Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.7 LAccepted-AOC | ₹34.7 L Quoted ₹36.4 L | L1 | Accepted-AOC LOWEST BIDDER |
| 2 | L2₹37.4 L+₹95,947 (2.63%)Rejected-Finance | ₹37.4 L+₹95,947 (2.63%) | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 3 | L3₹38.7 L+₹2.3 L (6.31%)Rejected-Finance | ₹38.7 L+₹2.3 L (6.31%) | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
25 Jul 2023, 6:00 pmClosed
GE 869 EWS
GE 869 EWS PIN 913869 C/O 99 APO
REP/MAINT OF LT OVERHEAD LINES, UG CABLES AND VOLTAGE STABILIZERS WITH CONNECTED WORKS AND CERTAIN E/M WORKS AT CERTAIN TECHNICAL AREA OF 27(I) R O AND LIGHTENING CONDUCTOR SYSTEM AND EARTHINGS WITH CONNECTED WORKS AT LKG,CENTRAL SECTOR AND KOIRENGI
2023_MES_603117_1
8506/E8
Open Tender
Civil Works
Item Rate
210 days
LEIMAKHONG MIL STN
AS PER TENDER DOCUMENTS
2 documents required · 2 mandatory
₹500
GE 869 EWS
₹70,000
Yes
12 Oct 2023
16 Jun 2023
26 Jul 2023
16 Jun 2023
25 Jul 2023
6 Jul 2023
Amount
Schedule 'A'
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, poles struts, laying of cables/pipes, etc., not exceeding 10 Sqm on plan and not exceeding 1.5m in depth and getting out in hard/dense soil complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm as in soils complete all as specified and as directed.
Removing excavated materials to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5 mtr above the starting point as in soils complete all as specified and as directed.
Supply and spread sand in trenches as sand cushioning to underground cable for protection with dry fine river sand and provide required cover after punning down 18CM will be measured and paid complete all as specified and directed.(Note: Thickness of sand cushion after punning down will be measured and paid.)
Supply and laying well burnt sub class ‘B’ bricks ( designated 75) locally available best quality, laid dry in trenches for protection of underground cablecomplete all as specified and directed.
Dismantling of old unserviceable Steel tubular pole/ struts any size any type and removing from site complete all as specified and directed.
Supply and fixing of steel tubular swaged poles, type 410 SP 31 (Overall length 9.00 m) complete with cast iron base plate, finial taper plug, bolts, nuts screws and washers including painting two coats of black bituminous paint internally and externally up to planting depth and remaining external portion with two coats of aluminum paints over a coat of red oxide primer and writing pole Nos with white paint on black back ground complete all as specified and as directed.
Dismantling of stay assemblycomplete all as specified and as directed.
M &L for stay assembly 20 mm dia complete with accessories as shown in electrical plate No. 1 complete all as specified and directed. (Note : Excavation and concrete shall be measured and paid separately)
S&F in replacement for galvanized stay strand of size 7/3.15 mm complete all as specified and directed.
M&L for plain cement concrete 1:4:8 type D2 using 40 mm graded crushed stone aggregate as in foundation of pole, protection of UG cable, concrete base, etc complete all as specified and directed.
M&L for plain cement concrete (1:3:6) type C1 using 20mm graded crushed stone aggregate in coping of pole, concrete base work, protection of cable complete all as specified and directed.
Taking up/down worn out/damaged/unserviceable XLPE /PVC insulated underground cable armoured, heavy duty with aluminium conductors of any size, 1100 Volt grade from trench/duct/pole/wall/ pipes/rooftops etc. complete all as specified and directed.
Supply, laying, Jointing connecting in replacement of LT UG cable XLPE insulated,PVC bedded galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 10 sqmm 2 core laid in trenches / on poles / walls / in ducts / passing through pipes and including necessary cable lugs, bolts, nuts and washers complete all as specified and directed. (Make: Havells/KEI/Polycab/Gloster/Finolex).
All as per serial item No. 14 above but for 10 Sqmm 4 Core. (Make: Havells/KEI/Polycab/Gloster/Finolex).
All as per serial item No. 14 above but for 16 Sqmm 4 Core. (Make: Havells/KEI/Polycab/Gloster/Finolex).
All as per serial item No. 14 above but for 25 Sqmm 4 Core. (Make: Havells/KEI/Polycab/Gloster/Finolex).
All as per serial item No. 14 above but for 35 Sqmm 3.5 Core. (Make: Havells/KEI/Polycab/Gloster/Finolex).
All as per serial item No. 14 above but for 50 Sqmm 3.5 Core. (Make: Havells/KEI/Polycab/Gloster/Finolex).
All as per serial item No. 14 above but for 70 Sqmm 3.5 Core (Make: Havells/KEI/Polycab/Gloster/Finolex).
All as per serial item No. 14 above but for 95 Sqmm 3.5 Core (Make: Havells/KEI/Polycab/Gloster/Finolex).
All as per serial item No. 14 above but for 120 Sqmm 3.5 Core (Make: Havells/KEI/Polycab/Gloster/Finolex).
All as per serial item No. 14 above but for 150 Sqmm 3.5 Core (Make: Havells/KEI/Polycab/Gloster/Finolex).
All as per serial item No. 14 above but for 185 Sqmm 3.5 Core (Make: Havells/KEI/Polycab/Gloster/Finolex).
All as per serial item No. 14 above but for 240 Sqmm 3.5 Core (Make: Havells/KEI/Polycab/Gloster/Finolex).
Supply and laying of 32 mm bore GI tube light grade as in cable protection pipe including all fittings and including taking down / taking out from trench of cable complete all as specified and directed.
Supply and laying of 40 mm bore GI tube light grade as in cable protection pipe including all fittings and including taking down / taking out from trench of cable complete all as specified and directed.
Supply and laying of 80 mm bore GI tube light grade as in cable protection pipe including all fittings and including taking down / taking out from trench of cable complete all as specified and directed.
Dismantling of unserviceable worn out / weathered / damaged ACSR conductor, service feeder of any size and type from pole after disconnecting jumpers and insulator bindings complete all as specified and directed.
M&L for stringing ACSR conductor of any size including all binding wires and aluminium jointing, jumpering etc maintaining standard sag on LT OH lines complete all as specified and directed.
Material and labour for streching, tightening and restringing of ACSR conductors of any size and type and GI continuous earth conductors of any size, maintaining standard sag including providing aluminium binding wire and fixing of GI conductor complete all as specified and as directed.
Dismantling cross arm of MS channel or angle section from pole any size complete all as specified and as directed.
S&F of cross arms, bracing, clamps and back plates fabricated from structural steel section including nuts, bolts, washers etc, drilling hole for bolts in any shape or size with welding, bending cold or hot including painting two coats of aluminium paint over a coat of primer complete all as specified and directed.
Dismantling insulators of any type and any size complete all as directed.
S&F of pin type porcelain insulator of size 100 mm height, 65mm dia, vitreous, white, brown or green including one galvanized mild steel spindle, two galvanized iron washer and one galvanized iron nut for 1100 volts grade complete all as specified as directed. (Make : BHEL/Pactil/Jaypuria Brothers)
S&F of shackle type insulator, porcelain, vitreous, white, brown or green, 75 mm height 90 mm dia for working pressure of 1100 volts including galvanized steel straps of section 31x3 mm, 12 mm dia of bolts, washers and nuts complete all as specified and directed. (Make : BHEL/Pactil/Jaypuria Brothers)
Supply and fix of loop type insulator, vitreous porcelain, white, brown or green small size, with overall dimensions 65 x 90 mm, clearance of hole 16mm complete all as specified and directed. (Make : BHEL/Pactil/Jaypuria Brothers)
Material and labour for cutting of road/ hard standing n exc 20cm width and n exc 60cm in depth for laying of cable protection pipe including making good the disturbed road/hard standing by providing PCC (1:2:4) type B1 to match with existing surface complete all as specified and directed.
M&L for cleaning, scrapping, preparing of old painted steel tubular pole 9m long and applying one coat of aluminium red oxide primer and two coat of aluminium paint to pole and accessories / fittings whatever fixed on pole including marking/writing pole No on each pole with yellow SE paint with 5cm large bold letters on black background of suitable size at a height of 2m above GL complete all as specified and directed.
Trimming / cutting of the tree branches / bushes which falls within a clear distance of 3 meter from all sides from the LT over head conductor & within line of conductors, and shifting waste to nearby waste depot & cleaning area complete. Note :- Horizontal distance of tree touching to the over head lines shall be measured for the purpose of payment
Dismantling / Taking out old unserviceable service cable including batten/ suspending wires complete all as specified and directed.
S & F of Service wire connection incl GI wire one twin core 10 sq mm, 2 core 1100 volts grde heavy duty flat or circular cable multi stranded with aluminium conductor PVC insulated served with inner sheathing of PVC tape suspended by insulating hangers not more than one mtr apart incl 4 mm dia GI suspension wire Complete all as specified and directed. (Make: Havells/KEI/Polycab/Nicco/RR Kabel/Finolex).
S&F in repair Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size. Complete all as specified and directed.
M & L in repair for LT over head line seperator (4 wire in a single opertor) on over head lines complete all as specified & directed.
M&L in repair earthing complete with galvanized steel plate electrode 600 X 600 X 6 mm thick buried directely in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 mtr below normal ground level connected to GI earth wire 4mm as earthing lead by means of galvanized steel bolts,nuts check nuts and washers and other end connected with to Poles, Pannel board etc as directed including funnel, 20 mm bore, light grade galvanized iron pipe, wire mesh charcoal of coal dust and common salt in alternative layer all around the earth electrode compacted thickness 15cm with concrete pit in PCC 1:3:6 type C1 50 mm thick pre cast RCC 1:2:4 type B1 with 8mm dia cover slab set in CM (1:4) reinforcement with 8mm dia deformed bars @ 15 cm C/C and suitable handle of 10mm dia MS round bars, including earth work as required complete all as shown in electrical plate No. 5 of MES schedule Part I and testing complete all as specified and as directed. (Note: GI Earthing strip upto 7.5m in length is deemed to be included in the unit rate. The Strip required beyond 7.5m shall be measured and paid for separately)
Material and labour for taking out LT voltage stablizer from its position for repair and servicing /rewinding of capacity 50 KVA to 150 KVA, including disconnecting electric supply earth & neutral connection and removing the cable LT side & transport to workshop for service / repairs by dismantling the top portion of the voltage stablizer draining the transformer oil , dismantling & removing the bushes , lifting the winding with the help of crane , cleaning the deposited sherrly / mud at botom of the tank, removing the onserviceable silica gel etc complete & assume the parts of the transformer in total & install its original postion / loc after service / repair& connecting the LT cable , Earth and nutral connection including testing and commissioning. Note:- 1. The rates are to be included the following:- (a) To and from transportation charges from the support/location to work shop. (b) Crane, tools, plants and manpower are included in the above quoted rates. (c) Keeping the LV winding with cranr in electric over for 48 Hrs to improve the insulation is deemed to be included in the quoted rate. (d) Testing of BDV value of the transformer oil is to be included in the quoted rates. 2. The required spare parts LV winding, transformer oil etc shall be meassured and paid separately under the relevant item.
Supply & fix in repair brass spindle as per existing size, shape and specification for capacity 50 to 150 KVA 3 phase Voltage stablizer complete all as specified and directed.
Supply & fix in repair top cover gasket set as per existing size, shape and specification complete for capacity 50 to 150 KVA, 3 phase Voltage stablizer complete all as specified and directed.
M & L for rewinding of copper winding by using super enameled copper winding wire as per relevant IS and orginal gauge/data,including insulating materials such as cotton tape, packing and sleeves etc varnishing by vaccum impregnation and baking of coil core assembly for copper wound Voltage stablizer complete all as specified and as directed by Eng -in Charge.
Supply and filling top up of transformer oil first hand conforming to IS -335 of 1993 up to desired level of oil for 50 KVA to 150 KVA 3phase Voltage stablizer capacity complete all as specified and as directed. Note: - (i) Dielectric strength of oil should not be less than 50 KV with 2.5 mm gap complete all as specified and directed. (ii) Transformer oil shall be brought in manufacturer sealed drum at site. Make : As Zonal specification.
Dehydration of transformer oil of transformer/switch have using hot oil filteration plant for remover the moisture contents and carbon deposits from the oil bringing it to the dielectric strengnth not less than 50 KV with 2.5 mm gap after filteration complete all as specified and directed.
Supply & fixing in repair Aluminium lugs of size 35 Sqmm fixed with MCCBs / busbar in LT panels / Cable incl nuts, bolts & washer complete all as specified and directed.
Supply & fixing in repair Aluminium lugs of size 50 Sqmm fixed with MCCBs / busbar in LT panels / cables incl nuts, bolts & washer complete all as specified and directed.
Supply & fixing in repair Aluminium lugs of size 95 Sqmm fixed with MCCBs / busbar in LT panels / cables incl nuts, bolts & washer complete all as specified and directed.
Supply & fixing in repair Aluminium lugs of size 120 Sqmm fixed with MCCBs / busbar in LT panels / cables incl nuts, bolts & washer complete all as specified and directed.
Supply & fixing in repair Aluminium lugs of size 240 Sqmm fixed with MCCBs / busbar in LT panels / cables incl nuts, bolts & washer complete all as specified and directed.
Supply & fixing in replacement of LT Cable straight through joint kit of size 50 Sqmm 3.5 core to 120 Sqmm 3.5 core complete all as specified and directed.
Dismantling of old unserviceable Earthing strip any size any type and removing from site complete all as specified and directed.
Dismantling of old unserviceable Termination Rod/ Test Point Block any size any type and removing from site complete all as specified and directed.
Dismantling of old unserviceable Earthing Material any size any type and removing from site complete all as specified and directed.
Supply and fix aluminium strip 25 x 3.15 mm with saddles and fixing screws, insulators rawal plugs etc for conductor for roof and fixed on wall upto test point complete all as specified and directed.
Supply and fix galvanized iron strip 32 x 6mm fixed with saddles & fixing screws, PVC dash fastners, insulators fixed from test point to earth on walls or burried in ground / drawn into hume pipe complete all as specified and directed. NOTE : Excavation & earth work shall be measured and paid for seperately under relevant item of schedule.
Supply and fix single pointed air termination Aluminium rod 12mm dia, 300 mm long complete all as specified and directed.
S&F of Test point terminal block made of gun metal or phosphorous bronge 75 x 75 x 25mm of 6mm thickness drilled and screwed including 3 Nos 8mm dia 25mm long hexagonal head brass screws including box of size 90 x 90 x 90mm made of 1.6mm plain sheet and screwed to wall for protection of test point complete all as specified and directed.
M&L for Earthing complete with galvanised steel earth plate electrode 60cm×60cm×6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised iron strip 32×6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed.
M & L with electrician for repair/areplacement of electric system of constant current regulator of the following unserviceable spare parts and testing complete :- (a) Disconnecting of electric connection and servicing of constant current regulator of capacity 5 KVA installed at 27 R & O flight for runway lighting and checking of complete electrical circuit for smooth functioning of constant voltage.
(b) Thyrister model No H150 TB suitable for 5 KVA constant current regulator
(c) Relay 12 volt suitable for 5 KVA constant regulator
(d) Relay 24 volt suitable for 5 KVA constant current regulator
(e) Diode model No (In 4007) suitable for 5 KVA constant current regulator
(f) Complete HRC fuse suitable for 5 KVA constant current regulator
(g) Transformer (FT) suitable for 5 KVA constant current regulator
(h) Transformer (SD) suitable for 5 KVA constant current regulator.
(j) Copper wire single core of 16 Sqmm
(k) Copper lugs of size 16 MM dia.
(l) Copper lugs of size 25 MM dia.
(m) MCCB 100 Amps, 4 pole, 415 Volts, 25 K suitable for 5 KVA constant current regulator of capacity 5 KVA.
Supplying and fixing in replacement of 1100 volt grade heavy duty cable PVC insutlated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, two single core size of aluminium conductor 16 Sqmm cable flat or circular complete all as specified and directed.
Supply & Fix in replacement of high performance LED street light luminaire having single die ceramic base high power IP66 protection ,PDC housing with finless design and poly carbonate cover. LED light source or single 45 Watt.and fixing bracket made of 32 mm bore galvanised iron light grade pipe made to shape having overall length 1.2 mtr, fixed on pole /wall through two numbers mild steel clamp of 25mm width ,3mm thick MS flat strip and four Nos nuts,bolts & washers of 12mm dia ,150mm long grouted into wall including connection with twin core twisted flexible copper conductor cable complete all as specified and as directed. (Make : Havells/ Philips/ CG/ Bajaj)
M/S BIJOYA LAXMI ENTERPRISE
PERFECT BUILDERS AND SUPPLIERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .