Loading…
Loading…
Tender Value
₹2.7 Cr
EMD Value
₹5.5 L
Closing Date
21 Aug 2026, 3:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
DRAWING
15 conditions · 4 needing a document upload
Financial Eligibility Criteria: The tenderer must have minimum average annual contractual turnover of V/N or V whichever is less; where V= Advertised value of the tender in crores of Rupees. N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-F, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet
Electrical License: The tenderer shall possess a valid Electrical Contractor License, issued by any State Government or Union Territory Administration, authorizing execution of electrical works up to 650 V. The contractor shall have in his employment or shall engage a person holding a valid certificate of competency issued by any State Government or Union Territory Administration for supervision of electrical works up to 650 V.Offers not accompanied by a valid Electrical Contractor License and requisite Supervisor competency for works up to 650 V shall be summarily rejectedNote: In case of expiry of validity of license during contract, the contractor should renew the license so that it is always valid during contract).
Technical Eligibility Criteria: (a) The tenderer must have successfully completed or substantially completed any of the following during last 07 (seven) years, ending last day of month before the one in which tender is invited: Three similar works costing not less than the amount equal to 30% of advertised value of the tender, or Two similar works costing not less than the amount equal to 40% of advertised value of the tender, or One similar work costing not less than the amount equal to 60% of advertised value of the tender.
Definition of Similar nature of work: "Works of wiring/cabling or installation and commissioning of electrical items (other than on coaches) such as lights, fans, pumps, charging arrangements, earthing etc. (with or without supply of items / equipment) for 230V, 1phase or 415V, 3phase system or higher voltages".
9 conditions · 1 needing a document upload
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Tenderer /s are required to submit a scanned / attested copy of following information along with their tender- 1. Bank Account No 2. Name of Bank 3. Indian Financial System Code {IFSC} 4.PAN No 5. Tenderers Contact No Contractor should provide firms PAN, issued by Income Tax Department with his quote or within30 {Thirty} days of award of contract. No payment will be released without submission of PAN. All taxes including surcharge and cess shall be recovered from his payment as per tax provisions in vogue.
The tenderer shall thoroughly go through the entire tender document and strictly adhere the instructions and directions given at different pages.
It is responsibility of the tenderer that they ensure to see any corrigendum of the tender to check the corrigendum on the website from time to time.
All the required/supporting documents should be scanned and uploaded.
In case the date of closing mentioned in the Notice Inviting Tender is declared a holiday/bandh/strike etc. on any account, the date of closing tender online will not be changed as the application in the website of IREPS does not permit submission of any offer after closing date and time of the tender. However, opening of tenders online will be on any convenient day after the closing date/time of tenders.
Opening of e-tender online:- The e-tenders will be opened online using the IREPS portal. No representative is required to be present for opening of tender and taking notes of rates quoted and ranking as the complete details of rates etc. of all the bidders shall be available to the bidders in the website after the opening of the tender.
Provision of a new control office and standby alternate control in Nanded Division - Electrical Arrangements.
NED-E-21-2026-27
NED-E-21-2026-27
Open
Works - General
12 Months
Nanded, Maharashtra
₹0
₹5.5 L
21 Aug 2026
31 Jul 2026
7 Aug 2026
240 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 2,74,85,135 | ||
| — | 769.00 | — | — | ||
| Provision of concealed wiring with two runs of 1.5 Sq.mm 1100 Volts and one run of flexible copper conductor 1.5Sq.mm 1100 Volts FRLS PVC insulated wires ISI marked (Phase, neutral and earth)( upto 10 meters lenght) inthe PVC conduit pipe with 6A flush modular type switch including 2 way switches where ever required, ceilingrose, bulb holder and modular type plate cover to MS switch control box including all labour charges complete forlight points, ceiling fans and exhaust fans points cat walk points and ioh service buidling points etc. accessories. | — | — | — | 5,10,616 | |
| — | 5400.00 | — | — | ||
| Supply and run of 2 nos, 2.5 sqmm, 1100 V PVC (FRLS) insulated flexible copper conductor wires and one run of1.5 sqmm PVC (FRLS) insulated flexible copper cable for earthing in existing PVC conduit Pipe conforming to IS694 (2010) with latest amendements. | — | — | — | 5,45,400 | |
| — | 1000.00 | — | — | ||
| Supply and run of 2 nos, 4.0 sq.mm, 1100 V PVC (FRLS) insulated flexible copper conductor wires and one run of2.5 sq.mm PVC (FRLS) insulated flexible copper cable for earthing in existing PVC conduit pipe conforming to IS694 (2010) with latest amendements. | — | — | — | 1,52,000 | |
| — | 1000.00 | — | — | ||
| Supply and run of 2 nos, 6.0 sqmm, 1100 V PVC (FRLS) insulated flexible copper conductor wires and one run of2.5 sqmm PVC (FRLS) insulated flexible copper cable for earthing in existing PVC conduit Pipe conforming to IS694 (2010) with latest amendements. | — | — | — | 1,79,000 | |
| — | 4000.00 | — | — | ||
| Supply and Running of 25 mm dia, Ivory coloured PVC conduit ( ISI marked) of wall thickness not less than 2mm along with junction boxes, bends and all accessories etc. as required as per site requirement. Running ofconduit, fixing with suitable clamps and nuts in groove / open /shelter | — | — | — | 1,92,000 | |
| — | 600.00 | — | — | ||
| Supply and erection of 19mm size rigid conduit pipes of 2 mm thickness PVC pipe (ISI mark) concealed in wallwith all required accessories conforming to IS 9537.3.1983 with its latest amendments , including masonry workand labour charges etc (For wiring points and wiring to switch boards) (for brick wall) along with accessories (bends, elbow, deep junction boxes(3 way, 4 Way) etc Make:Miraj,Prince,Sudhakar,Kankai,Captain. | — | — | — | 13,800 | |
| — | 6000.00 | — | — | ||
| Cutting of groove in the wall, plastering of surface to the original for concealing of the conduit in the wall (Layingand fixing of conduit will be paid separately). | — | — | — | 2,46,000 | |
| — | 1000.00 | — | — | ||
| Supply and Laying of 25 mm FRPP corrugated Flexible conduit pipe as per standard specification. | — | — | — | 30,000 | |
| — | 500.00 | — | — | ||
| Supply and laying of 32mm x 12mm casing and capping of model : Glory type of M/s. Press Fit make orequivalent make with necessary screws (the distance between the screws shall not exceed 0.5 m) including jointsbends and all necessary accessories complete. | — | — | — | 23,000 | |
| — | 894.00 | — | — | ||
| Supply, fixing, connecting and commissioning of 6A 3pin/5pin modular plug socket, with 6A modular controlswitch on existing control board with wiring. | — | — | — | 3,10,218 | |
| — | 56.00 | — | — | ||
| Supply and fixing of 16 Amps 3/5 pin flush type power plug and socket with modular type switch control includingall accessories. | — | — | — | 23,968 | |
| — | 150.00 | — | — | ||
| Supply and Fixing of Surface mounting plastic gang box-8 module of model no: JS 08 006 of GM make orequivalent with 8 module cover plate (With support frame) of model no: PK SB 08 011 - CASABLANCA of GMmake or equivalent make comply with IEC 60669-1 with its latest amendments including all accessoriescomplete. | — | — | — | 52,350 | |
| — | 126.00 | — | — | ||
| Supply and fixing of surface mounting plastic gang box-12 module of model no:JS 12 008 of GM make or itsequivalent with 12 module cover plate (With support frame) of model no:PK SB 12 007 - CASABLANCA of GMmake or equivalant make comply with IEC 60669-1 with its latest amendments including all accessoriescomplete. | — | — | — | 50,022 | |
| — | 121.00 | — | — | ||
| Supply and fixing of metal flush box-6 module of model no:JIM 06 004 of GM FOURFIVE make or its equivalentwith 6 module cover plate (With support frame) of model no:PK SB 06 005 - CASABLANCA of GM make orequivalent make comply with IEC 60669-1 with its latest amendments including all accessories complete. | — | — | — | 32,065 | |
| — | 56.00 | — | — | ||
| Supply and Fixing of metal flush box-8 module of model no:JIM 08 005/6 of GM FOURFIVE make or its equivalentwith 8 module cover plate (With support frame) of model no:PK SB 08 011 - CASABLANCA of GM make orequivalent make comply with IEC 60669-1 with its latest amendments including all accessories complete. | — | — | — | 19,936 | |
| — | 62.00 | — | — | ||
| Supply and fixing of metal flush box-12 module of model no:JIM 12 008 of GM FOURFIVE make or its equivalentwith 12 module cover plate (With support frame) of model no:PK SB 12 007 - CASABLANCA of GM make orequivalent make comply with IEC 60669-1 with its latest amendments including all accessories complete. | — | — | — | 25,544 | |
| — | 92.00 | — | — | ||
| Supply and fixing of 20W 4 feet LED tube light with all connected accessories complete for fixing (The supplyincludes accessories such as clamps, ties extension wires etc for fixing) as per attached railway specification | — | — | — | 35,420 | |
| — | 427.00 | — | — | ||
| Supply and Erection of Recess / Surface mounting 18 W LED Square/round panel lighter as perattached railway specification with all connected accessories. | — | — | — | 3,27,082 | |
| — | 120.00 | — | — | ||
| Supply and Erection of energy efficient BLDC star electric ceiling fan of 1200mm sweep as per attached railwayspecification and including necessary plastering, masonry work and clamps nuts bolts etc. | — | — | — | 3,35,280 | |
| — | 600.00 | — | — | ||
| Supply and Installation of 300mm x 50mm x 2mm thick GI perforated cable tray with cover along with requiredangle supports, with coupler plates, Anchor bolts and nuts etc complete and the tray should be fitted on the wall/ Ceiling etc. complete. | — | — | — | 3,91,248 | |
| — | 8.00 | — | — | ||
| Supplying and erecting triple pole andneutral distribution board (TPNDB) withdoor surface/flush mounted with 4 waysfor incoming and 12 ways for outgoingSP/TP MCB's on iron frame/laminatedboard as per specification No. SW-SWR/MCBDB Make: Legrand/Havells/L&T. | — | — | — | 20,096 | |
| — | 8.00 | — | — | ||
| Supplying and erecting single pole andneutral distribution board (SPNDB), with 2ways for incoming and 10 ways (10 poles)for outgoing SP MCBs, with door, 1.2mmthickness surface / flush mounted, IP 43Protection on iron / GI frame as perspecification no. SW-SWR/MCBDB Make:Legrand/Havells/L&T. | — | — | — | 12,984 | |
| — | 16.00 | — | — | ||
| Supply and fixing of 32 A 4P MCB B Curve IS/IEC 60898-1 (2002) 10 kA breaking capacity IP20protected terminals of model no.402463 of Legrand make or it's equivalent. | — | — | — | 35,536 | |
| — | 10.00 | — | — | ||
| Supply and fixing of 40 A Electromechanical 4P RCBO 30 mA sensitivity as per in accordance with IS12640-2 & IEC 61009-1, of Model No.DHBMACTN8030040 of Havell's Make or its equivalent withnecessary connections and all accessories complete | — | — | — | 47,730 | |
| — | 1000.00 | — | — | ||
| Supply and laying of 32 mm dia 2 mm thick PVC pipe (ISI mark) concealed in roof slab and wall withall required accessories including masonry work(chipping etc.) and labour charges etc (for main tosub mains). | — | — | — | 63,000 | |
| — | 120.00 | — | — | ||
| Supply, fixing, connecting and commissioning of 35/36W LED Panel light fitting 2'x2' square type White with otherconnected accessories etc. Make: Havells/Crompton/Philips/Bajaj/Orient or similar | — | — | — | 3,63,120 | |
| — | 12.00 | — | — | ||
| Supply and fixing of Ventilating Fans(Exhaust fan) of 4 pole 300 mm sweepsize with metallic body with capacitorconforming to IS No.2312/67 (Reaffirmed2005) complete with louver and allconnected accessories. Make:Havells/CG/Bajaj/Khaitan | — | — | — | 27,360 | |
| — | 40.00 | — | — | ||
| Supply and fixing of B curve DP MCBs of 32 A with all connected accessories as per IEC 60898-1 with its latestamendments. | — | — | — | 28,040 | |
| — | 20.00 | — | — | ||
| Supply and Erection of B curve 16A DP MCBs of Rated Short-Circuit Breaking Capacity 10kA of IP 20 Protection asper IS/IEC 60898 - 1 with its latest amendments with all connected accessories. | — | — | — | 13,100 | |
| — | 60.00 | — | — | ||
| Supply and Erection of B curve 16 SP MCBs of Rated Short-Circuit Breaking Capacity 10kA of IP 20 Protection asper IS/IEC 60898 - 1 with its latest amendments including all connected accessories. | — | — | — | 13,620 | |
| — | 20.00 | — | — | ||
| Supply and Erection of B curve 20A SP MCBs of Rated Short-Circuit Breaking Capacity 10kA of IP 20 Protection asper IS/IEC 60898 - 1 with its latest amendments including all connected accessories. | — | — | — | 4,540 | |
| — | 26.00 | — | — | ||
| Supply, fixing and connecting of 2pole 2 module 32A Lexic RCBOs conforming to IS 12640-2(2008) with its latestamendments as advised by the site supervisor with all necessary accessories complete. | — | — | — | 89,856 | |
| — | 21.00 | — | — | ||
| Supply and fixing of 63 A 4P MCB C Curve, 10 KA capacity with necessary connections and all accessoriescomplete. | — | — | — | 57,561 | |
| — | 18.00 | — | — | ||
| Supply of DPX3 160+18 of 8 way DB of legrand cat no.5077 47 with metal door with provision for incomer ofMCCB up to 160 Amps , bus bar of capacity 250A and outgoing for 18 Module with busbar din and neutral linkwith all necessary accessories complete or equivalent make. | — | — | — | 2,91,816 | |
| — | 11.00 | — | — | ||
| Supply and installation of DPX3 160 thermal magnetic based release ; Icu = 36K A; 100A 4 Pole MCCB conformto IEC 60947-2 of model no. 4200 95 of Legrand make or equivalent make with extended ROM , spreader links (2sets). | — | — | — | 1,00,529 | |
| — | 1400.00 | — | — | ||
| Providing and fixing sheetmetal work in CRCA sheetwith fabrication of boxespanel boards etc. includingcutting, bending, drilling,welding, riveting etc.treated with anti-rusttreatment and duly powercoated as per the abovespecification. | — | — | — | 3,48,600 | |
| — | 250.00 | — | — | ||
| Supplying and erecting of50 mm x 5 mm sizeelectrolyte copper patti orbar in bus bar chamber / inpanel or any other purpose,500 V with require capacitywith 99.9% copper puritywith fixing arrangement(like lug or bottle type lug)to both the end with highgrade polyolefin insulationsleeve complete | — | — | — | 2,82,500 | |
| — | 4.00 | — | — | ||
| Supplying and erecting LTCT multifunction DLMScompliance energy meter of accuracy of class 0.5with optical & RS 232 port,backlit LCD, measures &displays tri vector energy,load survey, TOD, tamperdetection & logging, powerON /OFF events,instantaneous parametersof rating 1/5 A with displayin absence of powercomplete with zeroadjustment & testcertificate frommanufacturer erected onprovided M.S. box andconnected to CTs suitablefor 3x240V,50 Hz. | — | — | — | 32,548 | |
| — | 24.00 | — | — | ||
| Supplying and erecting LTcurrent transformer withbar primary 50/5 to 1000/5ratio with 15 VA burdenerected in provided CRCAbox duly secured withinsulating materialsconnected to the meterwith test certificates. | — | — | — | 21,072 | |
| — | 4.00 | — | — | ||
| Supplying and erectingpanel mounting type digitalammeter having three andhalf digit LED display,external CT operated,calibrated for 0 to 1000AAC supply with necessaryPVC wire leads and lugsand mounting hardware onprovided panel completewith calibration certificatefrom manufacturer suitableto operate on 500V. | — | — | — | 5,444 | |
| — | 4.00 | — | — | ||
| Supplying and erectingpanel mounting type digitalvoltmeter having Three andhalf digit LED display,calibrated for 0-750V ACsuitable to operate on 500VAC supply with necessaryPVC wire leads and lugsand mounting hardware onprovided panel completewith calibration certificatefrom manufacturer suitableto operate on 500V. | — | — | — | 5,220 | |
| — | 8.00 | — | — | ||
| Supplying and erectingselector switch suitable forvoltmeter/ammeter for 3phase AC supply500/1000V, 50Hz, onprovided box / panel andduly connecting withnecessary PVC wire leadsand lugs. | — | — | — | 2,560 | |
| — | 8.00 | — | — | ||
| Supply & provision of 3 NosRYB indication lamps ofLED type including with allconnected accessoriescomplete. | — | — | — | 3,504 | |
| — | 20.00 | — | — | ||
| Supply, erection, testingand commissioning of allmaterial, excavation, andcasting of cement concretefoundation/concreting inratio 1:3:6 | — | — | — | 1,20,140 | |
| — | 6.00 | — | — | ||
| Supply, fixing, testing andcommissioning ofMicroprocessor Release400 A range; 4Pole, MCCBsuitable for operation on415V,50 Hz 3 Phase ACsupply in LT Panel withsupply of all connectedaccessories and alliedmaterials as perspecification attached.Make: L&T/Legrand/Havells Or Similar | — | — | — | 2,09,670 | |
| — | 2.00 | — | — | ||
| Supply & fixing testing andcommissioning of 400A on-load change over switchsuitable to operate on415V, 50Hzconforms toIS:13947-3 with sheetsteel enclosure fronthandle operated. Make:L&T/Legrand/Havells OrSimilar | — | — | — | 59,530 | |
| — | 7.00 | — | — | ||
| Supply, fixing, testing andcommissioning ofMicroprocessor Release200-250 A ; 4Pole, MCCBsuitable for operation on415V,50 Hz 3 Phase ACsupply in LT Panel withsupply of all connectedaccessories and alliedmaterials as perspecification attached.Make: L&T/Legrand/Havells Or Similar | — | — | — | 1,57,822 | |
| — | 4.00 | — | — | ||
| Supply, fixing, testing andcommissioning ofMicroprocessor Release160 A ; 4Pole, MCCBsuitable for operation on415V,50 Hz 3 Phase ACsupply in LT Panel withsupply of all connectedaccessories and alliedmaterials as perspecification attached.Make: L&T/Legrand/Havells Or Similar | — | — | — | 70,156 | |
| — | 6.00 | — | — | ||
| Supply, fixing, testing andcommissioning ofMicroprocessor Release125 A ; 4Pole, MCCBsuitable for operation on415V,50 Hz 3 Phase ACsupply in LT Panel withsupply of all connectedaccessories and alliedmaterials as perspecification attached.Make: L&T/Legrand/Havells Or Similar | — | — | — | 85,182 | |
| — | 1.00 | — | — | ||
| Fabrication and erection of 14 SWG CRCA sheet steel enclosure of suitable size for outdoor distribution Panel with IP 54 protection, plinth mounted with Double Door, including cutting, bending drilling, welding and revetting etc, complete with cleaning with 7 tank process and painting with EPOXY powder coating including cost and conveyance of all materials and labour charges. The MDBs shall be mounted on suitable required size of CC plinth (CC plinth cost will be paid separately)/ wall mounted and secured with bolts, nuts and washers as advised by Engineer at site. The panel comprising of 1600A tinned Copper Bus Bar RYB & N of same size) as per IS 613: 2000 or latest amendment required shape supported with appropriate DMC / SMC barriers and colour coded with heat shrinkable sleeves, LT 3 Phase Digital Multifunction energy meter with 3 lines LCD display for measuring all the parameters( Voltage/ Current/ Power/Frequency/power factor /kw/kwh/ kvar/kvarh) , Current T/Fs, indication lamps for incoming & outgoing feeders. support insulators, neutral links, Incoming & outgoing terminals, suitable cable termination glands , grommets, lugs, connecting wires and all other accessories with the following switchgear and accessories. Suitable busbars has to provided for the incomings of all the MCCB's from main bus barThe cables should be properly terminated in the switchgears with necessary lugs and all necessary accessories complete. The panel should conform to IS/IEC 61439or its amendment in all respects. The panel should comprise of the following Switchgear: 1.Supply and installation of ACB 800 Amps 36KA-2 nos, 2. Supply and installation of on load change over switch of 800A of conforms to IS/IEC:60947-3 or its latest amendments -1 nos, 3.Supply and installation of microprocessor based release; Icu =50KA ; 400A 4 Pole MCCB conform to IEC 60947-2 or latest amendments communication capable for energy management with spreader links (2 sets), phase barriers-2 nos, 4. Supply and installation of 320 A 4P MCCB, 36 KA, Micro processor based adjustable with LSIG protection communication capable conform to IEC 60947-2 or it's equivalent with extended ROM, spreader links(2 sets)-2 nos. 5. Supply and installation of 250 A4P MCCB, 36 KA, Microprocessor based adjustable with LSIG protection communication capable conform to IEC-60947 -2 or its latest amendments model no 4205 39 of legrand make or its quivalent with extended ROM, spreader links (2 sets)-2 nos, 6. Supply and installation of DPX3 160 thermal magnetic based release; Icu = 36KA; 100A 4 Pole MCCB conform to IEC 60947 - 2 or its latest amendments of model no. 4200 95 of legrand make or equivalent make with extended ROM, spreader links (2 sets)-4 no. 7. Supply and installation of DPX3 160 thermal magnetic based release; Icu=36K; 63A 4 Pole MCCB conform to IEC 60947-2 OR ITS LATEST AMENDMENT OF MODEL NO. 4200 93 OF LEGRAND MAKE OR IT'S EQUIVALENT WITH EXTENDED rom, spreaser links (2 sets) -4 nos, 8. Supply and fixing of 40/50/63A A 4P MCB C Curve, 10 KA capacity with necessary connections and all accessories complete-2 nos, 9. Supply and erection of LT 3 phase Digital Multifunction energy meter with 3 lines LCD Display for measuring all the parameters ( Voltage/Current/Power/Frequency/power factor/kw/kwh/kvar/kvarh) on existing box panel board- 14 sets of 3 nos. The LT control panel should manufactured by CPRI approved manufactures only. | — | — | — | 9,04,673 | |
| — | 1000.00 | — | — | ||
| Supply, running and connecting of 4core 16 sq.mm. PVC insulated and PVCRound Sheathed, Multicore AnnealedBare Copper Conductor (flexible)industrial cable for Voltage Grade 1100Volt, Conforming to IS 694 : 2010 orits latest amendment." | — | — | — | 11,96,000 | |
| — | 1200.00 | — | — | ||
| Supplying, erecting & terminatingXLPE armored cable 4 core 400sq.mm. aluminium conductor withcontinuous 12.97 sq.mm. (8 SWG)G.I. 6 earth wire complete erectedwith glands & lugs, on wall/trusses/pole or laid in providedtrench/ pipe as per specification. | — | — | — | 23,36,400 | |
| — | 1200.00 | — | — | ||
| Supply and erection of 160mm HDPEpipe of Grade PE-100. PN 6 (6Kg/Cm2Capacity) with accessories as per IS4984-2016 (SDR-21) | — | — | — | 7,38,000 | |
| — | 1600.00 | — | — | ||
| Supply and laying of 4 core240 sq mm cross linkedpolyethylene (XLPE)insulated LT UG cable, PVCouter sheathed, armouredwith galvanized round steelwire or steel strip and withaluminum conductorsuitable for rated voltage at1100 volts grade andconforming to IS:7098(Part-1)/1988 with amdt.no. 1, 2 & 3 (reaffirmed2005) or latest. | — | — | — | 24,03,200 | |
| — | 1920.00 | — | — | ||
| Supply and erection of110mm HDPE pipe ofGrade PE-100. PN 6(6Kg/Cm2 Capacity) withaccessories as per IS 4984-2016 (SDR-21) | — | — | — | 6,83,520 | |
| — | 400.00 | — | — | ||
| Supply and Laying of 4 core 10 sqmm copper cables XLPE insulated, cores laid up, PVC innersheathed unarmoured 650/1100V grade as per IS 7098(Part 1) 1988. | — | — | — | 1,86,400 | |
| — | 300.00 | — | — | ||
| Supply, Laying, Testing and Termination of 1.1 KV Grade 4 core 16 sq.mm XLPE insulated PVC sheathedAluminium armoured cable as per IS 7098(Part 1)1988 with latest amendments and with necessary lugs andterminations complete. | — | — | — | 42,300 | |
| — | 300.00 | — | — | ||
| Supply, Laying, Testing and Termination of LTUG 4 core 25 sqmm XLPE insulated PVC sheathed Aluminiumarmoured cable as per IS 7098 (Part 1) 1988 with latest amendments and with necessary lugs and terminationscomplete. | — | — | — | 60,900 | |
| — | 300.00 | — | — | ||
| Supply, Laying, Testing and Termination of 1.1 KV Grade 4 core 50 sqmm XLPE insulated PVC sheathedAluminium armoured cable as per IS 7098(Part 1)1988 with latest amendments and with necessary lugs andterminations complete. | — | — | — | 1,02,300 | |
| — | 600.00 | — | — | ||
| Supply, Laying, Testing and Termination of 4 core 120 sqmm XLPE insulated underground armoured aluminiumcable with heat resistant insulation as per IS 7098(Part 1)1988 with latest amendments with necessary lugs andterminations complete. | — | — | — | 5,08,800 | |
| — | 600.00 | — | — | ||
| Supply, erecting and laying of HDPE pipeof PE-80 grade in PN-4 outer dia of HDPEpipe 63 mm (nearest 2" dia) and wallthickness minimum 2.5 mm maximum 2.8mm with "T' joints, bends, elbows etc.including all other connected accessories.Make: M/s.Sudhakar/ Nagarjunapolymer/Nandi/Plasto | — | — | — | 74,400 | |
| — | 100.00 | — | — | ||
| Supply of 100 mm dia 'B' class ERW GIpipe conforming to IS: 1239 Part 1(2004)and fixing with suitable clamps onwall/building including laying of cablethrough GI pipe. | — | — | — | 1,07,400 | |
| — | 800.00 | — | — | ||
| "Cutting of esphated road/ concrete/ cement/under the track etc., and excavation of cable trench 30cm widex90cm deep oad etc., for laying of HT/LTUG cable. After laying of cable the trench should be brought to its original position by providing tar/ concrete/ cement as per the site conditions and asper directions of Rly.Engineer." | — | — | — | 1,62,400 | |
| — | 400.00 | — | — | ||
| Excavation of cable trench 30 cm wide x 90cm deep in all types of soils for HT/LTUG cable as per specification | — | — | — | 48,800 | |
| — | 3400.00 | — | — | ||
| Supply and running of 8 SWG GI wire is tobe laid for earth continuity. | — | — | — | 40,800 | |
| — | 10.00 | — | — | ||
| Supply and erection of earth electrode as perthe enclosed specification (including digging earth pit, electrode earth box with reinforced concrete complete with all connected materials and works including connecting the earth electrode and aerial earthing according to IS 3043 and RDSO drawing ETI/OHE/P/7021 in other than substations. | — | — | — | 37,980 | |
| — | 2.00 | — | — | ||
| "Supply, testing, installation and commissioning of pure sine wave 10 KVA online UPS with180 Ah, 12 Volt Battery Bank consisting of 16 nos Batteries along with Battery Rack. Back up time 180minutes minimum. Switching Technology: IGBT-PWM. With inbuild isolation transformer. Input voltage:AC single phase 160v-260v Output voltage: AC single phase, 230 Volt, 50 Hz. Protection for undervoltage at battery terminal, Short Circuit & overload at UPS output terminal, Overload Limit: 20%overload for minimum 10 minutes, 50% overload for minimum 1 minutes, 50% overload for minimum 3second. Additional 16 nos Batteries with same rated capacity and specification as above along withBattery Rack to be provided as spare battery bank. Battery type SMF-VRLA(Make-As per MII Policy)(Warranty Period : Upto 30 months from the date of delivery.)" | — | — | — | 10,50,200 | |
| — | 2.00 | — | — | ||
| "Three Phase 3 HP Electric Siren, 5 Km Brand: NA (DetailedDescription/Specification as per Product # 1 of GeM Contract No. GEMC-511687763869558dt.15/04/2026)" | — | — | — | 55,456 | |
| — | 1.00 | — | — | ||
| Supply, installation ,testing and commissioning of 40 KVA,415 V ,three phase , 50Hz, diesel Generator set with AMF panel complete in all respect as per specification and CPCB IV+ or latest emission norms as per MoEFCC (Warranty Period : 24 months ) | — | — | — | 7,11,369 | |
| — | 20.00 | — | — | ||
| — | — | — | 2,34,760 | ||
| Installation, Electrode of17.2 rod ofLength required | : - Supply, of earthing enhancingcompound RDSOspecification | Testingand mm diameter 3m along with to fillup the No.RDSO/PE/SPEC/PS/0109(Rev.0)-2008 | ofmaintenance 250micron friendly | ||
| — | 500.00 | — | — | ||
| Supply, fabrication, laying,welding and connection ofGI Flat of size 25x3 mmfrom earth pit with GI nutBolt suitable size | — | — | — | 46,500 | |
| — | 1.00 | — | — | ||
| Supply, fixing, testing, connecting and commissioning of 1.5 Ton capacity Hi wall splitinverter Air conditioner 5 star rated with hermitically sealed Copper Condensor and ISEER> 5.5, R-32 Refrigerant including all accessories & fixing of Outdoor Mounting Stand etc.with required lenght of the cables between indoor and outdoor units Note: (1) AC unitsupplied to railways must match with the BEE Star Rating valid as on the date of supply.(2)The Product must be registered, on the name of Consignee, with OEM, after successfulinstallation | — | — | — | 65,110 | |
| — | 8.00 | — | — | ||
| Supply, fixing, testing, connecting and commissioning of 2.0 Ton capacity Hi wall splitinverter Air conditioner 5 star rated with hermitically sealed Copper Condensor and ISEER5- 5.5, R-32 Refrigerant including all accessories & fixing of Outdoor Mounting Stand etcwith required lenght of the cables between indoor and outdoor units Note: (1) AC unitsupplied to railways must match with the BEE Star Rating valid as on the date of supply.(2)The Product must be registered, on the name of Consignee, with OEM, after successfulinstallation | — | — | — | 5,80,560 | |
| — | 60.00 | — | — | ||
| Supply and provision of set of copper pipes i.e. from Indoor to outdoor and outdoor toindoor unit suitable for 1.5-ton/2 ton inverter AC including foam insulation over and aboveof 3 mtrs. of set of pipes supplied along with AC by OEM as per site requirement | — | — | — | 56,880 | |
| — | 30.00 | — | — | ||
| supply and fixing of 16A combined unit with concealed metal box with 4M cover Plate +16A c curve MCB + 16A Socket + 16A Magnus plug top equivalent to model no: AA 4 068of GM make (glossy white) for AC points. | — | — | — | 23,880 | |
| — | 30.00 | — | — | ||
| Supply and fixing of wall/floor mounting type Voltage stablizer of V-Guard VG 500 VoltageStabilizer forAC up to 2 Ton (170 - 270 V) with all connected accessories and works.Makes v- guard,keeline.. | — | — | — | 70,080 | |
| — | 6.00 | — | — | ||
| Supply, installation, testing, gas charging & commissioning of 2TR capacity Inverter type, copper coil, BEE star cassette AC unit with all connected accessories. | — | — | — | 7,06,284 | |
| — | 7.00 | — | — | ||
| Supply, installation, testing, gas charging & commissioning of 3TR capacity, Inverter type, copper coil, BEE star cassette AC unit with all connected accessories. | — | — | — | 11,39,215 | |
| — | 13.00 | — | — | ||
| Supply, fabrication and fixing of suitable size out door wall mounted chair type MS base frame stand for outdoor unit2/ 3.0TR cassette unit including all connected accessories etc. | — | — | — | 31,707 | |
| — | 130.00 | — | — | ||
| Supply of 1" CPVC Drain pipe with all connected accessories as per site requirement. | — | — | — | 19,240 | |
| — | 130.00 | — | — | ||
| Erection of 1" CPVC Drain pipe with all connected accessories as per site requirement. | — | — | — | 1,430 | |
| — | 130.00 | — | — | ||
| Supply of copper pipe 1/4" & 1/2" of 20 SWG along with 9 mm thickness insulation | — | — | — | 1,42,870 | |
| — | 130.00 | — | — | ||
| Erection of copper pipe 1/4" & 1/2" of 20 SWG along with 9 mm thickness insulation | — | — | — | 7,150 | |
| — | 4.00 | — | — | ||
| Supplying, Installation, Testing & Commissioning of 20HP Variable Refrigerant Flow air cooled Out door units of 20HP having 100%hermetically sealed inverter typ e twin Rotary/Scroll Compressor(s), minimum two compressors (with individual separate PCB), microprocessor based Controller,top discharge type condensing unit(s),with R-410A Refrigerantor equivalent, vibration Isolators with suitable foundation etc.complete as required. To have better efficiency condenser fan shall be capable to operate at differents peed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS18728:2024 and work even at 50°C ambient temperature without tripping. The system shall be able todeliver 100%of the rated capacity upto39dEGC. The unit shall be suitable to work on 400V+/-10%, 3Phase, 50Hz AC power supply and BMS compatible. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilicfilm to prevent water accumulation on the surface of the heat exchanger,enhance water dispersion, and reduce the risk of degradation, t here by improving overall performance and durability. | — | — | — | 15,28,880 | |
| — | 8.00 | — | — | ||
| "Supplying, Installation, Testing and Commissioning of following minimum capacity of 8.0 TR and external static pressure VRF/VRV ceiling mounted high ductable type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration Isolators, drain pan, drain pump, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± 10%, 50 Hz complete asrequired. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Singnals. The coolingcapacity of indoor unit will be at air inlet conditions of 27 0C DB and 19 0C WB temperature. (Make will be same as of Outdoor )" | — | — | — | 6,81,528 | |
| — | 24.00 | — | — | ||
| "Supplying, Installation, Testing and Commissioning of Y/T/Multi Joints. Joints shall be of same Original EquipmentManufacturer (OEM) make as of ODUs and IDUs for Indoor Units" | — | — | — | 1,08,840 | |
| — | 6.00 | — | — | ||
| "Supplying, Installation, Testing and Commissioning of Y/T/Multi Joints. Joints shall be of same Original EquipmentManufacturer (OEM) make as of ODUs and IDUs for Outdoor Multi Joint" | — | — | — | 48,588 | |
| — | 140.00 | — | — | ||
| "Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper of 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2mm refrigerant piping for VRV/VRF system, complete with fittings, with suitableadjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :" | — | — | — | 86,100 | |
| — | 40.00 | — | — | ||
| "Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper of 19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm refrigerant piping for VRV/VRF system, complete with fittings, with suitableadjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :" | — | — | — | 29,560 | |
| — | 90.00 | — | — | ||
| "Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper of 28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm refrigerant piping for VRV/VRF system, complete with fittings, with suitableadjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :" | — | — | — | 1,04,130 | |
| — | 70.00 | — | — | ||
| "Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper of 34.9 mm dia (OD) (Hard drawn) with tube thickness 1.62 refrigerant piping for VRV/VRF system, complete with fittings, with suitableadjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :" | — | — | — | 90,020 | |
| — | 30.00 | — | — | ||
| "Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper of 41.27 mm dia (OD) (Hard drawn) with tube thickness 1@46>10@mm refrigerant piping for VRV/VRF system, complete with fittings, with suitableadjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :" | — | — | — | 41,040 | |
| — | 12.00 | — | — | ||
| Supply of remotes for VRF conditioners | — | — | — | 12,000 | |
| — | 300.00 | — | — | ||
| Supply, Installation, Testing and Commissioning of CONTROL CABLING of 2Cx0.75sq. Mm and communication cabling (6Cx1.5Sq.mm Shielded)Copper for communication between indoor and outdoor units to be suitably laid in PVC conduit as per site requirement. | — | — | — | 74,400 | |
| — | 200.00 | — | — | ||
| Supply and erection of 2 inch PVC Drain Piping with insulation | — | — | — | 52,400 | |
| — | 300.00 | — | — | ||
| Supply and Installation of 22G With G.I material which is fixed at plunems and starting of duct | — | — | — | 4,42,500 | |
| — | 920.00 | — | — | ||
| Supply and Installation of 24G With G.I material which for all for supply air duct. | — | — | — | 12,48,440 | |
| — | 200.00 | — | — | ||
| Supply & erection of GI duct damper in the Ducting as per site requirement and site enginners instructions | — | — | — | 1,27,400 | |
| — | 300.00 | — | — | ||
| Supply and Installation of Acostic insulation of 10mm which is fix for plunems and starting of duct for the above AC system | — | — | — | 2,65,500 | |
| — | 920.00 | — | — | ||
| Supply & erection of thermal insulation of ducts with 9 mm thick nitrile rubber faced with alluminium foil all round the duct as per instructions of site engineer | — | — | — | 81,880 | |
| — | 400.00 | — | — | ||
| Supply and erection of opposed blade MS volume control damper as per required for the site condition and instruction of site engineer. | — | — | — | 2,26,400 | |
| — | 1.00 | — | — | ||
| Supply of Central Monitoring Unit suitable for monitoring and controlling of all outdoor and indoor units. Total number of Central Monitoring units shall be capable of connecting to all the above indoor units and outdoor units. (Considering unit Lot as Job) | — | — | — | 50,000 | |
| — | 1.00 | — | — | ||
| ITC of Central Monitoring Unit suitable for monitoring and controlling of all outdoor and indoor units. Total number of Central Monitoring units shall be capable of connecting to all the above indoor units and outdoor units (Considering unit Lot as Job) | — | — | — | 5,500 | |
| — | 1.00 | — | — | ||
| Pressure testing of the entrire system with Nitrogen and vaccumizing the nitrogen (Considering unit Lot as Job) | — | — | — | 60,000 | |
| — | 1.00 | — | — | ||
| Supply, installation, testing and commissioning of initial Charge of refrigerant gas - R 410 A (Considering unit Lot as Job) | — | — | — | 2,50,000 | |
| — | 1.00 | — | — | ||
| Lifting , shifting & positioning of VRF Outdoor units (Considering unit Lot as Job) | — | — | — | 60,000 | |
| — | 40.00 | — | — | ||
| Supply and installation of removable core, heavy gauge, powder coated aluminum Diffussers /Grills for Supply Air with coller damper | — | — | — | 2,48,000 | |
| — | 40.00 | — | — | ||
| Supply and installation of removable core, heavy gauge, powder coated aluminum Diffussers /Grills for Return Air without coller damper. | — | — | — | 2,20,000 | |
| — | 8.00 | — | — | ||
| Supply and Installtion of Canvas Connections | — | — | — | 12,000 | |
| — | 4.00 | — | — | ||
| Supply and Instalation of Odu stands | — | — | — | 17,200 | |
| — | 500.00 | — | — | ||
| Supply & installation of Ms Structural work for supporting VRF out door units | — | — | — | 49,000 | |
| — | 1.00 | — | — | ||
| Supply ,installation, testing and commissioning of fire alarm (2 version)addressable loop panel. Make : Honeywell, Ceise fire, Micro guard or similar. | — | — | — | 89,680 | |
| — | 90.00 | — | — | ||
| Supply ,installation, testing and commissioning of addressable optical smoke detector. Make: Honeywell, Ceisefire, Micro guard or similar | — | — | — | 1,76,580 | |
| — | 6.00 | — | — | ||
| Supply ,installation, testing and commissioning of manual call point. Make: Honeywell, Ceise fire, Micro guard or similar. | — | — | — | 21,522 | |
| — | 6.00 | — | — | ||
| Supply ,installation, testing and commissioning of Hooter. Make :Honeywell, Ceisefire, Micro guard or similar. | — | — | — | 25,560 | |
| — | 1000.00 | — | — | ||
| Supply and fixing of 1.5sqm 2 core cable including casing. piping, capping, clamping, under ceiling. Make: polycab, finecab, RR cable or similar. | — | — | — | 2,47,000 | |
| — | 2.00 | — | — | ||
| Supplying and erectingD.C.P. type fireextinguisher 25 kgcapacity cartridge typewith gun metal cap 150gram CO2 gas cartridge,powder and bracketsconforming to IS 2171-1985/ IS 15683 andcomplete erected withnecessary clamps madefrom 50x6 mm M.S. flatwith nuts & boltsgrouted in wallcomplete. Make:Apex/Universal/ Safepro | — | — | — | 24,214 | |
| — | 6.00 | — | — | ||
| Supply and Installation of Analog Addressable Short Circuit Isolator. Make: Honeywell | — | — | — | 13,086 | |
| — | 6.00 | — | — | ||
| Supplying and erecting D.C.P. typefire extinguisher 6 kg capacitycartridge type with gun metal cap 150gram CO2 gas cartridge, powder andbrackets conforming to IS 2171-1985/IS 15683 and complete erected withnecessary clamps made from 50x6mm M.S. flat with nuts & boltsgrouted in wall complete. Make:Apex/Universal/ Safepro | — | — | — | 21,438 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TenderNo.NED-E-21-2026-27NewCTObuilding.pdf
ATTACHMENT
DGSetSpec.pdf
ATTACHMENT
GCC-2022.pdf
ATTACHMENT
GCCCorrectionSlips1to11_compressed.pdf
ATTACHMENT
Earthing Specification
ATTACHMENT
RitesInspectionLetter.pdf
ATTACHMENT
TechCircular05-2022provisionofearthelectrodesearthing3_compressed.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .