Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.5 LAccepted-Finance | ₹3.5 L | L1 | Accepted-Finance LOWEST BID VALUE |
| 2 | L2₹4.8 LRejected-Finance | ₹4.8 L | L2 | Rejected-Finance HIGHER BID VALUE |
| 3 | L3₹4.8 LRejected-Finance | ₹4.8 L | L3 | Rejected-Finance HIGHER BID VALUE |
| Sl No | Description | Qty | Unit | Firemax Safety & Security Pvt.Ltd. L1 | R. S. ENTERPRISE L2 | Swathik Mahajan L2 |
|---|---|---|---|---|---|---|
| 1.00 | Checking, Cleaning, Rectification, Testing, Refixing & Recommissioning with soft addressing of dismantled Microprocessor-based intelligent, addressable 2 loops fire alarm control panel (FM & EN54 Part 2 & 4 Approved) with its inbuilt 2 Loop Cards and fully networkable with each loop capable of taking minimum 125 devices, a minimum 160 character alpha-numeric liquid crystal display. After recommissioning the panel shall be able to give pin point location of all fire/ fault conditions and must be able to automatically switch off respective control switches whenever any alarm is triggered as per direction of EIC. (Make: - Apollo- MxPro 5 - Departmental Supply) | 2 | Items | 5,000 ₹10,000 | 7,000 ₹14,000 | 7,000 ₹14,000 |
| 2.00 | SITC of Analog Addressable Intelligent Multi-Sensor Detector (FM & EN54 approved) with two inbuilt optical smoke sensor as well as additional heat detector sensor with decentralised intelligence, addressable Phototharmal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard. [Note: Detectors without built-in fault isolator is also acceptable but in such case the agency shall provide one independent fault isolator module for every group of addressable devices (Numbers of addressable devices in a group will be as per latest recommended standards) without any additional cost] as directed by EIC. (Make- Apollo) | 70 | Nos. | 2,010 ₹1,40,700 | 2,760 ₹1,93,200 | 2,760 ₹1,93,200 |
| 3.00 | SITC of Analog Addressable Heat detector (Fixed temperature cum rate of rise) (FM & EN54 approved) with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard. [Note: Detectors without built-in fault isolator is also acceptable but in such case the agency shall provide one independent fault isolator module for every group of addressable devices (Numbers of addressable devices in a group will be as per latest recommended standards) without any additional cost] as directed by EIC. (Make- Apollo) | 4 | Nos. | 2,010 ₹8,040 | 2,780 ₹11,120 | 2,780 ₹11,120 |
| 4.00 | SITC of Analog Addressable Manual Call Point (FM & EN54 approved) with in-built fault isolator as per NFPA style 7 wiring completed as required. [Note: Detectors without built-in fault isolator is also acceptable but in such case the agency shall provide one independent fault isolator module for every group of addressable devices (Numbers of addressable devices in a group will be as per latest recommended standards) without any additional cost] as directed by EIC. (Make- Apollo) | 12 | Nos. | 3,015 ₹36,180 | 3,980 ₹47,760 | 3,980 ₹47,760 |
| 5.00 | SITC of Analog Addressable Hooter (sound output minimum 90dB) cum Strobe (strength of light 10cd) (FM & EN54 approved) complete with necessary modules if required with inbuilt fault isolator as per NFPA style 7 wiring completed as required. [Note: Detectors without built-in fault isolator is also acceptable but in such case the agency shall provide one independent fault isolator module for every group of addressable devices (Numbers of addressable devices in a group will be as per latest recommended standards) without any additional cost] as directed by EIC (Make- Apollo) | 12 | Nos. | 4,015 ₹48,180 | 4,880 ₹58,560 | 4,880 ₹58,560 |
| 6.00 | SITC of 12V, 7Ah Sealed Laed Acid SMF Battery for FACP with voltage regulation (27⁰C) Standby use 13.6V-13.8V, Cycle Use 14.1V-14.4V, Max Initial Current 1.4A (Make: Exide - CS7-12) | 4 | Nos. | 950 ₹3,800 | 1,280 ₹5,120 | 1,280 ₹5,120 |
| 7.00 | Supply & Laying of 2 Core 1.5 sq.mm Unarmoured FRLS Copper Cable (Finolex/Polycab/KEI) with S&F of 20 mm dia "FR" PVC rigid conduit (Precision-Medium) on the surface of the wall/ ceiling by shaddeling complete with all accessories and mending good damages to building works as directed by EIC. | 600 | Mtr | 80 ₹48,000 | 110 ₹66,000 | 110 ₹66,000 |
| 8.00 | Submission of comprehensive Single Line Diagram (SLD) and Quantified List of the installed fire alarm system components upon completion of the commissioning proces. This documentation will mention the block/room names, specific locations of detectors, Manual Call Points (MCP), hooters, and the associated cable path lines. Autocad Soft Copies in .dwg format as well as printed hard copies of the SLD and List will be provided within three days of the commissioning date, ensuring timely and accurate documentation for all relevant as directed by EIC. | 2 | Items | 1,000 ₹2,000 | 2,500 ₹5,000 | 2,500 ₹5,000 |
| 9.00 | Add: GST @18% on total amount of above items as applicable | 1 | Item | 53,442 ₹53,442 | 72,136.8 ₹72,136.8 | 72,136.8 ₹72,136.8 |
| 10.00 | Add: LWC @1% on total amount of above items as applicable | 1 | Item | 3,503.42 ₹3,503.42 | 4,728.97 ₹4,728.97 | 4,728.97 ₹4,728.97 |
Tender Value
₹3.5 L
EMD Value
₹7,085
Closing Date
3 Jun 2026, 12:05 pmClosed
Assistant Engineer, PWD, NMCH Electrical Sub-Divn.
32, Gorachand Road, Kolkata-700014
WBPWD/AE/eNIT17/2025-26/2nd Call
2026_WBPWD_5014150_1
WBPWD/AE/eNIT17/2025-26/2nd Call
Open Tender
Electrical Work/ Equipment
20 days
CPH
Please refer Tender documents.
4 documents required · 4 mandatory
₹7,085
O/O The Asst. Engr., PWD, NMCH Elect. Sub-Divn.
30 Jun 2026
20 May 2026
3 Jun 2026
20 May 2026
3 Jun 2026
22 May 2026
22 May 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Checking, Cleaning, Rectification, Testing, Refixing & Recommissioning with soft addressing of dismantled Microprocessor-based intelligent, addressable 2 loops fire alarm control panel (FM & EN54 Part 2 & 4 Approved) with its inbuilt 2 Loop Cards and fully networkable with each loop capable of taking minimum 125 devices, a minimum 160 character alpha-numeric liquid crystal display. After recommissioning the panel shall be able to give pin point location of all fire/ fault conditions and must be able to automatically switch off respective control switches whenever any alarm is triggered as per direction of EIC. (Make: - Apollo- MxPro 5 - Departmental Supply) | 2 | Items | 1.25 | ₹2.5 |
| 2 | SITC of Analog Addressable Intelligent Multi-Sensor Detector (FM & EN54 approved) with two inbuilt optical smoke sensor as well as additional heat detector sensor with decentralised intelligence, addressable Phototharmal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard. [Note: Detectors without built-in fault isolator is also acceptable but in such case the agency shall provide one independent fault isolator module for every group of addressable devices (Numbers of addressable devices in a group will be as per latest recommended standards) without any additional cost] as directed by EIC. (Make- Apollo) | 70 | Nos. | 1.25 | ₹87.5 |
| 3 | SITC of Analog Addressable Heat detector (Fixed temperature cum rate of rise) (FM & EN54 approved) with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard. [Note: Detectors without built-in fault isolator is also acceptable but in such case the agency shall provide one independent fault isolator module for every group of addressable devices (Numbers of addressable devices in a group will be as per latest recommended standards) without any additional cost] as directed by EIC. (Make- Apollo) | 4 | Nos. | 1.25 | ₹5 |
| 4 | SITC of Analog Addressable Manual Call Point (FM & EN54 approved) with in-built fault isolator as per NFPA style 7 wiring completed as required. [Note: Detectors without built-in fault isolator is also acceptable but in such case the agency shall provide one independent fault isolator module for every group of addressable devices (Numbers of addressable devices in a group will be as per latest recommended standards) without any additional cost] as directed by EIC. (Make- Apollo) | 12 | Nos. | 1.25 | ₹15 |
| 5 | SITC of Analog Addressable Hooter (sound output minimum 90dB) cum Strobe (strength of light 10cd) (FM & EN54 approved) complete with necessary modules if required with inbuilt fault isolator as per NFPA style 7 wiring completed as required. [Note: Detectors without built-in fault isolator is also acceptable but in such case the agency shall provide one independent fault isolator module for every group of addressable devices (Numbers of addressable devices in a group will be as per latest recommended standards) without any additional cost] as directed by EIC (Make- Apollo) | 12 | Nos. | 1.25 | ₹15 |
| 6 | SITC of 12V, 7Ah Sealed Laed Acid SMF Battery for FACP with voltage regulation (27⁰C) Standby use 13.6V-13.8V, Cycle Use 14.1V-14.4V, Max Initial Current 1.4A (Make: Exide - CS7-12) | 4 | Nos. | 1.25 | ₹5 |
| 7 | Supply & Laying of 2 Core 1.5 sq.mm Unarmoured FRLS Copper Cable (Finolex/Polycab/KEI) with S&F of 20 mm dia "FR" PVC rigid conduit (Precision-Medium) on the surface of the wall/ ceiling by shaddeling complete with all accessories and mending good damages to building works as directed by EIC. | 600 | Mtr | 1.25 | ₹750 |
| 8 | Submission of comprehensive Single Line Diagram (SLD) and Quantified List of the installed fire alarm system components upon completion of the commissioning proces. This documentation will mention the block/room names, specific locations of detectors, Manual Call Points (MCP), hooters, and the associated cable path lines. Autocad Soft Copies in .dwg format as well as printed hard copies of the SLD and List will be provided within three days of the commissioning date, ensuring timely and accurate documentation for all relevant as directed by EIC. | 2 | Items | 1.25 | ₹2.5 |
| 9 | Add: GST @18% on total amount of above items as applicable | 1 | Item | 1.25 | ₹1.25 |
| 10 | Add: LWC @1% on total amount of above items as applicable | 1 | Item | 1.25 | ₹1.25 |
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.59 MB
Tendernotice_2.pdf
PDF • 0.51 MB
BOQ_5082107.xls
BOQ • 0.37 MB
Corrigendum_Date_eNIT17_1.pdf
PDF • 0.10 MB
Download all tender documents and submit your bid