40 deg 'c' - +80 deg 'C', Connected
Between 3Nos. phase to neutral & 3Nos. phase to earth and
1Nos. neutral to earth with discharge Current Imax. ≥ 50KA
Per mode & In ≥ 25kA per Mode. Make & Model: Argos-AG-
415-40T1-E or eq. SPD with 125A 4P HRC fuses of 100kA
breaking capacity. For connecting SPD minimum 16sqmm
copper wire must be used & length of connecting leads shall
not be more than 500mm for per mode connection with each
busbar including all necessary accessories. The SPD shall
complience with IEC 61643-11 and certified by
TUV,CE,ROHS,UL94V-O.
d) OUTGOINGS CONNECTED AS SHOWN IN SLD:
8 Nos. 630A 4P MCCB built in thermal magnetic based release
i) (adjustable O/L, adjustable S/C & adjustable E/F) of fault
breaking capacity 35KA
3 Nos. 400A 4P MCCB built in thermal magnetic based release
ii) (adjustable O/L, adjustable S/C & adjustable E/F) of fault
breaking capacity 35KA
2 Nos. 250A 4P MCCB built in thermal magnetic based release
iii) (adjustable O/L, adjustable S/C & adjustable E/F) of fault
breaking capacity 35KA
1 Nos. 125A 4P MCCB built in thermal magnetic based release
iv) (adjustable O/L, adjustable S/C & adjustable E/F) of fault
breaking capacity 35KA
2 Nos. 100A 4P MCCB built in thermal magnetic based release
v) (adjustable O/L, adjustable S/C & adjustable E/F) of fault
breaking capacity 35KA
2 Nos. 63A 4P MCCB built in thermal magnetic based release
vi) (adjustable O/L, adjustable S/C & adjustable E/F) of fault
breaking capacity 35KA
a) INCOMING
INCOMER-1 :(FROM NON ESSENTIAL PANEL)
1 Nos. 630A 4P MCCB built in Micro processor based O/C, S/C
& E/F release of fault breaking capacity 35KA
1 Nos. 630A 4P, AC1 duty, Power Contactor with wide band
coils and with minimum 2NO+2NC contact placed for incomer
circuit breaker
INCOMER-2: (FROM D.G-400kVA)
1 Nos. 630A 4P MCCB built in Micro processor based O/C, S/C
& E/F release of fault breaking capacity 35KA
1 Nos. 630A 4P, AC1 duty, Power Contactor with wide band
coils and with minimum 2NO+2NC contact placed for incomer
circuit breaker
INCOMER-3 :(FROM NON ESSENTIAL PANEL)
Digitally signed by Rakesh
DSR20 DESCRIPTION
1 Nos. 630A 4P MCCB built in Micro processor based O/C, S/C
& E/F release of fault breaking capacity 35KA
1 Nos. 630A 4P, AC1 duty, Power Contactor with wide band
coils and with minimum 2NO+2NC contact placed for incomer
circuit breaker
INCOMER-4: (FROM D.G-400kVA)
1 Nos. 630A 4P MCCB built in Micro processor based O/C, S/C
& E/F release of fault breaking capacity 35KA
1 Nos. 630A 4P, AC1 duty, Power Contactor with wide band
coils and with minimum 2NO+2NC contact placed for incomer
circuit breaker
INCOMER-5 :(FROM NON ESSENTIAL PANEL)
1 Nos. 400A 4P MCCB built in Micro processor based O/C, S/C
& E/F release of fault breaking capacity 35KA
1 Nos. 400A 4P, AC1 duty, Power Contactor with wide band
coils and with minimum 2NO+2NC contact placed for incomer
circuit breaker
INCOMER-6: (FROM D.G-200kVA)
1 Nos. 400A 4P MCCB built in Micro processor based O/C, S/C
& E/F release of fault breaking capacity 35KA
1 Nos. 400A 4P, AC1 duty, Power Contactor with wide band
coils and with minimum 2NO+2NC contact placed for incomer
circuit breaker
BUSCOUPLER-1 & 2
2 Nos. 400A 4P, AC1 duty, Power Contactor with wide band
coils and with minimum 2NO+2NC contact
b) METERING, INDICATIONS AND RELAYS:
Transformer Supply & D.G Incomer
1 Set. of R/ Y/ B phase indicating lamp with control HRC Fuse.
Provide 3Nos indicating lamps for status indication "ON","OFF"
ii) , Tripped due to earth fault on each incomer with control MCBs
1 no. Multi Function Meter with Max Demand controller with
iii) RS485 (Trinity make :-EXPERT PLUS/Eq.) with Nylon CT's /
1Set of Single Phase Preventor for each D.G incomer with
iv) indicator for trip and hooter for alarm including control MCBs
Reverse power relay for each D.G. set Incomer with indicator
for trip and hooter for alarm
1 Set of 3 Phase microprocessor Based Under & Over Voltage
vi) Relay with time delay setting, including control MCBs.
Provide control accessories like automatically controlled
constant voltage constant current, 24/12 V DC battery charger
with battery charging indication, battery charged indication,
vii) Over charged battery protection, low battery protection, High
Voltage protection, charger on - AC, DC Ammeter, DC
Voltmeter, 8 window fault annunciater with inbuilt P.B and
Hooter, trip alarm and reset etc. for each D.G. Set incomer
Provide 8 window annunciator with hooter , 2 Window for over
Current & Earth fault, 2 Window for OTI alarm & Trip, 2
viii) Window for WTI alarm & Trip & 2 Window Bucholz alarm & Trip
( If applicable) for each Transformer incomer
Provide emergency stop Push Button Station for Emergency
stop Head with Switching position indicator and yellow anti-
ix) lock collar, push to lock and turn to release. Legend -
Emergency Contact - 1 NC. Metric knock outs for Cables entry
for each incomer ACB/MCCB.
c) TVSS & BUSBARS SECTIONS
BUSBAR-1&2:-800Amps TP+50%N, 35kA, 500volts grade
busbar chamber of suitable length with Aluminium busbars
mount on SMC supports. All interconnections shall be as
follows; a). Upto 63A, FRLS PVC insulated copper flexible
colour coded wires b). 64Amp to 200Amp Copper Bus-bars and
c). 201Amp and above Aluminium Bus-bars , current density of
bus-bars shall not be less than 1 Amps/sq.mm for Aluminium
and 2 Amps/sq.mm for copper cross sectional area of Bus Bar.
Digitally signed by Rakesh
DSR20 DESCRIPTION
BUSBAR-3:-500Amps TP+50%N, 35kA, 500volts grade busbar
chamber of suitable length with Aluminium busbars mount on
SMC supports. All interconnections shall be as follows; a). Upto
63A, FRLS PVC insulated copper flexible colour coded wires b).
64Amp to 200Amp Copper Bus-bars and c). 201Amp and
above Aluminium Bus-bars , current density of bus-bars shall
not be less than 1 Amps/sq.mm for Aluminium and 2
Amps/sq.mm for copper cross sectional area of Bus Bar.
Each Bus Section with 1 No Surge protection device Type 1 (
Class B),true status indication, 7 Mode, spark gap type suitable
for 10/ 350 µ s surge,Voltage Protection level Up < 4.0kV,
Operating Temperature -40 deg 'c' - +80 deg 'C', Connected
Between 3Nos. phase to neutral & 3Nos. phase to earth and
1Nos. neutral to earth with discharge Current Imax. ≥ 50KA
Per mode & In ≥ 25kA per Mode. Make & Model: Argos-AG-
415-40T1-E or eq. SPD with 125A 4P HRC fuses of 100kA
breaking capacity. For connecting SPD minimum 16sqmm
copper wire must be used & length of connecting leads shall
not be more than 500mm for per mode connection with each
busbar including all necessary accessories. The SPD shall
complience with IEC 61643-11 and certified by
TUV,CE,ROHS,UL94V-O.
d) OUTGOINGS CONNECTED AS SHOWN IN SLD:
3 Nos. 630A 4P MCCB built in thermal magnetic based release
i) (adjustable O/L, adjustable S/C & adjustable E/F) of fault
breaking capacity 35KA
2 Nos. 400A 4P MCCB built in thermal magnetic based release
ii) (adjustable O/L, adjustable S/C & adjustable E/F) of fault
breaking capacity 35KA
4 Nos. 320A 4P MCCB built in thermal magnetic based release
iii) (adjustable O/L, adjustable S/C & adjustable E/F) of fault
breaking capacity 35KA
2 Nos. 250A 4P MCCB built in thermal magnetic based release
iv) (adjustable O/L, adjustable S/C & adjustable E/F) of fault
breaking capacity 35KA
2 Nos. 125A 4P MCCB built in thermal magnetic based release
v) (adjustable O/L, adjustable S/C & adjustable E/F) of fault
breaking capacity 35KA
3 Nos. 100A 4P MCCB built in thermal magnetic based release
vi) (adjustable O/L, adjustable S/C & adjustable E/F) of fault
breaking capacity 35KA
1 Nos. 63A 4P MCCB built in thermal magnetic based release
vii) (adjustable O/L, adjustable S/C & adjustable E/F) of fault
breaking capacity 35KA
1 Nos. 40A 4P MCCB built in thermal magnetic based release
viii) (adjustable O/L, adjustable S/C & adjustable E/F) of fault
breaking capacity 35KA
PLC FOR INTERLOCKING, SYNCHRONISING & LOAD
PLC based Automatic / Manual Synchronisation and check
synchronising Panel with auto and manual operation and Load
Manager for both Mains and DG power, whose function will be
to determine the Load, decide how many DG sets to be
synchronised, perform Synchronisation and supply power to
the load. Supplier to submit the Bill of materials for the above
functions also provide motorised potential meter for each
generator for voltage correction.
Including Electrical & Mechanical interlocking between each
Incomers and buscouplers as shown in SLD, Auto D.G.
selection and Start/Stop, Load management including PLC
Expansion Module, Sheild wire, NC01 cable, PLC
restart/refreash, Power Supplies, arrangement Nesecarry
arrangments, Softwere and Hardwares need to be provided for
1kVA online UPS with minimum 15 minutes backup, built in
battery for PLC system.
Digitally signed by Rakesh
DSR20 DESCRIPTION
The capacitor banks in tier formation, Each capacitors
specifications shall be MPP HEAVY duty cylindrical construction
Oil Filled capacitors, 415/440/480/525Volts, 50 hz, Temp.
Class-'D', Operating losses - <0.0025 (TAN DELTA), Over
current withstand capability, 1.3 times rated current, 200 x In
Inrush current withstand capability rated current, Operating
life - 30,000 hours, Having over pressure disconnector switch,
Number of switching, 3000 operations per year, conforming to
IEC 60831-1+2/IS 13340-42. Provide Thermostat controlled
panel mounted heavy duty exhaust fan in each Capacitor
Compartment and space heater in Bus bar alley. The
installation of capacitor panel shall be as per IS:16636 and IEC
61921 latest as on date.
1 Nos. 630A 4P MCCB built in microprocessor based release
(adjustable O/L,S/C&E/F) of fault breaking capacity 35KA
(Ics=Icu=100%) upto 415V manually operated with extended
rotary handle with castle lock for door interlock with Phase
spreader & Phase Barriers at both sides. MCCB shall
conforming to IS-1397-2 1993 as amended.
METERING, INDICATOR AND RELAYs
Provide 3 Nos. Resin cast CTs, Class-1.0 and MFM True RMS
type digital with min. features of measurements covering
A,V,Hz, PF, kW,VAr,VA, kVA, kVAR, kWH, kVAH, kVARH,MDI,
Harmonics,Run Hours, RS-485 Port, LCD display with class-0.5
accuracy for all incomer feeder.
1Set of R,Y,B phase indication lamps with control MCB as per
fault requirement with each incomer
Provide 3Nos indicating lamps for status indication "ON","OFF"
, Tripped due to earth fault on each incomer MCCB.
TVSS & BUSBARS SECTIONS
700Amps TP+50%NL, 25kA, 500volts grade busbar chamber
of suitable length with Aluminium busbars mount on SMC
supports. All interconnections shall be as follows; a). Upto
63A, FRLS PVC insulated copper flexible colour coded wires b).
64Amp to 200Amp Copper Bus-bars and c). 201Amp and
above Aluminium Bus-bars , current density of bus-bars shall
not be less than 1Amps/sq.mm for Aluminium and
2Amps/sq.mm for copper cross sectional area of Bus Bar.
1 No Surge protection device Type 2 ( Class C), 4 Mode, MOV
type suitable for 8/ 20 µ s surge,Voltage Protection level Up <
1.8kV, Operating Temperature -40 deg 'c' - +80 deg 'C',
Connected Between 3Nos. phase to neutral and 1Nos. neutral
to earth with discharge Current Imax. ≥ 40KA Per mode & In
≥ 20kA per Mode. Make & Model: Argos-AG-230-40T2-E or eq.
SPD with 63A 4P HRC fuses of 100kA breaking capacity. For
connecting SPD minimum 10sqmm copper wire must be used
& length of connecting leads shall not be more than 500mm
for per mode connection with each busbar including all
necessary accessories. The SPD shall complience with IEC
61643-11 and certified by TUV,CE,ROHS,UL94V-O.
Automatic Power Factor Controller Relay should be 12+1 alarm
stage Microcontroller based three phase measuring controller
with electromechanical relay contacts, it should take 3 CT
inputs for to compensate reactive power even in unbalanced
load condition, it should have feature to autosense the
capacitor banks and capable to sense & take corrective action
even at 1% load Current of main CT primary. It shall have
1No. alarm output, Contactor switching time should be site
selectable from minimum 10 seconds onwards, It should
measure and display all three Voltage,Current,PF ,Power &
Energies, instant & Avg PF, Sys KVAR , Required KVAR , THD
for all three phase V & I with order wise Harmonics atleast up
to 15th order with RS485 Port.
1Set of Start/Stop illuminated push buttons, Auto/Manual/off
selector switch 2P/2W+OFF, ON/OFF/TRIP indicator, Timer
each backed up with HRC fuses with provide complete set for
each outgoing contactor.
Digitally signed by Rakesh
DSR20 DESCRIPTION
2Nos. Flashing Buzzer Over / Under Compensation
1Set of demand Controller with standard parameters with
minimum 2 relay output and mainly used for alarm and
indication if the power factor goes lagging below from 0.85
and leading above from 1.0 also if life cycle to complete of
capacitor panel.
OUTGOINGS WITH CONTACTOR
Each below capacitor bank feeder shall be with TP capacitor
duty contactor of same required kVAR, TP HRC Fuse, door
mount toggle Switch & light for each capacitor compartment,
control wiring and backed up HRC Fuse.
i) 3 Sets of 1x50 KVAR Capacitor bank with 100A TP MCCB
ii) 1 Sets of 1x25 KVAR Capacitor bank with 63A TP MCCB
iii) 3 Sets of 1x15 KVAR Capacitor bank with 63A TP MCCB
iv) 1 Sets of 1x10 KVAR Capacitor bank with 32A TP MCCB
v) 4 Sets of 1x5 KVAR Capacitor bank with 16A TP MCCB
1Nos. 63 4P 'C' Curve 10kA MCB with central overload trip
mechanism and flag indication
TVSS & BUSBARS SECTIONS
100A 4P, 415volts grade busbar chamber of suitable length
with Aluminium bus-bars mount on SMC supports current
density of bus-bars shall not be less than 2 Amps/sq.mm for
copper cross sectional area of Bus Bar. For interconnections
provide 3 x 100A tinned copper insulated prong type short
links with end cap , 4Nos. neutral bus bar (For three phase &
One common), 3Nos earth bar, din bar as required. The cost
shall include required minimum 10sqmm copper insulated
colour coded interconnection wire set, circuit identification
lables & laminated wiring detail chart as standard.
1 No Surge protection device Type 2 ( Class C), 4 Mode, MOV
type suitable for 8/ 20 µ s surge,Voltage Protection level Up <
1.8kV, Operating Temperature -40 deg 'c' - +80 deg 'C',
Connected Between 3Nos. phase to neutral and 1Nos. neutral
to earth with discharge Current Imax. ≥ 40KA Per mode & In
≥ 20kA per Mode. Make & Model: Argos-AG-230-40T2-E or eq.
SPD with 63A 4P HRC fuses of 100kA breaking capacity. For
connecting SPD minimum 10sqmm copper wire must be used
& length of connecting leads shall not be more than 500mm
for per mode connection with each busbar including all
necessary accessories. The SPD shall complience with IEC
61643-11 and certified by TUV,CE,ROHS,UL94V-O..
1 Nos. 63 4P Power Contactorwith Auto/Manual selector and
self Start/Stop illuminated switch.
1 Nos. Digital Astro-time of eq to Finder make (Part no:
12.81.8.230.0000 or eq.) with 230V AC supply & operating
range of 184 … 264V AC & shall have contact rating of
1CO(SPDT), 16A/250V AC with AgSnO2 contact material and
in- built minimum 6 years battery back up. Switching of loads
shall be as per Astro-program i.e. calculation of sunrise and
sunset times through date, time and location coordinates. It
shall also have the provision for calculation of sunrise and
sunset times by programming through 2 digits of initial PIN /
POSTAL codes. It shall have an option of Astro ON period
override by time switch and Offset function which allows
programming of switching times offset from the astronomic
time (by up to 90 min, in 10 min steps). It shall have LCD
status indication with back light display along with internal
easily replaceable battery on the front side for set-up and
programming. It shall be suitable for “ Smart ” mode 4 digit
protected programming via smartphones with NFC
30 Nos. 16A 4P 'C' Curve MCB with central overload trip
mechanism and flag indication of 10kA breaking capacity
devided equally in per phase or as indicated in Single line
3 Nos. 32 DP 'C' Curve MCB with central overload trip
mechanism and flag indication of 10kA breaking capacity
1No. 32A DP Plug and Top for Maintainance
Digitally signed by Rakesh
DSR20 DESCRIPTION
All MCB shall be mounted on din channel inside closed
chambers shall have Acrylic sheet infront and front door should
be a glass for see thru.
MS Stand of 450mm height to be provided with black painted.
G. L.T./ CONTROL CABLES
Supply of following sizes of Power Cables multi stranded
Aluminium conductor, XLPE Insulated, cores laid up PVC tape /
1 Extruded Inner sheath , Armour, FRLS at outer sheath,1100V
grade as per IS 7098(Part 1) 1988 with upto date
Laying of one number PVC insulated and PVC sheathed / XLPE
power cable of 1.1 kV grade of following size direct in ground
2 7.1 including excavation, sand cushioning, protective covering and
refilling the trench etc. as required.
Supplying and making end termination with brass compression
3 9.1 gland and aluminium lugs for following size of PVC insulated
and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV
grade as required
Supplying and laying of following size DWC HDPE pipe ISI
marked along with all accessories like socket, bend, couplers
etc. conforming to IS 14930, Part II complete with fitting and
4 14.16 cutting, jointing etc..direct in ground (75 cm below ground
level) including excavation and refilling the trench but
excluding sand cushioning and protective covering etc.,
complete as required.
Supply of Stranded Compact Circular Aluminium Conductor,
Conductor Screen with Extruded Semi Conducting Compound,
XLPE Insulated (Earthed), Insulation Screening with extruded
Semi Conducting Compound in combination with Copper Tape
5 (0.3kA for 1 sec), cores laid up, inner sheath of PVC tape,
galvanised flat steel strip armoured and overall PVC Sheathed
following size Cable conforming to IS 7098 / (PART-II) 2011
with latest amendments.
Laying of one number PVC insulated and PVC sheathed / XLPE
power cable of 11 kV grade of following size direct in ground
6 8.1 including excavation, sand cushioning, protective covering and
refilling the trench etc. as required.
Digitally signed by Rakesh
DSR20 DESCRIPTION
supplying and making indoor cable end termination with heat
7 10.4 shrinkable jointing kit complete with all accessories including
lugs suitable for following size of 3 core, XLPE aluminium
conductor cable of 11 kV grade as required.
Supplying and making outdoor cable end termination with heat
shrinkable jointing kit complete with all accessories including
8 10.5 lugs suitable for following size of 3 core, XLPE aluminium
conductor cable of 11 kV grade as required.
Supplying and making straight through cable jointing with heat
shrinkable jointing kit complete with all accessories including
9 10.6 ferrules suitable for following size of 3 core, XLPE aluminium
conductor cable of 11 kV grade as required.
Supplying and fixing cable route marker with 10 cm X 10 cm X
10 7.10 5 mm thick G.I. plate with inscription there on, bolted /welded Each 5.00 508.00 2540.00
to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing
the same in ground as required.
Digitally signed by Rakesh
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT.pdf
Tender Document
BOQ.pdf
Tender Document
3b SCC.pdf
Tender Document
8 Milestone.pdf
Tender Document
GCC with upto date amendments.pdf
Tender Document
LIST OF MAKES.pdf
Tender Document
Singed IP.pdf
Tender Document
Site Plan.pdf
Tender Document
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .