Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.0 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹9.7 L+₹43,955 (4.75%)Rejected-AOC | L2 | Rejected-AOC Other than lowest bidder | |
| 3 | L3₹10.7 L+₹1.4 L (15.5%)Rejected-AOC 499 A VIDHYUT NAGAR A AJMER ROAD JAIPUR 302021 | JAIPUR | JAIPUR | RAJASTHAN | 302021 | L3 | Rejected-AOC Other than lowest bidder | |
| 4 | L4₹10.7 L+₹1.5 L (16.3%)Rejected-AOC | L4 | Rejected-AOC Other than lowest bidder |
Tender Value
₹11.8 L
EMD Value
₹23,700
Closing Date
3 Feb 2020, 6:00 pmClosed
GE(S) Jaipur
GE(S) Jaipur, MES, Kalyan Marg, Bani Park, Jaipur-302006
REPAIR AND MAINT TO DG SET AND CONNECTED ITEMS AT NIWARU, JAIPUR MIL STN UNDER GE(S) JAIPUR
2020_MES_313430_1
GE (S)J-49P/2019-20 8540/ /E8
Open Tender
Civil Works
Item Rate
270 days
GE (S) Jaipur
Category E b(i )
9 documents required · 9 mandatory
₹500
Yes
GE (S) Jaipur
₹23,700
Yes
24 Feb 2020
10 Jan 2020
4 Feb 2020
10 Jan 2020
3 Feb 2020
24 Jan 2020
10 Jan 2020 - 17 Jan 2020
Amount
Opening of DG set 15 KVA capacity Air/water cooled by unscrewing nuts, bolts and servicing of DG set, complete servicing, checking of oil, coolant, v-belts, greasing and oiling of parts and toping up , cleaning the inner & outer body, tank and radiator etc by removing sludge etc and reassembling the DG set after repair and replacement of unserviceable parts of DG set and testing complete including comprehensive maintanance of DG sets as per B check with providing qualified staff at the site which will be adequate to perform routine maint and observ and understand the fault, Rectifing the fault if they fail to solve the faults, contractor shall immediatly provied extra specialised work force so as to attend to the fault in minimum reasonable time with out any extra cost.Complete all as specified and including replacement of following spare parts-:- (i) Spin on filter for Lubricating Oil -01 No (ii Diesel filter-01 No (iii)Air Filter - 01 No (iv)Water separator - 01 No (v)primary element - 01 No (vi) secondary element - 01 No Note -Make of DG 15 KVA are Kirloskar,cummines, Ashok Leyland
Opening of DG set 30 KVA capacity Air/water cooled by unscrewing nuts, bolts and servicing of DG set, complete servicing, checking of oil, coolant, v-belts, greasing and oiling of parts and toping up , cleaning the inner & outer body, tank and radiator etc by removing sludge etc and reassembling the DG set after repair and replacement of unserviceable parts of DG set and testing complete including comprehensive maintanance of DG sets as per B check with providing qualified staff at the site which will be adequate to perform routine maint and observed and understand the fault, Rectified the fault if they fail to solve the faults, contractor shall immediatly provide extra specialised work force so as to attend to the fault in minimum reasonable time with out any extra cost.Complete all as specified and including replacement of following spare parts-:- (i) Spin on filter for Lubricating Oil -01 No (ii Diesel filter-01 No (iii)Air Filter - 01 No (iv)Water separator - 01 No (v)primary element - 01 No (vi) secondary element - 01 No Note -Make of DG 30 KVA are Kirloskar,cummines, Ashok Leyland
Opening of DG set 62.5 KVA capacity Air/water cooled by unscrewing nuts, bolts and servicing of DG set, complete servicing, checking of oil, coolant, v-belts, greasing and oiling of parts and toping up , cleaning the inner & outer body, tank and radiator etc by removing sludge etc and reassembling the DG set after repair and replacement of unserviceable parts of DG set and testing complete including comprehensive maintanance of DG sets as per B check with providing qualified staff at the site which will be adequate to perform routine maint and observ and understand the fault, Rectifing the fault if they fail to solve the faults, contractor shall immediatly provied extra specialised work force so as to attend to the fault in minimise reasonable time with out any extra cost.Complete all as specified and including replacement of following spare parts-:- (i) Spin on filter for Lubricating Oil -01 No (ii Diesel filter-01 No (iii)Air Filter - 01 No (iv)Water separator - 01 No (v)primary element - 01 No (vi) secondary element - 01 No Note -Make of DG 62.5 KVA are Kirloskar,cummines
Opening of diesel engine and pump set 7.5 HP capacity Air/water cooled by unscrewing nuts, bolts and complete servicing, checking of oil, coolant, v-belts, greasing and oiling of parts and toping up , cleaning the inner & outer body, fuel tank etc by removing sludge etc and reassembling the diesel engine and pump set after repair and replacement of unserviceable parts and testing complete as per B check with providing qualified staff at the site which will be adequate to perform routine maint , observe and understand the fault, Rectifiy the fault if they fail to solve the faults, contractor shall immediatly provied extra specialised work force so as to attend to the fault in minimum reasonable time without any extra cost.Complete all as specified and including replacement of all existing filters etc.
Supply only of following spare parts for item No-1 to 4 above :- Note:- (i) Fixing charges of these spare parts shall be deemed to be included in respective item of Sch A. (ii) The make of different pats under this item shall be of Kirloskar/cummines/Ashok leyland as per OEM
Lub oil
Coolant additive
Battery for DG SET 12 Volt 88 Ah make-Exide express/AMARON
Battery for DG SET 12 Volt 120 Ah make-Exide express/AMARON
Control panel comprising of composite meter for digital display of voltage, current, Power factor, kW frequency,energy meter and set of push start /stop, acknowledge /reset mains breaker close/trip alternator breaker close /trip and indications of (load on mains, load on set, set fails to start, low oil pressure, high temprature alarm, high temprature trip, alternator over load) self start assembly of 30 KVA DG ashok leyland
Tempratour sensor /HWT sensor assembly of 30 KVA DG ashok leyland
Add on block 2 NO+2 NC make- cat part LADN22 schneider or equivalent in appx "B"
Power contactor(4 pole AC&DC control) current rating 32 amp AC1 rating50 Hz make- cat part LC1 E3210/LC1DT32 schneider or equivalent in appx "B"
Relay card 12 V DC Cat part-RC5CH-1CO-12V DC-DC for 30 KVA DG.
Distilled water in one litre container.
M&L for repairing of AMF panel/LT panels incl welding of doors, fixing of hinges, brazing complete all as specified and directed by engineer in charge.
M&L for preparation of old steel surface for painting two coat of synthetic enamel paint area exc 10 Sqcm complete all as specified and directed by engineer in charge.
M&L for Replacement of change over switch 63 Amps 415 V , 4 pole front handle type as per site requirement complete all as specified and directed.MAKE- Havells cat part IHCNF series OR EQUIVALENT IN ABB/L&T/SCHNEIDER/LEGRAND
M&L for Replacement of change over switch 100 Amps 415 V , 4 pole front handle type as per site requirement complete all as specified and directed.MAKE- Havells cat part IHCNF series OR EQUIVALENT IN ABB/L&T/SCHNEIDER/LEGRAND
M&L Earthing complete as per electrical plate No 5 of MES SSR Part I with galvanised steel plate earth electrode 60 cm x 60 cm x 6.0mm, burried directly vertically in ground in a pit of depth not less than 2.5 metres below ground level with the top edge of earth plate at a depth not less than 1.8m below normal ground level connected to and including galvanised iron or steel earth strip 32X6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel. Earthing wire protected by galvanised iron or steel pipe 50mm bore medium grade and connected to continuous earth wire on pole/ test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be inclusive of excavation and earth work in any type of soil,charcoal, salt,funnel , PCC pit and RCC cover complete all as specified & directed. Note 1- following items deemed to be included in quoted rate (a) Earth electrode. (b) Main earthing lead from earth electrode to test point and further to equipment to be earthed upto 7.5 metre. (c) Material and labour for connecting earth electrode and earthing lead as specified. (d) Adequate quantity of charcoal dust and common salt as per direction. (e) All labour involved including testing of earth net work. (f) Excavation and earth work or drilling hole for electrode. (g) P.C.C. pit and C.I. cover. (h) Funnel with watering pipe, wire mesh and copper lugs etc. as specified. (j) G.I. protection pipe of size ordered specified for protection of earthing lead from mechanical injury or tempering. Note 2 - On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost.
Dismantling old existing earthing system of any size complete.
Supply & fixing earth continuity conductor fixed to panel/ DG set or buried in ground any other indicated situation for loop earthing GI earth strip of size 32 mm x 6 mm all as specified and directed.
Dismantling all electrical connection and Shifting of DG set of Capacity 62.5 KVA silent type from existing location to New location including arranging heavy duty vechicle ,necessary crane or chain pulleys arrangements etc , making good the damages etc as reqd. and reinstallation complete including general checking of DG set in presence of Engineer in charge by attending the oil leakages checking the tightness of the items such as cylinder head bolts, fan belt,fuel piping connection, engine to drive unit coupling and mounting, etc as reqd and making all electric connetion complete
Demolition of existing platform and construction of platform of size 4 mtr x 3 mtr and height 0.6 mtr for diesel generator complete all as shown in Sketch attached as Annexure 'A' and specified in particular specification.
Supply, install, testing and commissioning and testing factory made and tested (CPRI type test certified) LT AMF Panel (KIOSK) out door type IP 65, platform mounted, suitable for 62.5 KVA DG 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet 75mm x 30 mm thick MS Channel frame work, duly powder coated finish. having front and rear openiable hinged double door shuters with aprons and cable allay for cable entry and locking arrangement complete including provision of 65mm Godrej (freedom) lock with 2 keys. Panel must comprise multi functional meter , The scope of work includes provision of the following INCOMING (a) MCCB 100 amp, 4 pole, 25 KA, Ics=100%Icu Adjustable thermal and fixed magnetic setting , 50 Hz, 415 volts grade - 02 No. Make : HPL cat part IHLASF0100# or equivalent IN ABB /LEGRAND (b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 150 Amp, 4 pole, not less than 30cm long mounted on insulators for incomming supply 01 No. (c) Neon indicating lamps (R, Y & B) -01` Set for each incoming (d) LT-CT operated dual sources PLUS multi function meter 96x96 sqmm flush mounted with LCD display measuring & displaying parameters of 2 sources (Mains/generator) in one meter energy accuracy class 0.5 with RS 485 communication with 2 no relay output make- Cat part DUSCT2EMGPD25 of HPL or equivalent in ABB ,schneider Outgoing (a) automatic load transfer chaneover switch 100 amps, 4 pole, 415 volts 50 Hz front operated - 01 Nos. Make: Cat part ATS1004POXS in HPL or equivalent in ABB (b) Neon indicating lamps (R, Y & B) -01` Set for each outgoing (c) spare -01 Nos with MCCB 63 amp, 4 pole, 25 KA, Ics=100%Icu Adjustable thermal and fixed magnetic setting , 50 Hz, 415 volts grade Make : HPL cat part IHLASF063 or equivalent IN ABB /LEGRAND (d) spare -01 Nos with MCCB 25 amp, 4 pole, 25 KA, Ics=100%Icu Adjustable thermal and fixed magnetic setting , 50 Hz, 415 volts grade Make : HPL cat part IHLASF025 or equivalent IN ABB /LEGRAND
Excavation in trenches n.exc 1.5metre wide and n.exc 1.5 metre in depth for foundation etc or for laying of cable etc and getting out in soft/loose soil.
Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25 Cm in depth.
Removing of excavated material (soil) to a distance n.exc 50 metre and depositing where directed at a level n.exc 1.50metre above the starting point.
M & L Bricks for protection cover to under ground cable (with old size sub class ‘B’ bricks) laid flat abutting each other with width of protection being equal to length of brick. The gap between adajcent bricks shall not exceed 10 mm as directed by Engineer-in-Charge.
laying only Bricks for protection cover to under ground cable (retrieved undamaged old sub class 'B' bricks during excavation for laying of cable) with width of protection equal to length of brick laid flat abutting each other with width of protection being equal to length of brick. The gap between adajcent bricks shall not exceed 10 mm as directed by Engineer-in-Charge.
M & L Sand cushioning to PVC under ground cable with screened and washed sand and punning to provide a required cover.
Taking out old U/S LT U/G cable of following sizes :-
16 Sqmm, 4 core cable
25 Sqmm, 4 core cable
50 Sqmm, 3½ core cable
70 Sqmm, 3½ core cable
16 Sqmm, 2 core cable
10 Sqmm, 2 core cable
Supply and Laying Cable XLPE insulated screened PVC bedded galvanized steel strips or wire armoured, cables (heavy duty) ISI marked with stranded aluminium conductor, 1100 volts grade and connecting and testing in trenches, under floors/ roads or on walls of following sizes :- (Note 1.: Earth work, excavation shall be measured & paid separately under respective item of Schedule). make- Havells/Gloster/Polycab
16 Sqmm, 4 core cable
25 Sqmm, 4 core cable
50 Sqmm, 3½ core cable
70 Sqmm, 3½ core cable
16 Sqmm, 2 core cable
10 Sqmm, 2 core cable
Supply & fixing or laying galvanised steel tubing light grade (ISI marked) for protection of under ground cable on poles / walls under road crossing etc of following sizes including dismantling & taking down existing pipe :-
100mm bore
80mm bore
50mm bore
M&L for drilling hole under road for laying of U/G cable through pipe of suitable size complete all as specified and directed at site.
S.R.Enterprises
DIVYA ASSOCIATES
M/S Anil Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .