Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹36.6 LAccepted-AOC | L-1 | Accepted-AOC Accept | |
| 2 | L-2₹3.9 L+₹24,700 (6.74%)Rejected-AOC | L-2 | Rejected-AOC Reject | |
| 3 | L-3₹4.4 L+₹72,100 (19.7%)Rejected-AOC 6A BLOCK P PANDAV NAGAR MAYUR VIHAR EAST DELHI DELHI 110091 | EAST DELHI | DELHI | 110091 | L-3 | Rejected-AOC Reject |
Tender Value
₹4.5 L
EMD Value
₹9,100
Closing Date
28 Jul 2020, 3:00 pmClosed
Executive Engineer
O/o PWD BnR Nirman sadan EE Electrical Division, 4th floor Rohtak
Construction of Facilitation Centre at Jahanra Bagh Stadium in District Jhajjar. (Pdg. Fire Alarm System)
2020_HRY_136696_5
PWD/Electrical/101284-101288
Open Tender
Electrical Works
Item-rate/Agreement basic
90 days
Jhajjar
Please refer tender documents.
3 documents required · 3 mandatory
₹500
E.E., Electrical Division, PWD BnR Branch Rohtak
₹9,100
Yes
21 Sept 2020
22 Jul 2020
30 Jul 2020
22 Jul 2020
28 Jul 2020
22 Jul 2020
Amount
SITC of Micro processor based 2 wire fault tolerant, networkable type along with UPS 650VA separately installed (Microtek / Sukam / Luminous make ) Fire Alarm / Detection Control Panel (having nos. of loops to suit minimum 20% extra over the nos. of fire detectors. The panel shall be able to give location of all fire / fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF respective control module when ever any alarm is triggered. The panel shall have rectifier, loop cards, minimum 160 characters LCD unit/ 5.7’’TFT to indicate Fire / Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects. The Panel Shall be sheet Steel power coated, sealed to IP30. The Panel shall have 20 Zones with individual LED Indicators, expandable to 80 LED Indicators. The Panel shall have 3 Serial Ports. The pane\l shall have a built in power supply and battery charger along with maintenance free 24 AH,2 x 12 volt SMF lead acid batteries capable of running for a minimum 24 hours with battery charger complete as required. And conforming to BS5839 standards and Duly Approved by EN 54/UL/VDS/ as per specifications complete in all respect up to the entire satisfaction of Engineer-in – charge of work. (Make: Bosch FPA 5000 Series/ Morley IAS ZXe Series/GST-N-200
SITC of intelligent Analog Addressable type Smoke Detector that combine photo Electronic and fixed temp thermal with inbuilt isolator or isolator base complete with LED Hard Addressable Having rotary decade Address switches, with Mounting Base Complete as required conforming to BS 5839 standards and duly approved by EN54/UL/VDS respect up to the entire satisfaction of Engineer – in Charge of work. (Make: Bosch FAP- OT 420/Morley IAS MI-PTSE-S21+B501/GST-I9101+C9504E.
SITC of addressable heat detector with fixed and rate of raise feature including mounting base with LED etc. complete as required. Each Detector should have 2 as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005. Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m. Shall be EN54/VDs/UL certification. (Detectors without inbuilt isolators may be considered with an addtitional isolator Module after 15 devices (Make: Bosch FAH-440+FAA-440, Siemens Cerberus HI921 + DB-11, Honeywell Morley MI-RHSE+B501, GST-I-9103
SITC of UL/EN54/LPCB listed and FM approved line isloating for isolation the section of circuit in case of short in the addressable loop wiring Make: Bosch / Siemens Cerberus / Morley / Edwards
SITC of intelligent Analog Addressable type Manual Call Point having Surface or flush mounting option fully compliant to EN 54 having Rotary Decade switches for addressing with Back Box for mounting as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. (Make: Bosch FMC-210-DM-G-R/Morley IAS MI-MCPFLEXI/ GST-D19204.
SITC of Addressable Loop powered hooter with strobe complete with mounting base as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. (Make: Bosch/ Morley/GST).
SITC of addressable Control Relay Module with flixible network structures with a mamimum switching current of 1 A @ 30V DC shall be EN54/UL/VDS Certification with all labour and material required to complete the job in all respect upto the entire satisfaction of Engineer-in-charge of the work Makes: Bosch / Siemens Cerberus / Morley / Edwards/GST-I9301).
SITC of Intelligent Analog Addressable Type Monitor Modules having option of RAIL or Surface Mounting with Tri Color LED status indicator with Built in Short Circuit Isolators having Visible Rotary Decade Address Switch from 01-99 dully approved to GEA GEW1-082 conforming to BS5839 Standards and Duly approved by EN54/LPCB/VDS with all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer-in- Charge of work. Makes-Bosch-FLM-42012E/Morley IAS MIDMMI/ GST-I-9300.
SITC of Analog Addressable type Active Repeater panel with Backlit LCD Display, having controls for reset, mute, Accept, Silence alarms and self test conforming to BS5839 standards and Duly approved by EN54/UN54/VDS with all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in Charge of work.(Make: Bosch FMR 500 13/ Morley IAS ZXr-A/GST-NRP-00).
Supply and erection of Fire Extinguisher duly hang on wall with necessary hooks complete in all respect. Make: Safex / Minimax / Cease Fire
(i) ABC dry Powder extinguisher 6 Kg. Cap
SITC of PVC conduit pipe 25mm dia ISI marked (medium) recessed in wall / ceiling etc. including cost of PVC bends inspection box and all other material required to complete the job in all respect upto the entire satisfaction of Engineer-in-Charge of the work. (Based on HSR) Make: Bec / AKG / Kalinga / Diplast
Supply and erection of PVC unsheathed copper conductor cable two core 1100 volts grade in pipe of suitable size excluding cost of erection of pipe. Make: Havells / Polycab / Finolex
SITC of Glow type EXIT sign board photo luminescent of size 300mmx250mmx1.5mm rigid sheet signage containing Zink sulphate as bare chemical class 1 material PSPA fixed on 3mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with cahin and fastener.
SITC of minimum 1000 Mtr. Range Kheraj / National make SIRON generator provided at the roof of the building with separate power SITC relay.
Vowels Technology and Services
DU VENT TECHNOLOGIES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .