Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.9 LAccepted-AOC | L1 | Accepted-AOC 1ST LOWEST | |
| 2 | L2₹37.0 L+₹3.4 L (10.2%)Rejected-Finance | L2 | Rejected-Finance 2ND LOWEST | |
| 3 | L3₹37.5 L+₹3.9 L (11.5%)Rejected-Finance | L3 | Rejected-Finance 3RD LOWEST | |
| 4 | L4₹37.8 L+₹4.2 L (12.4%)Rejected-Finance | L4 | Rejected-Finance 4TH LOWEST | |
| 5 | L5₹38.3 L+₹4.7 L (13.9%)Rejected-Finance | L5 | Rejected-Finance 5TH LOWEST |
Tender Value
₹31 L
EMD Value
₹62,000
Closing Date
5 Aug 2022, 6:00 pmClosed
GARRISON ENGINEER I GOS
GARRISON ENGINEER I GOPALPUR MILITARY STATION PO GOLABANDHA DIST GANJAM ODISHA 761052
REPAIR TO CHAIN LINK FENCING PATH HARDSTANDING ETC AT OFFICERS MD ACCN AREA INCLUDING REPAIR REPLACEMENT OF STREET SECURITY LIGHT CABLES LED STREET LIGHT FITTINGS JUNCTION BOXES POSTTOP LANTERNS LAND SCAPE ROAD WAY LUMINARIES TIMER PANELS HIGHT MAST
2022_MES_538761_1
8000/16/2022-23/0915/E8
Open Tender
Civil Works
Item Rate
270 days
GOPALPUR-ON-SEA
PLEASE REFER TENDER DOCUMENTS
6 documents required · 6 mandatory
₹500
Yes
GARRISON ENGINEER I GOS
₹62,000
Yes
8 Sept 2022
16 Jul 2022
8 Aug 2022
16 Jul 2022
5 Aug 2022
30 Jul 2022
Amount
Demolition of Cement Concrete (unreinforced) of any description & in any position not otherwise specifically provided for complete all as specified & directed.
S&F machine pressed precast concrete interlocking paver block any shape & size conforming to IS 15658-2006 of 60 mm thickness, M-35 Grade with grey cement & pigment complete all as specified & directed.
M&L for Sand filling under floors or in foundations including watering and consolidation complete all as specified and directed.
M&L for 100 mm thick cement concrete 1:4:8 type D-2 using 40 mm graded stone aggregate as in sub base of floor complete all as specified and directed.
M&L for hard core of gauge n exc 63 mm, deposited, spread and levelled in layers n exc 15 cm thick, watered and rammed to a true surface complete all as specified & directed.
M&L for cement concrete 1:2:4 type B-1 using 20 mm graded stone aggregate as in path/ hard standing surface finished even and fair complete all as specified and directed.
M&L 75 mm thick cement concrete 1:3:6 type C2 using 40 mm graded stone aggregate as in sub base,floor , plinth protection etc and finishing cement concrete even and fair complete all as specified & directed.
M&L for excavating over areas, n exc 1.5 m deep and getting out in soft/ loose soil complete all as specified and directed.
M&L for providing Glass strip of 6 mm thick and 40 mm deep in hardstanding for making panels complete all as specified and directed.
M&L for 10 mm thick heavy duty exterior designer tiles of size 300 mm x 300 mm as in floor set, jointed in neat cement slurry and pointed with grey cement and pigment complete all as specified and directed.
M&L for screed bed or bedding layer of mortar 15 mm thick in CM 1:4 for laying floor finishes complete all as specified and directed.
M&L for PCC 1:2:4 type B-0 using 12.5 mm graded stone aggregate as in sub base flooring average 25 mm thick surface finished even and rough (as in levelling course) to receive the topping layer complete all as specified and directed.
Dismantling floor, hearth or wall tiling including cement mortar bedding etc (but not backing) and removing rubbish off the premises complete all as specified and directed.
S&F in repairs 110mm dia PVC (SWR) pipes single socketed, in any length with rubber ring joints, laid in trenches or in floors complete all as specified and as directed
S&F in repairs 110mm bore PVC (SWR) bends any radius complete all as specified and as directed
Demolition of RCC of any description and in any position not other wise specially provided for reinforcement cut as required to facilitate demolition complete all as specified and directed.
M&L for pre cast cement concrete 1:1.5:3, type A-1, using 20mm graded stone aggregate as in cover slabs (for manholes etc) and similar articles with plain faces, set in CM 1:4 complete all as specified and directed.
M&L for Mild Steel TMT bar 10mm dia and over cut to length bent to shape required including cranking, bending spirally for hoping for columns hooking ends and binding with & including Mild Steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed.
M&L for finishing cement concrete even and smooth with using extra cement complete all as specified and directed.
Demolition of brick work or stone/boulder masonry built in cement mortar including all quoins, arches, pillars etc complete all as specified and directed.
M&L Brick work using fly ash bricks straight or curved on plan exc 6m mean radius built in cement mortar 1:6 complete all as specified and directed.
M&L for 15mm thick rendering in CM 1:6 on brick or concrete surface, finishing even and smooth without using extra cement complete all as specified and directed.
Returning, filing in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in any type of soil etc complete all as specified and directed
Removing excavated material (Soil) exc. 250 m but n exc. 500 m and depositing where directed complete all as specified and directed.
Taking down cement plaster on brick or concrete surface including racking out joints, hacking for key, scrubbing down with water etc complete all as specified and directed.
M&L for preparation of new plastered surfaces of walls and applying three coats of white wash complete all as specified and directed
Dismantling posts or sturts (wood,steel or RCC) any section incl taking out embedded portion and making good disturbed ground etc complete all as specified & directed.
Dismantling fencing wire mesh any type etc complete all as specified & directed.
Excavation in post holes (or similar holes) each n.exc 0.5 cum getting out making good the disturbed surface if required in soft/ loose soil complete all as specified and directed.
M&L for PCC 1:3:6 Type C-2 using 40 mm graded stone aggregate in foundation filling and mass concrete complete all as specified & directed.
S&F Angle iron posts and rails,drilled and struts in fencing including cutting tops to shape as directed, driiling holes, notching for wire, etc, flat iron fillets (for secruing wire mesh etc) including all necessary drilling, bolting or riveting, etc and similar work conforming to Fe-290 Gde E-165.
S&F mild Screw bolts (Machine made) with hexagonal or square head at one ends and to fitted with washers and one hexagonal or square n.exc 15cm long, dia of neck 11 to 15mm complete all as specified & directed.
S&F PVC coated chain link of 3.16mm dia mild steel galvanised fencing of mesh size 100 mmx 100 mm as per IS : 2721-2003 weight n exc 4.00 kg per sqm complete all as specified & directed.
S&F mild steel round bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clips quality conforming to Fe-410-W (Gde E-250) quality-A or Fe-290 (Gde-E-165) complete all as specified & directed.
Excavation in trenches n .exc 1.5 mtr wide and not exec 1.5 mtr depth and getting out in looses/soft soil complete all as specified & directed.
Removing excavated material to a distance not exc 50M and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified & directed.
S&F in repairs double wall corrugated HDPE pipe 50mm outer dia for protection of UG cable complete all as specified and directed
M&L PCC 1:4:8 type D 2 using 40 mm graded stone aggregate for filling of pole & stay complete all as specified & directed.
M&L PCC 1:3:6 type C 2 using 40 mm graded stone aggregate for filling of pole & stay complete all as specified & directed.
M&L PCC 1:2:4 type B1 using 20 mm graded stone aggregate for coping of pole complete all as specified & directed.
M & L for tube light grade galvanised with all fittings laid along the pole/in trenches / under road or floor of 50 mm bore including removing the rusted old one complete all as specified and directed.
Taking out old unserviceable PCC/steel tubular pole 9 mtrs long and supply and fixing steel tubular swaged poles with cast iron base plate, finial taper plug, bolts, nuts, screws as specified type 410 SP-31 (9.0 mtr long) and erecting in position all as specified and directed with shifting of conductors and insulators including painting the exposed portion with two coats of aluminium paint over a coat of red oxide primer and internally through out plus embedded portion with two coats of black bituminous paint over a coat of red oxide primer with and including marking of pole number with black paint in yellow circle, complete all as specified and directed.
Taking out old usserviceable PCC pole of any size and supply and fixing in repairs Prestressed concrete pole, 9.0 metres long, 102mm x 172mm at top and l02mm x 279mm at bottom, class 10 and erecting in position all as specified and directed with shifting of conductors and insulators including painting the exposed portion with two coats of weather proof paint complete all as specified and directed.
S & F in replacement of Cross arm, bracings, supports , clamps and back plate fabricated from structural steel section, including nut , bolts , washers, welding , bendings cold or hot, drilling hole for both in any shape or size as indicated or directed and inclusive of one prime coat, one under coat and one finishing coat of paint incl taking down the old unserviceable cross arms complete all as specified & directed.
S&F in replacement of insulator pin type porcelain vitereous , white brown or green insulator including one galvanised mild steel spindle, two galvinised washer and one GI nut 100 mm height and 65 mm dia for 1100 Volt grade complete all as specified & directed.
S&F in replacement of insulator shackle type, porcelain, vitereous, white brown or green insulator including one galvanised mild steel straps, washers, insulator bolts, washer and nuts for working pressure 1100 Volts height 100mm, dia 115mm, section of strap (31x5) mm dia of bolt 14 mm complete all as specified & directed.
S&F stay assembly complete with accessories as shown in electrical plate No 1 (Loop type insulator, stay clamps, excavation and concrete only measured separately) using diameter of stay rod 16 mm and MS stay plate 230mm x 230mm including taking down complete all as specified & directed.
S&F in replacement of loop type insulator vitreous white,brown or green insulator small size,with over all dimensions 65 x 90 mm,clearance of hole 16 mm complete all as specified & directed.
Taking out old UNSV and Supply, laying, jointing and testing of XLPE insulated, armoured, heavy duty LT under ground cable 1100 Volts grade with aluminium conductor laid in trenches, on poles, through pipes, fixed to walls etc cross sectional area for following sizes, including taking down old, complete all as specified & directed:- (a) 10 Sqmm 2 Core
(b) 16 Sqmm 2 Core.
(c) 16 Sqmm 4 Core.
(d) 25 Sqmm 3.5 Core.
M&L for replacement of Earthing complete with GI earth plate 60x60cmx6mm thick electrode and 4mm dia GI wire as earthing lead.burried directly in ground ( earth pit not less than 2.25 metres deep below ground level ) with top edge of the plate not less than 1.5 metres below normal ground level. connected to GI wire earth lead 4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part-I and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade up to 7.5 mtr length of earth wire,charcoal dust and salt etc and connected to earthing test point complete all as specified & directed.
M&L for replacement of Earthing complete with GI earth plate 60x60cmx6mm thick electrode and using galvanised iron strip 32 x 6 mm as earthing lead burried directly in ground ( earth pit not less than 2.25 metres deep below ground level ) with top edge of the plate not less than 1.5 metres below normal ground level. connected to GI strip 32x6 mm as earthing lead means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part-I and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade up to 7.5 mtr length of earth wire,charcoal dust and salt etc and connected to earthing test point complete all as specified & directed.
S&F in replacement of moduled case circuit breaker Four pole 100 Amps 16 KA capacity 415V 50Hz with Ics = 50% Icu as per IEC 60947-II suitable for isolation class II front face fixed overload and fixed short circuit setting. taking out the old unserviceable complete all as specified & directed.
S&F in repairs of digital voltmeter 0 to 500 volts 96 x96mm flush type in LT Panels incl taking out the old unserviceable complete all as specified and directed.
S&F in replacement of digital ammeter range as per existing 96 x96mm flush type in LT panels incl taking out the old unserviceable complete all as specified and directed.
S&F in replacement of LT current transformer ratio from 200/5 Amps or 100/5 or 400/5 in LT panels incl taking out the old unserviceable complete all as specified & directed.
S&F in repair indicator assembly (RYB) LED type in LT panel boards incl taking out the old unserviceable complete all as specified and directed.
S & F in replacement of new generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high efficiency LED as lighting source and lens embedde PC coverhaving bottom opening seperate driver compartment with IP 66 protection and impact resistance of IK08 with suitable for pole dia 42 mm of capacity 45 watts complete all as specified and directed. Note :- CA no to be written on the light by the contractor in the quoted rate
S & F in replacement of new generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high efficiency LED as lighting source and lens embedde PC coverhaving bottom opening seperate driver compartment with IP 66 protection and impact resistance of IK07 with suitable for pole dia 42 mm of capacity 45 watts complete all as specified and directed. Note:- CA No to be written on the light by the contractor in the quoted rate
S&F in replacement of LED driver for suitable for 45W to 60 W complete all as specified & directed.
S&F in repair for PVC junction box of size 270 x 225 x 135 mm with Aluminium bus bar 200 Amps capacity -4 No's . MCB SP 6 Amp - 1 No and having provision of cable hole in bottom for two to three armoured cables of size 25 Sqmm 3.5 core, connection box shall be fitted on street light pole and fixing arrrangements i.e. MS clamps etc deemed to be provided by the contractor complete all as specified & directed.
Taking down and replacement of existing unserviceable street light fitting bracket with new brackets made out of 32mm bore GI pipe, light grade, tubing bend to shape, 1.2 metre long, fixed to pole/wall, painting with two coats of aluminium paint over a coat of red oxide primer complete all as specified & directed.
Taking down and replacement of existing unserviceable clamps with new clamps made out of 40x3 mm bending to shape, drilling holes for bolts suitable for fixing GI pipe bracket to steel pole, made in two halves, including nuts, bolts, washers and painting with two coats of aluminium paint over a coat of red oxide primer, complete all as specified & directed.
M&L for painting steel tubular/ RS Joist/ Rail pole 9 mtrs long alongwith bends with two coats of aluminium paint over a coat of red oxide primer and internally through out plus embedded portion with two coats of black bituminous paint over a coat of red oxide primer with and including marking of pole number with black paint in yellow circle, complete all as specified & directed.
M&L for painting PCC pole 9 mtrs long alongwith bends with two coats of weather proof paint and two coats of black bituminous paint over a coat and including marking of pole number with black paint in yellow circle, complete all as specified & directed.
M&L for painting to Timer panel of any size with two coats of sky blue paint over a coat of red oxide primer outerside and two coats of off white paint over a coat of red oxide primer internally complete all as specified & directed. Note: 1. Before painting the contractor will ask for a shut down of the recpective feeder from the JE. Note: 2. While painting of the panels protection of MCCB's and MCB's to be taken care of by the contractor. Any damage occured during the painting will be bear by the contractor.
S&F of Cable jointing kit for 1.1 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 4 core XLPE armoured aluminium conductor cable of size 16 to 25 sqmm complete all as specified & directed.
Checking of street/security lights breakdown maint of overhead lines/9 mtr pole/swan neck poles by checking out the cables/carbon removel /connectors/mcbs etc and locating the fault and replacing with necessary cables for jumpers/ clamps & connectors/terminal box etc, making good, cleaning and lubricating the parts etc complete all as specified and as directed : Note 1: quoted rate inclusive of vehicle with ladder and manpower job card received from power house and after completion of work job card return to power house. Note 2: Drivers/PCBs/cables/fittings/terminal box/ disc/pin insulators, are measured and paid separately under relavent items
S&F in replacement of Timer panel, made of MS Enclosure factory made consisting Astronomical timer with max load of 12 KW with 65 A TP contactor with MCB 63 Amp TPN three phase 415 volts conforming to IS/IEC 60947-4-1, provided with protection degree IP 54 with internal wiring FRLS copper cable, in built shor-circuit-protection, class H insulation complete as as specifed and directed. with suiteable size of angle iron frame and necessary PCC Wk complete all as specified & directed.
M&L for taking down the motorised / manual High Mast Lights circular grid accomodating MH/MV light fittings any cap over a ht of 15 mtr to the ground, taking aside, replacing the unsv control gears/ light fittings with LED fixtures and raising back to its original position upto 15 mtr etc complete all as specified and as directed (Rates quoted shall be incl of replacing required accessories where specifically not mentioned but required to complete the Job except LED fixtures)
S&F in replacement astronomical + digital time switch 3 years complete all as specified and directed.
S&F in replacement of automatic modular contactor with 3NO+1NC, 40A, 3 module, 50HZ suitable for timer switch of street light complete all as specified and directed
Boring of holes horizontally for laying of 40mm dia pipe (minimum depth 0.60 Mtr from top level) under road, Pavement, hard standing complete all as specified and directed.
S&F post-top lantern 25 watt ruby clear energy saving, environmental friendly, long life aesthetically designed with IP 65 symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source
M&L in replacement of new generation energy saving and environmental friendly, long, life pressure die cast aluminium housing flood light with PC diffused lens enclusre over LED for glare free light of capacity 120 watts, 240 volts, 50Hz complete all as specified and directed. Note:- CA No to be written on the light by the contractor on the quoted rate
M & L for Cutting and trimming of tree branches 3 mtr all around of any size which is obstructing illumination of street light and touching LT Over head line by using required tools and plants incl removing trimmed tree branches. (Note : Each cleaning will be measured and paid separetely)
S&F in repairs SP 5-32 amp rating 240V, 10KA 'C' curveminiature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning.
S&F in repairs SPN 32-40 amp rating 240V, 10KA 'C' curveminiature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning.
S&F in repairs TPN 40-100 rating 415, 10KA 'C' curveminiature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning.
S&F in repairs PVC insulated and FR PVC round sheathed copper conductor(flexible), 1100 volts, conforming to IS 694 of size 1.50 Sqmm 3 core complete all as specified and directed
S&F for in repairs service wire sheathed flat 2 core aluminium conductor of size 4 Sqmm, 1100 volts grade complete all as specified and directed
S&F for in repairs service wire sheathed flat 2 core aluminium conductor of size 6 Sqmm, 1100 volts grade complete all as specified and directed
M&L for in repairs service wire sheathed flat 2 core aluminium conductor of size 10 Sqmm, 1100 volts grade complete all as specified and directed
S&F in repairs PVC conduit pipes 19 mm outer dia corrsion free, thermal resistance -5 degree to +60 degree celcius, self extinguishing complete all as specified and directed
M/S. KISHAN ENGINEERING
MM ENGINEERING SYSTEMS
M/S K MURALIDHARA PATRA
M/s Ats Electricals
Likitha Enterprises
M/s Bapujee Builders and Traders
S J ENTERPRISES
V.Venkata Ramaiah
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .