Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹1,000
EMD Value
₹31,000
Closing Date
14 Dec 2024, 2:00 pmClosed
Executive Engineer EDD Leh
PDD Choglamsar
same as above
2024_PDNRE_15177_1
e-NIT No. 129 of ED Leh of 2024-25 dated 07-12-2024
Open Tender
Electrical Works
Turn-key
30 days
Leh
Please refer Tender documents.
6 documents required · 6 mandatory
₹1,000
Payable To Executive Engineer EDD Leh
₹31,000
18 Dec 2024
7 Dec 2024
16 Dec 2024
7 Dec 2024
14 Dec 2024
8 Dec 2024
Amount
DT (Supply Part)
100 KVA, 11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level- 2, (Aluminium wound upto 25kVA, Copper wound for 25kVA or higher kVA ratings) , and with LV Cable Box having detachable Aluminium Gland plate
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp,Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
185 mm² Cable, 1.1kV Grade, PVC Insulated Stranded Conductor FRLS type for 25/63/100kva & 250KVA DTs
9 Mtr. Long Pole,ST-410 SP33)
33kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 900mm
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
33kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 900mm
LT Distribution Box for 100 kVA DTR with TPN MCCB short ckt rating 16 KA for incomer 140Amp and suitable MCCBs for outgoing circuits with terminal extensions
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Three Phase Trivector meter (Smart Meter)
Wedge Connectors/PG Clamps
Danger Plates with Clamps
GI Barbed Wire for Anti Climbing
Cement bottoming 1:2:4 mix as per REC standards.5cum/pole
Painting of Poles Red Oxide
Painting of Poles Aluminium Paint
Transformer Fencing
Sundry items like aluminium lugs, jumper, binding Tape
Installation/Testing/Commissioning (Part)
100 KVA, 11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level- 2, (Aluminium wound upto 25kVA, Copper wound for 25kVA or higher kVA ratings) , and with LV Cable Box having detachable Aluminium Gland plate
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp,Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
185 mm² Cable, 1.1kV Grade, PVC Insulated Stranded Conductor FRLS type for 25/63/100kva & 250KVA DTs
9 Mtr. Long Pole,ST-410 SP33)
33kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 900mm
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
33kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 900mm
LT Distribution Box for 100 kVA DTR with TPN MCCB short ckt rating 16 KA for incomer 140Amp and suitable MCCBs for outgoing circuits with terminal extensions
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Three Phase Trivector meter
Wedge Connectors/PG Clamps
Danger Plates with Clamps
GI Barbed Wire for Anti Climbing
Cement bottoming 1:2:4 mix as per REC standards.5cum/pole
Painting of Poles Red Oxide
Painting of Poles Aluminium Paint
Transformer Fencing
Sundry items like aluminium lugs, jumper, binding Tape
HT Line (Supply Part )
9 Mtr. Long Pole( ST-410 SP33)
DP Structure (80/kg)
GI V cross-arm with top Bracket including clamp(14.631 kg/complete V-set)
30 mm² ACSR Conductor
33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
33kV Polymeric composite Disc Insulator 36kV, 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
Galvinized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Red Oxide
Aluminium Paint
Cement bottoming 1:2:4 mix as per REC standards .45cum /pole
HT Line (Installation/Testing/Commissioning Part)
9 Mtr. Long Pole( ST-410 SP33)
DP Structure (80/kg)
GI V cross-arm with top Bracket including clamp(14.631 kg/complete V-set)
30 mm² ACSR Conductor
33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
33kV Polymeric composite Disc Insulator 36kV, 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
Galvinized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Red Oxide
Aluminium Paint
Cement bottoming 1:2:4 mix as per REC standards .45cum /pole
LT Line (Supply Part)
8 Mtr. Long Pole( ST-410 SP15)
50sqmm LT AB Cable
Tension fitting
Suspension fitting
Straight through cable jointing Kit
Galvinized Nuts and Bolts
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Red Oxide
Aluminium Paint
Cement bottoming 1:2:4 mix as per REC standards .45cum /pole
Single Phase Energy Meter Smart Meter
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Service Cable single core 35sqmm
Service Line 3.5Core 16mmsq
LT Line (Installation/Testing/Commissioning Part)
8 Mtr. Long Pole( ST-410 SP15)
50sqmm LT AB Cable
Tension fitting
Suspension fitting
Straight through cable jointing Kit
Galvinized Nuts and Bolts
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Red Oxide
Aluminium Paint
Cement bottoming 1:2:4 mix as per REC standards .45cum /pole
Single Phase Energy Meter Smart Meter
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Service Cable single core 35sqmm
Service Line 3.5Core 16mmsq
M/S NAWANG PHUNCHOK GOVT CONTRACTOR (BID ID -144465)
M/S STANZIN OTSAL (BID ID -144466)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .