Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Rejected-Technical | Rejected-Technical Not Full field all Technical qualification |
| 4 | Rejected-Technical | Rejected-Technical Not Full field all Technical qualification |
Tender Value
₹5.0 L
EMD Value
₹4,950
Closing Date
13 Oct 2021, 2:00 pmClosed
Superintending Engineer, EUCC-V , Cis-gomti
LESA Bhawan Near Residency, Kaiserbagh Lucknow
INSTALLATION OF 250 KVA TRANSFORMER AND CONSTRUCTION OF REQUIRED 11 KV and LT LINES AT MINI INDUSTRIAL AREA, MAU, MOHANLAL GANJ, LUCKNOW
2021_MVVNL_628632_1
24/EUCC(V)/LESA/2021-22
Open Tender
Electrical Works
60 days
AT MINI INDUSTRIAL AREA, MAU, MOHANLAL GANJ, LKO
As per tender document
2 documents required · 2 mandatory
₹1,180
A/c.No. 10101985364,IFSC CODE No. SBIN0003347,SBI
₹4,950
28 Oct 2021
7 Oct 2021
13 Oct 2021
7 Oct 2021
13 Oct 2021
7 Oct 2021
Amount
Safe Dragging, loading, carriage and unloading of following store materials with proper stacking from ESC Daliganj to JE dump store and JE dump store to work site within municipal areas.
S.T. POLE 11 MT. LONG
S.T. POLE 09 MTR. LONG
V TYPE X-ARM
11 K.V. PIN INSULATOR
11 K.V. PIN WITH NUT
DISC INSULATOR T&C TYPE 45 KN
DISC FITTING T&C TYPE 45 KN
ACSR WEASAL CONDUCTUR
TOP CHANNEL 100X50 MM
MS- ANGLE 65X65X6 MM
GI WIRE 8 SWG
STAY SET COMPLETE 16X1800 MM
STAY WIRE 7/10 SWG
MS- EARTHING ROD 20X2500 MM
TRANSFORMER 250 KVA, 11.04 KV
LT-XLPE CABLE 1X240 SQMM
LT-ABC 3x95+1x70+1x16 SQ MM
LT-DISTRIBUTION BOX 03 PHASE
Construction of masonary type transformer plinth of size 2x2x1.5 m with brick, cement. Coarse sand, sand & brick ballast, filling of sand in the hallow space, plastering outer surface in ratio 1:4:6 top of the plinth 4" thickness grouting of 02 Nos. MS channel of size 100x50x2000 mm on the top of plinth for placement of transformer (All materials will be arranged by contractor).
Construction of fuse unit plinth as per norms installation of fuse unit structure on newly constructed plinth (All materials will be provided by contractor).
Supply and fixing of tail less fuse unit. 500 Amp x 600 Volts
Construction of retaining wall, fabrication and erection of wiremess fencing of 2 mtr height arround T/F and LT-Distribution box including with provision of 01 No. gate with locking arrangement, made of MS Angle Iron os size 50x50x6 mm joint with nuts with bolts. The pannel must be suport with ms flat size 50x50x6 mm wireness of size 10 SWG rectangle type its painting as per norms of RESPO (All materials will arranged by contractor)
Installation and commissioning of 250 KVA T/F
Supply and fixing of 11 KV TPMO.
Supply and fixing of Copper L piece for 250 KVA T/F
Fabrication & erection of S/S type double pole on 11 mtr. long ST-Pole with fixing of top/MS-Channel 100x50 mm, MS-angle 65x65x6 mm, Pin insulator with pin with arrangement of Bus bar and fixing of D.O. fuse set as per Respo norms. (All materials will be provided by contractor except ST-pole, MS- channel, MS- Angle, Pin insulator and Pin).
Laying of Single Circuit LT PVC cable 1x240 Sqmm from Transformer to fuse unit.
Supply, fixing & crimping of reqiured size lugs and its connection with LT lines.
Pipe boring type Earthing 20 mtr deep from ground level or upto water level with ‘B’ class G.I. Pipe 2" dia connection of equipments through GI strip 50x6mm with earthing included in the job as per norms for Transformer/other required equipments (All required material will be provided by contractor).
Digging of pit in Kachcha/Pakka land in depth upto 1/6 length of pole and Dragging of pole from nearby place/dump site to Pit, Erection of single pole along with proper in alignment for 11 KV and LT- Line on 09/11 mtr long ST pole and refilling with ramming of earth
Grouting of pole in depth of 01 mtr below ground level in ratio 1:4:8 in cement, sand and brick ballast as per RESPO norms.
Construction of pole plinth 300 mm x 450 mm above ground level in 1:2:4 in cement, coarse sand and stone gritt as per RESPO norms.
Painting of new erected 09/11 mtr ST pole with two coat of Red oxide paint, PO red paint at top of pole 2 mtr and balance by two coats of best quality aluminium paint of ISI mark as per norms.
Erection of stay set 16x1800 mm by digging of pit of size 0.4x0.6x1.6 mtr including grouting, binding, nuzzling and fixing of stay insulator with stay wire of size 7/10 SWG (All material will be provided by contractor except Stay rod (complete set) and stay wire).
Earthing of poles with MS- Earthing rod 20x2500 mm, earth wire with nut and bolts as per norms (All material will be provided by contractor except MS-Earthing rods).
Straightening of tilted poles.
Cutting/trimming of tree branches which are touching in 11 KV Line.
Fabrication & erection of Single Pole support for 11 KV & LT ABC line composite on 11 mtr long ST-Pole with fixing of X-arm, T-off channel, Disc Insulator with fitting, Pin insulator with Pin, F-bracket, necessary clamps and other accessories like I/J Hook & suspension clamp etc. (All materials will be provided by contractor except ST-Pole & 11 KV X-arm, T-off channel, 11 KV Disc Insulator with fitting and Pin insulator with Pin).
Erection of Single stud pole support of 09 mtr long ST-Pole with fixing of necessary clamps and other accessories required for erection. Its grouting, plinthing & painting etc. are included in this work (All materials will be provided by contractor except ST-Pole).
Stringing and sagging of 03 phase 11 KV line on ACSR Weasel conductor including jumpering & binding as per norms.
Fabrication & fixing of guarding angle on Single and Double poles and guarding of 11 KV O/H line as per Respo norms including fixing of all necessary clamps and hooks etc (All required materials will be provided by contractor except guarding angle and G.I. wire).
Fabrication & erection of Single Pole support for LT ABC line on 09 mtr. Long ST-Pole with fixing of necessary clamps and other accessories like I/J Hook & suspension clamp etc. (All material will be provided by contractor except ST-Pole).
Stringing and sagging of LT line on ABC 3x95+1x70+1x16 Sqmm including jumpering with clamps as per norms.
Erection and commissioning of LT distribution box 03 phase on LT- poles with connection from lines by Pearcing/PG clamps and fixing of other required clamps (All materials will be provided by contractor except LT-Distribution box).
Supply and fixing of required nut and bolts of different sizes
Supply and fixing of 30-40 watt LED street light with fitting Alluminium body and G.I. Pipe 100 mm dia complete set and holding clamp
Supply and fixing of Alluminium conductor cable PVC insulated 16 Sqmm 02 core for connection of street light
Supply and fixing of 32 Amp 240 Volt DP metal claid reviable type switch for street light.
dev engineering corporation
stage.html
html • 0.03 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid