Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹40.8 LAccepted-AOC | 1 | Accepted-AOC Accept-L1 | |
| 2 | 2₹42.3 L+₹1.5 L (3.70%)Rejected-AOC | 2 | Rejected-AOC Reject L2 | |
| 3 | 3₹42.5 L+₹1.7 L (4.12%)Rejected-AOC 11TH FLOOR ECO CENTRE BUSINESS TOWER P NO 4 EM BLOCK SECTOR V KOLKATA 91 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | 3 | Rejected-AOC Reject-L3 | |
| 4 | 4₹44.6 L+₹3.8 L (9.19%)Rejected-AOC | 4 | Rejected-AOC Reject-L4 | |
| 5 | 5₹48.1 L+₹7.2 L (17.7%)Rejected-AOC 1ST FLOOR KRISHNA TOWERS OPP TO THRIKKAKARA TEMPLE THRIKKAKARA P O COCHIN 682 021 | ERNAKULAM | KERALA | 682021 | 5 | Rejected-AOC Reject-L5 |
Tender Value
₹65.8 L
EMD Value
₹1.3 L
Closing Date
9 Jan 2018, 6:00 pmClosed
AGM (E-E)
HAL Airport, Bangalore
Provision of VRF Type Air-conditioning System at GAGAN, Bangalore
2017_AAI_5413_1
AAI/BLR/EE/GAGAN/VRF/17-18
Open Tender
Electrical Works
Works
120 days
GAGAN, Bangalore
As per NIT criteria
12 documents required · 12 mandatory
₹1,120
AAI
₹1.3 L
24 Jan 2020
28 Dec 2017
16 Jan 2018
28 Dec 2017
9 Jan 2018
28 Dec 2017
28 Dec 2017 - 8 Jan 2018
Amount
Supply,Installation,Testing and Commissioning of Outdoor machines for air conditioning system, based on variable refrigerant mass flow with Heat Pump (should run either Heating or Cooling), comprising of minimum one or more full Inverter output scroll compressors, with R410 refrigenrant, condenser coil & fins provided with anti-corrosive treatment, necessary accessories for oil separation, moisture removal, flow control, interconnecting piping, condenser air fan, electrical and microprocessor based panel, interconnecting cabling, all housed inside a weather-proof cabinet suitable for exposed installation on terrace including suitable mounting MS Stand frame.
Supply, Installation Testing and Commissioning of ,high CFM VRF Indoor Unit with multi speed fan, 3 or 4 row Cooling coil of Copper tubes and Aluminum fins, electronic expansion valve, Cleanable filter, drain pan with built in auto drain pump & suitable inter lock between Indoor & the drain pump with the following capacity TR & CFM including Refrigerant "Y" / "T" joints with insulation, as recommended by manufacturer, suitable for the combination of indoor and outdoor machines.
11 TR with 4400 CFM Ceiling suspended Type
8 TR with 3200 CFM Ceiling suspended Type
8 TR with 3200 CFM Floor Mounted Plenum Discharge Type
Supply, Installation Testing and Commissioning of Cassette unit Type , CFM VRF Indoor Unit with multi speed fan, 3 or 4 row Cooling coil of Copper tubes and Aluminum fins, electronic expansion valve, Cleanable filter, drain pan with built in auto drain pump & suitable inter lock between Indoor & the drain pump, rand cord less remote controller with the following capacity TR & CFM including Refrigerant "Y" / "T" joints with insulation, as recommended by manufacturer, suitable for the combination of indoor and outdoor machines.
4 TR with 1250 cfm
Supply, installation, testing and commissioning of refrigerant piping using eddy current free Copper pipes and fittings like elbows, couplers, tee joints, brass fittings, "U" loops, expansion loops etc. Insulation of pipes using 13 mm thick upto 19 mm Cu Pipe & 19 mm thick above 19 mm Cu pipe Nitrile rubber insulation with material having class "O" for fire properties, structural clamps with hard PVC pipe sleeves under the clamps to protect insulation at supports, tagging to enable tracing connectivity to respective units as approved.
9.52 mm dia with 13 mm thick insulation
12.7 mm dia with 13 mm thick insulation
19.05 mm dia with 19 mm thick insulation
22.23 mm dia with 19 mm thick insulation
Supply, Installation, Testing and Commissioning of Communication Cabling with necessary PVC Conduit, ( Suitably layed & tighed with PVC ties on cable trays to connect outdoor units with respective indoor units ).
(2 Core x 1.5 sqmm )
Supply, Installation, Testing and Commissioning of Power Cabling for VRV/VRF Outdoor units to the field isolator.
Supply, laying, testing and commissioning of 1100V grade, XLPE insulated unarmoured Copper conductor cable as per specifications. with end termination of heavy duty double end compression brass cable gland,tapping, crimping, etc. from MCCB to VRF unit. The cabling shall be layed and tightened with PVC ties on suitable supports ,well supported at specific intervals .
(4 Core x 10 sqmm)
(4 Core x 2.5 sqmm)
Supply, installation, testing & commissioning of Drain Piping from the indoor units to the nearest drain main header.
Drain Piping shall be Hard CPVC-. Drain Piping shall be insulated with 9mm electron beam (physically) cross linked polyolefin foam insulation with factory applied reinforced aluminium foil facing on oneside, material having class "O" for fire properties (Make : Thermobreak).
Supply and installation of Factory Fabricated duct Sheet Metal Works as per IS Standards specification. Galvanizing shall be Class VI light coating of zinc, Lock Forming Quality prime material .The Duct shall be supported with Hi-tech Supports
Supply and installation of GI duct sheet metal DAMPER for motorized VCD.
Supply and installation of Actuator to run the shaft of the Volume Control Damper(VCD).(Make : Honeywell, siemens,balemo)
Blue Star Ltd
Snowmex Refrigeration
AIRTECH ENGINEERS
Sterling and wilson Pvt ltd
TRAC FUJICO AIR SYSTEMS LLP
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .