SE EWC Gorakhpur
Srirampuram Colony Mohaddipur Gorakhpur
Strenthning Work and Replacement of Damage Cable Under EDC-I Gkp
2024_PVVNV_920941_1
53/EWC(G)/2023-24
Open Tender
Electrical Works
Item Wise
30 days
Gorakhpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,540
SE EWC Gorakhpur
₹25,000
Yes
28 May 2024
1 Apr 2024
15 Apr 2024
1 Apr 2024
12 Apr 2024
1 Apr 2024
Amount
Work No-1 Part-A Particulars (Provided by contractor)
Armoured copper control cable 2 x 2.5 mm2
Armoured copper control cable 4 x 2.5 mm2
Battery charger with 24 Volt battery with cabinet (As per Instruction of Supervision Authority)
Part-B WORK Shifting & loading of following materials on private truck from store centre Gorakhpur & carriage up to 33/11 KV Sub Station Pipraich Gorakhpur Distt-Gorakhpur & Un-loading of the same with proper stacking
33 KV VCB, 750MVA
Dismantling of existing pale fencing and resetting after completion of all related work.
Mounting, Installation, wiring and complete connection of 33 KV VCB with earthing
installation of battery and battery charger in control room and making connection.
Laying from switchyard to control room for 33 KV panel, CT and T/F by digging trench in switchyard including cost of sand and 1st class bricks with covering and making connection complete.
Painting of erected structure in switchyard.
Work No-2 Part -A- Materials (Provided by contractor)
33 KV ‘XLPE’ C/J Kit 3x300mm² Outdoor
33 KV Top channel with clamp (125 x 65 x 3200 mm)
extra support angle for cable support
clamp for extra angle
Number Plate with clamps.
Danger Board with Clamps.
Barbed wire.
Alumunium Paint.
Bolts, Nuts, & Washers.
Red Oxide Paint.
33 KV Stay Rod 20x1800mm
33 KV Stay clamp
stay wire 7/8 SWG
GI Wire 5mm
Earthing Rod 20x2500mm
Al. lug for Dog conductor
PART - B- WORK Shifting, Loading Carriage & Unloading of following materials from store centre Gorakhpur to work site
ACSR Dog conductor
3x300 Sq mm XLPE Cable 33 KV
ST Pole 9 m Long
Laying of 33 KV 3x300 mm² ‘XLPE’ cable(D/C) by digging pit & making trench in Proper size (1.2M depth x1.2M wide) below ground level by fixing bricks(4½˝) on both side of trench wall and 9˝ brick work at the centre of the trench along the cable. Fixing brick slab on top after filling sand around both the cable including cost of bricks and sand. as per site requirement HDD mathod can be used.
Jointing charge of 33 KV ‘XLPE’ C/J Kit 3x300 mm² Outdoor/Straight Through
Laying of 33 KV ‘XLPE’ cable in air after providing 6” dia.M.S. pipe 3m long Complete work.
Labour charges for inserting of MS Pipe, Rising of 33 KV cable and jumpering complete work
Providing and boring of Special Pipe earthing for 33 KV Jointing Kit.
Erection of Double pole structure on 9 mtr ST Pole for only Cable rising including all works of evocation of pit, pole erection, making plinth for poles 30 cm above, grouting in the ratio 1:4:8 (cement, sand, 40 mm brick ballast), back filling of earth, proper ramming & fitting of all accessories (extra angle for cable support with clamps, top channel 125 x 65 x 3200 mm with clamps, danger board with clamp, Aluminium paint, red oxide paint, barbed wire, earthing etc. complete) .
Grouting of stay rods (20 x 1800) mm including all work of excavation, cement concrete in size (0.60 x 0.60 x 0.30) m in ratio 1:4:8 cement, sand, 40mm brick ballast) including back filling, proper ramming etc. Fixing tightening & nozzling of stay wire with stay rod with the poles of required tension requirement.
R N traders
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .