Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹84.8 L
EMD Value
₹1.7 L
Closing Date
10 Jan 2020, 4:00 pmClosed
Er Pawan Tickoo
Executive Engineer PWD RandB Electric Div. Jammu
please reffer BOQ
2019_PWDJK_85447_1
e-NIT No. EDJ/143 of 2019-20 Dated 08-11-2019
Open Tender
Electrical Works
Item Rate
Degree College Paloura Jammu
please reffer to NIT
3 documents required · 3 mandatory
₹1,000
Yes
Executive Engineer PWD RandB Electric Div. Jammu
₹1.7 L
Yes
17 Jan 2020
8 Nov 2019
11 Jan 2020
9 Nov 2019
10 Jan 2020
9 Nov 2019
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group C
Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
2 X 6.0 sq. mm + 1 X 6.0 sq. mm earth wire
4 X 6 sq. mm + 2 X 6 sq. mm earth wire
4 X 10 sq. mm + 2 X 6 sq. mm earth wire
4 X 16.0 sq. mm + 2 X 6.0 sq. mm earth wire
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
1 x 1.5 sq. mm
Supplying and drawing co-axial TV cable RG-6 grade, 0.7mm solid copper conductor PE Insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/recessed steel/PVC conduit as required.
Supplying and fixing of following sizes of PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of Recessed conduit as required.
Supplying and fixing following size/modules , GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
1 or 2 module ( 75mm x 75mm)
3 module ( 75mm x 75mm)
4 module ( 125mm x 75mm)
6 module ( 200mm x 75mm)
8 Module (125mmX125mm)
12 Module (200mmX150mm)
Supplying and fixing on exisitng GI Box modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 & 5/6 amps modular socket outlet and 15/16 amps modular switch, connection, painting etc as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings).
Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required.
Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required
5/6Amp Switch
2 way 5/6 Amp 2 way Switch
3 pin 5/6 Amp socket outlet
15/16 A switch
6 pin 15/16 A socket outlet
Telephone socket outlet
TV antenna socket outlet
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
Supplying and fixing call bell / buzzer suitable for D.C./A.C. single phase , 230volts, complete as required.
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.
Installation of exhaust fan upto 450mm sweep in the existing opening, including making the hole to suit the size of the above fan, making good the damage, connection, testing, commissioning etc. as required.
Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes.
Supplying and drawing following pair, 0.5 sq.mm FR PVC insulated copper conductor, unarmoured telephone cable in the existing surface/recessed steel/PVC conduit as required
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
8 way , Double door
12 way , Double door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
4 way (4 + 12), Double door
6 way (4 + 18), Double door
8 way (4 + 24), Double door
Supplying and fixing 5 amps to 32 amps rating, 240 Volts, 'C" series, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Single pole and neutral
Supplying and fixing following Electrical items complete with connections as required.
MCB SPN 40 Amp
MCB SPN 63 Amp
MCB TPN FP 40Amps
MCB TPN FP 63Amps
Fan Box
M.S Deep Box
Angle/Batten Holder
Phenolic laminated round sheet 4" dia average
Aluminium cable twin core 10 sq. mm
Aluminium cable twin core 16 sq. mm
Supply, installation, testing & commissioning of CPRI Approved maintenance free copper earthing system with 3 mtrs. Electrode 40 mm dia with minium 2mm thick and does not require manual additional of water. The electrode shall be pre-filled with hygroscopic powder and provided with suitable breathing and leaching ports at the ends. the electrode shall be surrounded by suitable powdered form of BEE MOIST so as to provide maximum contact between the electrode and the compund. The compound should be eco-friendly and having ROHS certification. The earthing pit should be covered with PVC cover. along with providing and laying of 25 x 3 mm copper strip from copper rod upto the main panel.
Supply, installation, testing & commissioning CPRI Approved of GI Electrode Earthing with 50mm dia and 3 meter length, with 3mm thick the electrode should be hot-dip galvinised. The GI Electrode shall be pre-filled with Cristaline Conductive Materila (CCM). The GI electrode shall be surrounded with BEE MOIST compound to provide maximum contact betwen the electrode and compound should be eco-friendly and having ROHS certification GI Electrode Earthing should be maintinance free and does not require regular manual addition of water GI Electrode shall be tested from CPRI. The earthing pit should be covered with PVC cover. along with providing and laying of 25 x 5 mm G.I strip from G.I rod upto the main panel.
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreousenameled white on both sides, and with inscription in single red colour on front side as required.
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc. as required.
150mm dia R.C.C. Pipe
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
upto 35sq.mm
Above 185 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
upto 35sq.mm
Above 185 sq. mm and upto 400 sq. mm
Supply of 1.1kV Grade XLPE Insulated PVC sheathed Aluminium Armoured cables conforming to IS 7098 Part-II of following ratings conforming to IS 7098 Part-1 with Latest Amendments
3.5C X 300 sq. mm
3.5C X240 sq. mm
4Cx 16sqmm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade as required
3½ X 300 sq. mm (70 mm)
3½ X 240 sq. mm (62mm)
Supplying, installation, testing & commisioning of Lightening fixtures.
20/22 watt LED 4 feet tube light fitting/fixture CRCA housing with 2000 Lumens and min lumens efficiency 100 Lumens/watt P.F 70.95 THD < 16% & voltage input range 140-270 V with Shot circuit & overloading protection circuit off
10/12 watt min.1100 Lumens ( system output), surface mounting having CRCA body, IEC compliant (Mirror Light)
18/20 Watt surface mounted round/square slim panel LED Down Lighter min 1400 Lumens (system output) of die cast aluminium housing and heat sink IEC complaint.
10W LED Endura Bulkhead.
Post top lamps of pure polyester UV resistant powder coated die cast aluminium housing with PMMA clear diffusser of wattage 20 watt
Supply of 1200 mm sweep 230V 50Hz celing fan with double ball bearing with low power consumption (5 star rating)
Supply of following sizes of heavy duty exhaust fan as per approved makes
300mm Sweep
Supply, Installation, Testing and Commissioning of 225mm(w)x38mm(h) 3 compartment GI underfloor raceway.
Supply, Installation, Testing and Commissioning of Galvanised Steel Junction Box of size 225mmX225mm suitable for 225mm(w)x38mm(h) 3 compartment GI underfloor raceway.
Supply , Installation of 9U Network Rack made of CRCA 1.2mm sheet powder coated with RAL9017 color, 4mm toughened tinted glass, Injected one piece polyurethane gasket on frame. Rack components shall be Cooling Fans - 2 Nos, cable Manager - 3Nos, cantilever tray 255D-1 No., Heavy duty stationery shelf, hardware, nuts , power distribution board.
Supply , Installation of 42 U Network Rack made of CRCA 1.2mm sheet powder coated with RAL9017 color, 4mm toughened tinted glass, Injected one piece polyurethane gasket on frame. Rack components shall be Cooling Fans - 2 Nos, cable Manager - 3Nos, cantilever tray 255D-1 No., Heavy duty stationery shelf, hardware, nuts , power distribution boards - 5 Nos.
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed steel/ PVC conduit as required.
Supply erection, 24 Port Patch Panel Cat6
Supply erection, Testing and commisioning of Cat6 UTP keystone connector
Supply erection, Testing and commisioning of Cat6 UTP patch cord 1m
Supply Installation Testing and commisionng of RJ45 outlet in existing oxes / plates / frames
Supply Installation Testing and commisionng of Wifi Access Point with PoE ( 4 Port)
Supply, Installation, Testing and commissioning of 150KVA Indoor type, Unbalanced input , unbalanced output, LV Automatic Servo Voltage Stabilizer indoor type, suitable for input voltage range of 135V to 460V three phase, and out voltage at 433V +/-1%. The stabilizer shall have all necessary protections i.e. overvoltage , undervoltage, surge protection, overcurrent, short circuit. Contractor shall submit necessary documents, drawings for approval before intiating procurement process. Stabilizer shall have suitable arrangement for termination of cables as per site requirements. Stabilizer shall be supplied with first fill of oil, and complete with bypass panel alongwith MCCB's of suitable rating as its protection.
Supply , Installation, Testing and commissioning of POP up box suitable for 6Module accessories mounting.
Supply, Installation of DLP PVC Trunking system on walls consisting of following components.
DLP Trunking Body 50mmx145mm with 2 covers 45mm
End cap
Flat Angle
External Angle
Internal Angle
Flat Junction
4M frame for mounting of Outlets/Swiches
6M frame for mounting of Outlets/Swiches
Supply, Installation Testing and commisisoning of 10kVA min VAH10080 rating Online Double conversion IGBT True Online Uninterrupted Power Supply alongwith 30 Minutes battery backup suitable for three phase 330/415V input and three phase 415V +/-1% output. UPS shall have inbuilt galvanic isolation transformer , automatic and manual byepass system. UPS shall be supplied with SMF batteries, Mounting rack for batteries, internal cabling/busbar for banking of batteries, cabling between UPS to Battery bank. UPS shall have inbuilt protections against short circuit, undervoltage, overvoltage, surge protection, loss of neutral.
Supply, Installation of 10 pair Telephone krone box suitable for Termination of 10 Pair Telephone cable including Krone connectors for 10 Pair cables.
Supply, Installation, Testing and commissioning of Floor Mounted Low Voltage panel IP42 suitable for operation on 433V3 Phase, 50Hz supply, made of 2.0mm CRCA sheet enclosure with Aluminium bus bar Four wire with following switchgears and metering. Necessary arrangement be made for termination of incoming cable and outgoing cables . Contractor to get the G.A. drawings approved before execution. 400A 4P MCCB 36kA - 1 No. 250A 4P MCCB 36kA -1 No. Change over 250 amp 1 No. Digital Energy Meter for Measurement and display (LED/ LCD) of Current, Voltage, Pf. Current Transformer set having Ratio of 160/5, set of protection MCBs Aluminium Bus Bars 4 Wire shall be 600Amps 2 set MCCBs shall be interlocked as required by the scheme , all necessary accessories shall be provided in the panel by the contactors including Indications, Auxilliary contacts etc All MCCB's shall have rotary handle and ICU=ICS 100%.
Supplying, installation ,testing and commissioning floor/wall mounted Busbar chamber of following capacity Bus Bar Chamber made up of 1.6 mm thick IP42 sheet steel enclosure duly painted with powder coating complete with following accessories.4NO Aluminium bus bars having current density of 130A/Sq.cm at nominal current rating in conveinant sections and suitable for 415V,3phase,4wire,50HZ A.C.SUPPLY with 1 No. incomer 63 A 4P MCCB 10kA
Supply, Installation, Testing and commissioning of Floor Mounted Low Voltage panel IP42 suitable for operation on 433V 3 Phase, 50Hz supply, made of 2.0mm CRCA sheet enclosure with Aluminium bus bar Four wire with following switchgears and metering. Necessary arrangement be made for termination of incoming cable and outgoing cables . Contractor to get the G.A. drawings approved before execution. Incomer: 250Amps 4 Pole MCCB 36kA- 1 no. Digital Energy Meter for Measurement and display (LED/LCD) of Current, Voltage, Pf. Current Transformer set having Ratio of 160/5, set of protection MCBs Bus Bar : 600A 4 Wire Aluminium Bus Bar supported on DMC insulator, covered with high quality PVC sleeves. Outgoing : 160 A 4P MCCB 25KA - 2 Nos 63A 4P MCCB 16kA - 2 Nos. 40A 4P MCCB 10 kA -1 No. 63A 4P MCCB 10 kA - 2 Nos. All MCCBs shall be provided with Rotary operating Mechanisam All MCCB's shall have rotary handle and ICU-ICS 100%.
Supply Installation of 7 m long galvanised Steel tabular pole with bracket for mounting of 1 Nos LED street light including making foundation for the pole complete job, wiring from pole junction box to light, junction box with terminal blocks suitable to terminate loop in loop out cable of 4Cx16sqmm Aluminium alongwith installation of 6A SP MCB - 1No. in the box. of Pole .
Supply, Installation, Testing and commissioning of 70W led Street lights having system lumen efficacy of minimmum 100 lumen per watt, 3 kv Surge protection, IP 66, manufacturere name Embossed on dicast Aluminium body .
Supply, installation, testing and commissioning of 82.5 KVA capacity silent DG set comprising of stationary type, Liquid Cooled, turbocharged after cooled developing suitable BHP under NTP condition of BS:5514/ISO3046 & ISO 8528 and alternator brushless, self excited self regulated conforming to BS 5000/IS 4722 suitable for continuous operation, generating 82.5 KVA at 1500 RPM, 415 volts, 0.8 power factor 50HZ, 3 phase. The set shall have Microprocessor/relay based AMF control panel. The Engine and Alternator would be duly aligned and coupled with each other on the common MS fabricated base frame. The sound attenuating system of Silent DG Set shall conform to latest MOEF/CPCB II norms amended upto date, of noise level upto 75db at 1 meter distance. The set shall also have inbuilt fuel tank, fully filled with Diesel, and Batteries. Installation & commissioning of Silent DG Set at site, shall include handling, installation of DG Set on the Cement Concrete Platform, , and Earthing for DG set and Panel as per relevant IS specifications inspected at Manufacturer's works by M/S Cell New Delhi.
Supply, installation, testing and commissioning of Interactive Flat Panel Display ( as per technical specification enclosed)
Supply, installation, testing and commissioning of Cabinet including Controller, Visualizer, UPS, Keyboard and Mouse ( as per technical specification enclosed)
Supply, installation, testing and commissioning of Audio Podium Gooseneck microphone,gooseneck lamp,80W amplifier ( as per technical specification enclosed)
Supply, Installation, Testing and commissioning of Fire Detection system consisting of the following components.
Intelligent analog addressable photothermal multi detector complete with mounting base complete as required.
Intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required.
Addressable manual call point complete as required.
Intelligent addressable programmable sounder complete as required
Response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required.
Supplying, installation, testing and commissioning of Analog Addressable type Active/ Passive Repeater Fire Alarm panel with Backlit LCD Display, having Controls For Reset, Mute, AcceptSilence alarms and Self Test Conforming to BS5839 Standards and Duly approved by EN54/LPCB
Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring &LSZH outer sheath complete as required.
Supplying, installation, testing and commissioning of Full HD 2 MP 1080P D&N IR Dome/Bullet Camera ( as per technical specifications)
Full HD 5 MP 1080P Vandal proof D&N IR Bullet Camera ( as per technical specifications)
Supply Installation Testing & Commissioning of 3 Core Power Cable 1.5 sqmm.
Supply, Installation, Testing and comissioning of 8 port Layer ‑2 managable Switch with Power on Ethernet (PoE) enabled, with 8 nos. 10/100/1000base Tx PoE port with 2 SFP port, 1 no. dual personality Gbe Port for copper/fiber uplink, 20 Gbps switching capacity, 14.88 MPPS Forwarding performance , maximum power consumption 64 watt. ( as per technical specifications)
8 TB surveillance Hard disk storage device.
Micro SD/SDHC Card 128 GB
1 mtr. Cat 6 Networking patch cord cable.
Supply Installation Testing & Commissioning of 42" LED Monitor, Full HD, HDMI Port, Component Video Inputs, Digital Audio Out.
Supplying ,installation testing and commissioning of 32 Channel Network Video Recorder (NVR).
Supply Installation Testing & Commissioning of STP Cat 6 UTP Cable Armoured, Transmission frequency of 250 MHz (Minimum),cable Should be 4 pair and Cable should be Fire Retardant.
Supply Installation testing and Comissioning of 5mtr HDMI cable
Supply Installation testing and Comissioning of Surge protector for CCTV System.
Supply Installation testing and Comissioning of AVR of rating 3KVA complete with isolation transformer.
Supply,installation,testing and commissioning of 3.0 KVA rating online Double conversion IGBT True Online Uniterrupted power supply alongwith battery back up of 2 hours suitable for single phas 90-240 input andoutput220 volt .UPS shall have inbuilt galvanic isolation transformer,automatic and manual bypass system . UPS shall be supplied with SMF batteries,Mounting rack for batteries,internal cabling/busbar for banking of batteries between UPS to Battery bank.UPS shall have inbuilt protections againest short circuit, undervoltage, overvoltage ,surge protection,loss of neutral .
OFC to LAN media convertors
Maqsood Ahamed
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .