| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹47.8 LAccepted-AOC HO SR NO 73 TAPKIR MALA CHOWK TAPKIR NAGAR KALEWADI PIMPRI PUNE 411017 | PUNE | MAHARASHTRA | 411017 | L1 | Accepted-AOC Lowest amount quoted | |
| 2 | L2₹52.9 L+₹3.1 L (6.15%)Rejected-Finance 1257 SCHEME NO 5 NEAR HB COLLEGE VIJAY NAGAR JABALPUR MP PIN 482002 | JABALPUR | MADHYA PRADESH | 482002 | L2 | Rejected-Finance Second Lowest amount quoted | |
| 3 | L3₹64.2 L+₹14.3 L (28.7%)Rejected-Finance PLOT NO 81 SHANTAJI COLONY JANKI NAGAR JABALPUR MP PIN 482002 | JABALPUR | MADHYA PRADESH | 482002 | L3 | Rejected-Finance Highest amount quoted |
Tender Value
₹44.5 L
EMD Value
₹89,000
Closing Date
15 Feb 2020, 6:00 pmClosed
Shri B M Verma, IDSE, EE(SG)
Garrison Engineer (East), Near COD Estate, Ranjhi, Jabalpur (MP)-482011
As per BOQ
2020_MES_315865_1
8202/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Garrison Engineer (East) Jabalpur
D b(i)
8 documents required · 8 mandatory
₹500
Garrison Engineer (East) Jabalpur
₹89,000
Yes
17 Mar 2020
17 Jan 2020
17 Feb 2020
17 Jan 2020
15 Feb 2020
1 Feb 2020
17 Jan 2020 - 31 Jan 2020
Amount
Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendents, regulators, sockets etc and making good disturbed surfaces of walls, floors, as per existing finishes etc complete all as specified.
Taking down carefully unserviceable/partly unserviceable light fittings any type, tube light fittings and fixtures, etc, and making good to the disturbed surfaces of walls/floor etc to macth with existing surfaces including white washing/colour washing/distempering to match with existing wall/floor/ceiling finishes complete all as specified and directed.
Taking down serviceable/unserviceable electric meter including meter box from existing position carefully for refixing adjacent to main switch board including making good to disturbed surfaces to match with existing surfaces complete all as specified. Note : Unserviceable meters shall be deposited to E/M Store.
Fixing only serviceable electric meter on & including wooden board to the wall and including making good disturbed surfaces to match with the existing surfaces
M&L for the following point wiring with PVC insulated unsheathed stranded copper conductor cable of size 1.5 Sq mm (FRLS), with PVC insulated unsheathed stranded copper conductor cable of size 1.5 Sq mm (FRLS) stranded for earth continuity wire, to be drawn in and including, PVC medium grade conduit not less then 20 mm dia with MS sheet metal sunken switch/Terminal box 1.2 mm thick and hylam switch board cover 3.0 mm thick or PVC moulded switch board and brass screws with cup washers including all necessary wall cutting and making good disturbed surface all as directed and specified Make of cable - FINOLEX / PLAZA / HAVELLS/POLYCAB & Make of PVC conduit & conduit accessories - PLAZA / FINOLEX/ KALINGA. Note : (i) Making good to match with the adjoining surface shall be included in the quoted rate. (ii) Rate shall be included for Cutting/chases of wall/floor/ceiling
-ditto- all as per item No 5 above but One light point controlled by one way switch
-ditto- all as per item No 5 above but One ceiling /exhaust fan point controlled by one switch and regulator
-ditto- all as per item No 5 above but One 3 pin 5 amp socket out point on the same board with other switches.
-ditto- all as per item No 5 above but One 3 pin 5 amps socket out let point on independent board
-ditto- all as per item No 5 above but One bell/buzzer point controlled by one bell push.
-ditto- all as per item No 5 above but One light point controlled by two 2-way switches
-ditto- all as per item No 5 above but for one socket outlet 15 Amp on independent board with 2.5 Sqmm (FRLS) cable and 1.5 Sqmm (FRLS) earth wire.
S&F Switch piano flush type single pole one way 5 amps. Make : Havells/Anchor/ Leader
S&F Switch piano flush button type two ways 5 Amps. Make : Havells/ Anchor/ Leader
S&F Socket out let 2 in one, 5/3 pin 5 Amp. Make : Havells/Anchor/Leader
S&F Switch socket combination 5 Amps 5 pin flush type Make : Havells/ Anchor/Leader
S&F Switch socket combination 5 in 1, 5 pin 5/15 Amps flush type universal. Make : Havells/Anchor/Leader
S&F Ceiling rose, surface bakelite 65x50 mm three terminal complete all as specified Make : Havells/Anchor/Leader
S&F Call bell AC-230 Volt single pole ding dong Make : Havells/Anchor/Leader
S &F Bell push, flush type 5 Amps. Make : Havells/Anchor/Leader
S&F regulator electronic step type 100/120 watt 5 step complete all as specified and directed Make : Havells/Anchor/Leader
S&F Lamp holder insulated body with back plate for angle holder all as per specified Make : Havells/Anchor/Leader
S &F LED tube light fittings decorative ultra slim linear fixture with extruded alluminium heat sink envioromentel friendly Energy efficient ready to use pack, 1x20/18 Watt, 4 feet, surface mounting type extruded pvc, snap on installers and domestic electronic Driver, connector block etc.with all accessories internal prewired & includingconeecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nos. make- Bajaj/Crompton /Havells/Wipro
S &F LED tube light fittings decorative ultra slim linear fixture with extruded alluminium heat sink envioromentel friendly Energy efficient ready to use pack,1x10 Watt, 2 feet, surface mounting type extruded pvc, snap on installers and domestic electronic Driver, connector block etc.with all accessories internal prewired & includingconeecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nos. make- Bajaj/Crompton /Havells/Wipro
Supply and fix LED security light fitting of 45 watt, aluminium pressure dia cast IP 66 with high power LED & LED driver of make Bajaj/Havells/Philips/Crompton
Supply and fix LED security light fitting of 60 watt, aluminium pressure dia cast IP 66 with high power LED & LED driver of make Bajaj/Havells/Philips/Crompton
S&F Surface mounting round, decorative LED down lighter 10-15 WATT and transulent defuser, prefixed with flat profile and mounting clamps etc., complete all as specified Make BAJAJ / Philips / HAVELLS / CROMPTON
S&F LED light fittings decorative 36/34 Watt surface mounting type extruded metal/aluminium body, and electronic LED driver, connector block etc. with all accessories internal prewired & including connecting up with 2 core flexible copper conductor cable with suitable size and mounting clamps etc complete all as specified and directed. Make-BAJAJ/ WIPRO / HAVELLS / CROMPTON
S&F LED light fittings decorative 36/34 Watt recess mounting type extruded metal/aluminium body, and electronic LED driver, connector block etc. with all accessories internal prewired & including connecting up with 2 core flexible copper conductor cable with suitable size and mounting clamps etc complete all as specified and directed. Make-BAJAJ / WIPRO / HAVELLS / CROMPTON
S & F High Bay light fitting 90/100 W LED suitable for hanger up to height 10 meter, die cast aluminium housing with heat dissipation fins, easy to maintain, enclosed type, top opening complete with ballast, lamp, reflector, hosing glass with gasket etc.including electrically connected all as specified and directed.MAKE PHILIPHS/WIPRO/HAVELLS/BAJAJ
S&F in repairs GI pipe 'light grade' bracket 25mm dia- 0.9m long & 2 set of clamps made out of 30x5mm MS flat & fixed with anchor bolt suitable for 45/60W security light fitting complete all as specified and directed
S&F in repairs earth enclosure with 2 pin earth plug socket complete with MCB SP 20/25 Amp,flush mounting type Make - LEGRAND/ABB/L&T
Dismantling unserviceable main switch/ kitkat DBs/ MCB including wooden board from existing position and making good disturbed surfaces of wall to match with existing surfaces
S&F MCB DB made of sheet steel , powder painted with neutral bus bar 200 A, neutral link, IP-43-IK09 protection grade , 415Volts TPN with 4 ways Double door, Make -L&T/ LEGRAND/ SCHNEIDER
S&F MCB DB made of sheet steel, powder painted with bus bar 200 A, neutral link, earth bar and Din rail , 230 Volts SPN with 4 ways Double door IP-43-IK09 protection grade, Make -L&T/ LEGRAND/ SCHNEIDER
S&F MCB DB made of sheet steel , powder painted with nuetral bus bar 200 A, neutral link, earth bar and Din rail ,230 Volts SPN with 8 ways Double door , IP-43-IK09 protection grade, Make -L&T/LEGRAND/SCHNEIDER
S&F MCB DB made of sheet steel , powder painted with nuetral bus bar 200 A, neutral link, earth bar and Din rail , 230 Volts SPN with 12 ways Double door IP-43-IK09 protection grade, Make -L&T/LEGRAND/SCHNEIDER
NOTE FOR ITEM Nos 27 to 30 -(i).The unit rate includes for cutting the brick walls to accommodate DB to make flush to wall/DB to be fixed on wall including frame made out of MS flat 40x5mm (ii).The unit rate includes for making good the disturbed surfaces including finishes to match with the adjoining surface. (iii) MAKE OF DB & MCB L&T/LEGRAND/ SCHNEIDER
S&F in repair of pvc insulated unsheathed bright annealed bare copper conductor 0.5 sq mm cond. const (NO./Dia mm) (16/0.20) single core industrial cable & pvc insulated, pvc round sheathed multicore indistrial cable for voltage grade up to 1100 V as per IS 694:1990 as as site requirement and as directed by Engr-in-Charge. make- polycab/Hevells/Plaza
S&F in repair of pvc insulated unsheathed bright annealed bare copper conductor 0.75 sq mm cond. const (NO./Dia mm) (24/0.20) single core industrial cable & pvc insulated, pvc round sheathed multicore indistrial cable for voltage grade up to 1100 V as per IS 694:1990 as as site requirement and as directed by Engr-in-Charge. make- polycab/Hevells/Plaza
S&F in repair of pvc insulated unsheathed bright annealed bare copper conductor 1 sq mm cond. const (NO./Dia mm) (32/0.20) single core industrial cable & pvc insulated, pvc round sheathed multicore indistrial cable for voltage grade up to 1100 V as per IS 694:1990 as as site requirement and as directed by Engr-in-Charge. make- polycab/Hevells/Plaza
S&F in repair of pvc insulated unsheathed bright annealed bare copper conductor 1.5 sq mm cond. const (NO./Dia mm) (30/0.25) single core industrial cable & pvc insulated, pvc round sheathed multicore indistrial cable for voltage grade up to 1100 V as per IS 694:1990 as as site requirement and as directed by Engr-in-Charge. make- polycab/Hevells/Plaza
S&F in repair of pvc insulated unsheathed bright annealed bare copper conductor 2.5 sq mm cond. const (NO./Dia mm) (50/0.25) single core industrial cable & pvc insulated, pvc round sheathed multicore indistrial cable for voltage grade up to 1100 V as per IS 694:1990 as as site requirement and as directed by Engr-in-Charge. make- polycab/Hevells/Plaza
S&F in repair of Sub main wiring power/circuit using PVC insulated unsheathed, stranded copper conductor cable 2 Single core of size 4 Sq mm, earth continuity conductor of size 2.5 Sq mm to be drawn through and including PVC conduit 25 mm dia medium grade concealed in walls/roof/floors all as directed by Engineer in Charge. Notes:- (i) Two wires of 4 Sq mm and one wire of 2.5 Sq mm and one run of PVC conduit shall be measured as one unit.
S&F in repair of service connection cable using PVC insulated unsheathed, aluminium conductor cable 2 core of size 10 Sq mm, of standred nomenclature follow SEI normes all as directed by Engr-in-Charge.
S&F in repair of service connection cable using PVC insulated unsheathed, aluminium conductor cable 2 core of size 16 Sq mm, of standred nomenclature follow SEI normes all as directed by Engr-in-Charge.
S&F in repair of Sub main wiring power/circuit using PVC insulated unsheathed, stranded copper conductor multicore flexible wires of cable 4 core of size 10 Sq mm, earth continuity conductor of size 2x6 Sq mm to be drawn through and including PVC conduit 50 mm dia medium grade conceled in walls/roof/floors through PVC conduit all as directed by Engineer in Charge.
S&F in repairs MCB TPN 415 Volts, 'C' series, breaking capacity 10 KA of rating 63Amps complete all as specified Make -L&T/LEGRAND/SCHNEIDER
S&F in repairs MCB SPN 240 Volts, 'C' series, breaking capacity 10 KA of rating 63Amps complete all as specified Make -L&T/LEGRAND/SCHNEIDER
S&F in repairs MCB SPN 240 Volts, 'C' series, breaking capacity 10 KA of rating 6-32Amps complete all as specified Make -L&T/LEGRAND/SCHNEIDER
S&F in repairs MCB SP 6-32 Amps 'C' series, breaking capacity 10 KA of rating complete all as specified Make -L&T/LEGRAND/SCHNEIDER
Earthing complete with galvanized steel earth plate electrode 600mm x600 mm x 6mm buried directly in ground vertically to a depth not less then 2.25 meter below normal ground level with top edge of the plate not less then 1.50 meter below normal ground level connected to galvanized earth wire 4.00mmdia by means of bolts ,nuts ,check nuts and washers complete up to and including test point made out of 40 x 6mm alum flat including earthing pit , charcoal common salt ,Earthing lead 4.00mm dia up to 7.5m, 20mm dia medium grade GI watering pipe ,G.I. protection pipe 15 mm dia up to 7.5m long,,PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate ,PCC pit cover including earth work complete all as shown in electrical plate No-3 of SSR-2009 (part-I)
Refixing of servicable MCB any type or size
Taking down partly unservicable tube light fittings any type, and fixtures, etc, and Refixing the same after repair including making good the disturbed surface complete all as specified.
Supply & Fix in repairs LED bulb of 7 Watt make of bajaj / crompton / Wipro
Supply & Fix in repairs LED bulb of 9 Watt make of bajaj / crompton / Wipro
Supply & Fix in repairs LED bulb of 12 Wattmake of bajaj / crompton / Wipro
Supply & Fix in repairs LED bulb of 15 Watt make of bajaj / crompton / Wipro
Supply & Fix in repairs LED tube rod of 18/20 Watt make of bajaj / crompton / Wipro
Supply & Fix in repairs LED Batten suitable for 18/20 Watt LED tube make of bajaj / crompton / Wipro
Supply & fix LED Lamp 40/45 watt type RETROFIT E-22 BASE MAKE : BAJAJ/WIPRO/ KHAITAN/ CROMPTON
Supply & fix LED Lamp 30/35watt type RETROFIT E-22 BASE MAKE : BAJAJ/WIPRO/ KHAITAN/ CROMPTON
Supply & fix LED Lamp 20/25 watt type RETROFIT E-22 BASE MAKE : BAJAJ/WIPRO/ KHAITAN/CROMPTON
S&F in repairs PVC rectangular block of size 100 x100 x50mm for mounting switches, sockets/fan Reg, etc with 3mm thick plastic laminated sheet cover. Make : Anchor/Press fit/Havells/C&S
S&F in repairs PVC rectangular block of size 175 x100 x50mm for mounting switches, sockets/fan Reg, etc with 3mm thick plastic laminated sheet cover Make : Anchor/Press fit/Havells/C&S
S&F in repairs PVC rectangular block of size 200 x150 x50mm for mounting switches, sockets/fan Reg, etc with 3mm thick plastic laminated sheet cover. Make : Anchor/Press fit/Havells/C&S
S&F in repairs PVC rectangular block of size 250 x200 x50mm for mounting switches, sockets/fan Regulator etc with 3mm thick plastic laminated sheet cover. Make : Anchor/Press fit/Havells/C&S
S&F in repairs PVC rectangular block of size 350 x300 x50mm for mounting switches, sockets/fan Reg, etc with 3mm thick plastic laminated sheet cover. Make : Anchor/Press fit/Havells/C&S
Taking down and refixing water storage tank of geyser type electric supplied 230 volts 50 Hz single phase and installed complete with proper fixing arrangement nut bolts & washers properly after repair work of capacity 25/50 ltrs.
S&F water storage tank of Geyser vertical type capacity 25 ltr make of metal stainless steel as specified and directed of make Bajaj/toshiba/Crompton
S&F water storage tank of Geyser horizontal type capacity 25 ltr make of metal stainless steel as specified and directed
S&F water storage tank of Geyser vertical type capacity 50 ltr make of metal stainless steel as specified and directed
S&F water storage tank of Geyser horizontal type capacity 50 ltr make of metal stainless steel as specified and directed
S&F Glass wool of any colour complete all as directed by Engineer-in-Charge
S&F heating element 1500 watt triangular type make of Bajaj / Tosiba / Havells all as specified and directed by Engineer –in-Charge
S&F heating element 1500 watt circular type make of Bajaj / Tosiba / Havells all as specified and directed by Engineer –in-Charge
S&F heating element 2000 watt make of Bajaj / Tosiba / Havells all as specified and directed by Engineer –in-Charge
S&F heatting element 2000 watt for solar system make of Bajaj / Tosiba / Havells all as specified and directed by Engineer –in-Charge
S&F thermostate for geyser Make : Bajaj / Tosiba / Havells as directed by Engineer –in-Charge
S&F neone lamp for geyser yellow / red Make :- L&T/Bajaj/Havells as directed by Engineer –in-Charge
S&F air release valve for geyser as specified and directed
S&F PVC connection armoured type both side brass union type nuts 45/60 cm length as specified and directed
S&F anchor bolts 75mm long made out of stain less steel complete all as specified and directed
S &F in repairs modular Switch piano flush type single pole one way 5 amps. Make GM/Anchor/Plaza
S &F in repairs modular Socket out let 2 in one, 5/3 pin 5Amp Make GM/Anchor/Plaza
S &F in repairs modular Switch socket combination 6 pin, 3 module 5/15 Amps flush type universal Make GM/Anchor/Plaza
S &F in repairs modular Bell push, flush type 5 Amps.Make GM/Anchor/Plaza
S &F in repairs modular Electronic regulator 100/120 Watt step type Make GM/Anchor/Plaza
Taking down and dismantling of ceiling fan, segregation of unserviceable parts, cutting and removing out copper winding, cleaning the armature, rewinding of fan armature with appropriate gauge of super enamelled copper wire with necessary insulating materials such as vertex paper, cotton tape, PVC insulation tape etc varnishing with approved grade of insulation varnish and heating up, re-assembling the fan complete with replacement of unserviceable spares parts, (spareparts will be measured & paid separately) including necessary lathe work for fixing of bush/bearing greasing the same with approved grade of grease, making all electrical connection and supply and fixing the following items and including necessary transportion to workshop, for 1200/1400/1500mm sweep fan :- (i) Split pin - 02 Nos (ii) Connection block - 1 No (iii) Insulation rubber bush. - 01 No
Fixing or hanging only ceiling fan after winding fan under item No. 82 above and connecting up including provision of 3 core 1.5 Sqmm cable from ceiling rose or connector to fan (max up to 1m length) all as specified and directed
All as pr item No. 82 here-in-above but exhaust fan of size 225mm to 450mm sweep (except rubber roll, split pin)
Fixing only Exhaust fan after winding fan under item No. 84 above and connecting up including provision of 3 core 1.5 Sqmm cable from ceiling rose or connector to fan (max up to 1m length) all as specified and directed
All as pr item No. 82 here-in-above but air circulater fan of size 600 mm to 750mm sweep (except rubber roll, split pin)
Fixing only air circulater fan after winding fan under item No. 86 above and connecting up including provision of 3 core 1.5 Sqmm cable from ceiling rose or connector to fan (max up to 1m length) all as specified and directed
All as pr item No. 82 here-in-above but wall fan of size 300 to 400 mm sweep (except rubber roll, split pin)
Fixing only wall fan after winding fan under item No. 88 above and connecting up including provision of 3 core 1.5 Sqmm cable from ceiling rose or connector to fan (max up to 1m length) all as specified and directed
Overhauling of ceiling fan of any make and sweep after opening and cleaning rotor bearing and stator properly and oiling/greasing of bearing/ bushes, reassmbling the same, fixing and coonecting on its existing position and testing on completion all as specified and as directed including taking down. (Note- (A) Overhauling of ceiling fans will be carried out at AGE E/M Yard only. (B) The spares required shall be measured and paid separately in the relevant items).
Taking down exhaust fan, of any size and type & cleaning/servicing and overhauling the same, refixing the same on its existing position and connection up.
Supply, fixing and connecting up flexible copper wire twin core of 23/.0078.
Supply only gun metal bush of any size (Make - MSP).
Supply only bearing for ceiling fan (Make - TATA/SKF No.6201/6202).
Supply only bearing for ceiling fan (Make - TATA/SKF No.6203/6204).
Supply only fan condensor 2.5 MFD (Make – USHA / UNIVERSAL).
Supply only fan condensor 4 MFD (Make – USHA / UNIVERSAL).
Supply only split pin.
S&F canopy of ceiling fan bottom and upper side of size 1200/1400/1500mm Make :- Usha / Orient / POLAR
Painting of ceiling fan 1200/1400 mm sweep complete including fan blade down rod with synthetic enamelled paint of white tint including cleaning and removing dust and dirt and making smooth surface for painting including writing MES No complete all as specified.
Supply & fix fan blade made out of aluminium alloy suitable for wall mounting fan of size 300 to 450 mm
Supply & fix GI tubing light grade 40 mm dia use as down rod of ceiling fan, cut to required length & incl. drilling of hole at both side
Supply & fix GI tubing light grade 20 mm dia use as down rod of ceiling fan, cut to required length & incl. drilling of hole at both side
Supply & fix GI tubing light grade 15 mm dia use as down rod of ceiling fan, cut to required length & incl. drilling of hole at both side
S & F in repairs Mild steel work in framed work such as Fan hooks, Clamps, gratings, ladders etc., with ends of bars welded and/ or riveted, or forged and similar work confirming to Fe 410 - O or Fe 310 - O and incl painting to surfaces using two coats of metallic primer and a coat of synthetic enamelled paint of desired colour as directed.
S& F MCCB DB VERTCLE TYPE made of sheet steel , powder painted with NUTRAL bus bar 200 A, neutral link, IP-43-IK09 protection grade , 415Volts TPN with 4 way Double door , of make Legrand/Seimens/L&T
Taking down of MCCB DB/MCCB of any types and any size
S&F in repairs MCCB 63 A 25 KA,4 POLE ,thermal magnetic relese, Ics=100% Icu complete all as specified Make : L&T / Schneider/Hager
S&F MCCB 100 A 25 KA, 4 POLE ,thermal magnetic relese, Ics=100% Icu complete all as specified Make : L&T / Schneider/Hager
S&F in repairs MCCB 160 A 35 KA, 4 POLE ,thermal magnetic relese, Ics=100% Icu complete all as specified Make : L&T / Schneider/Hager
S&F Single phase KWH meter with LCD display with box of rating 5-30A complete all as spceified and directed by Engr-in-Charge
S&F Three phase four wire KWH meter with LCD display with box of rating 10-40A counter type complete all as spceified and directed by Engr-in-Charge
S&F in repairs infra red light sensor (Ceiling mounted) with adjustable dusk to down setting to sense motion and direct wheather human has moved in or out of the sensor range time delay control min 10 sec plus minus 5 sec, max plus minus 2 min adjustable, light label control 5 lux to 2000 lux, rated load 1100 watt (incandscent), 550 watt halogen or 250 watt LED complete with testing complete all as directed by Engr-in-Charge.Make Vinay, Luker, Phillips, Bajaj.
Taking down ceiling fan /EXHAUST FAN of any size or make
Hanging only ceiling fan 1200mm/1400mm/1500mm during wiring Sweep by providing fan hooks in proper manner and making connection with 3 core copper cable including painting complete all as per specified and directed by Engr-in-Charge
Excavation in trenches, not exc 1.5 mtr wide and not exc 1.5 mtr deep for laying GI/CI pipes etc n.exc 10Sqm on plan and getting out in soft/loose soil complete all as specified and directed
Returning, filling in, including spreading, levelling, watering and well ramming in layer not exce 25Cm thick complete all as specified and directed
Removing excavated soil to a distance not exce 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point all as specified and directed.
M&L for run lead joints for the following size of pipes complete for water mains with spigot & socket pipes and fittings complete all as specified and directed:-
150 mm bore
100 mm bore
80 mm bore
S&F rubber gasket joint for flanged end pipe & fittings of following size :
150 mm bore
100 mm bore
80 mm bore
S&F in repairs machanical Gypsum joint ISI marked for spigot end pipe of following sizes:-
150 mm bore
100 mm bore
80 mm bore
S&F 80/150mm bore spigot/flanged/ socketed CI fittings. such as bends (any type radius and angle), tapers, tees, collars & tail piece socket/flanged/spigot etc complete all as specified.
Dismantling/taking out unserviceable sluice valve of size 80mm to 300mm bore dia by opening/cutting rusted nuts, bolts etc all as specified and directed.
S&F the following CI sluice valves both ends flanged and drilled, bonnet wedge stuffing box. Gland trust plate, hand wheel made out of grey CI, complete valve confirming to IS 14846/2000 and its fittings suitable for hydraulic test pressure of 15 Kg/sqcm PN 1.0 ISI marked complete all as specified and directed:- Make : Kirloskar/L&T/Upadhyay
80 mm bore
100 mm bore
S&F 150 mm bore CI sluice valves both ends flanged and drilled, bonnet wedge stuffing box. Gland trust plate, hand wheel made out of grey CI, complete valve confirming to IS 14846/2000 and its fittings suitable for hydraulic test pressure of 15 Kg/sqcm PN 1.6 ISI marked complete all as specified and directed Make : Kirloskar/L&T/Upadhyay
Cutting of road /hard standing for laying /dismentling of pipe line and making good surfaces matching with the existing surface after laying of pipe line.up to 30 cm
Taking up or down the following old unserviceable GI Tubing and connections including cleaning for refixing:- Note :- Excavation/earthwork shall be measured & paid separately.
15 mm bore
20 mm bore
25 mm bore
40 mm bore
50 mm bore
Refixing the following old GI Tubing and connections in New or old position (walls, Ceiling, Floors etc) of sizes:-
15 mm bore
20 mm bore
25 mm bore
40 mm bre
Laying only the followiing old serviceable removed GI Tubing from site and connection in New or old position (in trenches) of sizes :-
20 mm bore
25 mm bore
40 mm bore
50 mm bore
S&F the followiing GI tubing medium grade with all fittings and fixed complete laid in trenches of size :-
20 mm bore
25 mm bore
40 mm bore
50 mm bore
S&F the followiing GI tubing medium grade with all fittings complete to walls and ceilings or laid in floors of size :
15 mm bore
20 mm bore
25 mm bore
40 mm bore
Taking down/removing the following Unserviceable Gate valve/stop valve from water supply lines, closing the opening with plug or preparing for new as required necessary fittings complete all as specified.
20 mm bore
25 mm bore
40 mm bore
50 mm bore
S&F the followiing Gun metal Globe or Gate valve with iron wheel head, screwed both ends for iron pipe and fixed with required necessary GI fittings complete :- Make : Kartar/Zolto/Sant/Leader
20 mm bore
25 mm bore
40 mm bore
50 mm bore
Cutting the following existing galvanised iron pipe in position for insertion of new pipe/tees, branches etc.
15 mm bore
20 mm bore
25 mm bore
40 mm bore
50 mm bore
80 mm bore
100 mm bore
Supply and install steel, tubular swaged poles complete with cast iron base plate, finial taper plug nuts and taper plug , bolts, nuts and screws as specified type 410-SP- 31 (9.0 m long) complete all as specified and directed. Note : Excavation, earth work shall be measured and paid separately.
Dismantling/taking down steel tubular/pcc pole of any size including insulater & cross arm& stay wire & refixing at new location directed by engr-in -charge. Note :- Excavation, earth work & PCC shall be measured & paid separately.
Excavation in trenches for laying of cables, poles and stay in any type of soil not exceeding 1.5 mtr wide and n.exc 1.5 mtr deep and getting out complete all as specified and directed.
-Ditto- all as per item No 137 above but depth exc 1.5 mtr but n. exc 3 mtr deep
Preparation for surface of existing steel poles including cross arms, nuts, bolts, for painting LT pole 7.5 mtr long above ground level and applying one coat of approved quality of aluminum paint all as directed by Engr in charge.
M&L for Plain cement concrete (1:4:8) type D-2 using 40 mm graded stone aggregate as in foundation of poles etc complete all as specified.
M&L for Plain cement concrete (1:3:6) type C-2 using 40 mm graded stone aggregate as in foundation filling and mass concrete for stays,foundation and platform for transformer installation complete all as specified.
M&L for Plain cement concrete (1:3:6) type C-1 using 20 mm graded stone aggregate for coping of pole with and including formwork complete all as specified and directed.
S&F in repairs 1100 Volts grade line composite phase separators, moulded & bolted type as per IS 1445 - 1997 suitable for the following :-
Taking down u/s LT U/G cable (including all mounting accessories, bricks and sand etc ) from trenches, wall, floor etc and removing to store for safe custody upto 25 sqmm complete all as specified and directed. Note:- Excavation for taking out cable will not paid for separately, the cable shall be deemed to have taken down from the trenches excaveted for laying of cables.
Taking down u/s U/G cable (including all mounting accessories, bricks & sand etc) from trenches, wall, floor etc and removing to store for safe custody above 35 upto 120 Sqmm complete all as specified and directed. Note:- Excavation for taking out cable shall not be paid separately, the cable shall be deemed to have taken down from the trenches excaveted for laying of cables.
S&F XLPE insulated armoured and PVC sheathed "heavy duty" electric cable with aluminium conductor 1100 volts grade laid in trenches, passing through pipes /ducts including testing complete of following cross sectional area of the following sizes:- Note:- Rate is inclusive of cable gland & cable lugs. The contractor shall be used old cable route indicator retrietive from item No 33 to 35 above. Fixing cost for the same shall be included in the quoted rates of these items. Make : Havells/GLOSTER/Poly Cab/Paragon
2 core, 4 sqmm cross sectional area
2 core, 6 sqmm cross sectional area
2 core, 10 sqmm cross sectional area
4 core, 16 sqmm cross sectional area
3-1/2 core, 25 sqmm cross section area
3-1/2 core, 35 sqmm cross section area
3 -1/2 core, 50 sqmm cross sectional area
3 -1/2 core, 70 sqmm cross sectional area
3 -1/2 core, 95 sqmm cross sectional area
S&F in repairs 40mm bore, GI steel tubing "light grade" for cable protection passing under road /floor or for fixing to poles complete all as specified and as directed Make :- JINDAL/ ZENITH/ TATA/ PRAKASH
S&F in repairs 50mm bore GI steel tubing "light grade" for cable protection passing under road /floor or for fixing to poles complete all as specified and directed Make - JINDAL/ ZENITH/ TATA/ PRAKASH
S&F in repairs 80mm bore GI seel tubing "light grade" for cable protection passing under road /floor or for fixing to poles complete all as specified and directed Make - JINDAL/ ZENITH/ TATA/ PRAKASH
S&F in repairs RCC hume pipe for road crossing of cables class NP-2 of size 100 mm dia complete all as specified.
Cutting of hardstanding/ Road for laying of pipe line/cable and making good surfaces after lying of pipe line/ cable upto 30cm in depth as per existing specification complete all as specified and directed.
M&L for boring of hole under road/hard standing by trenchless technology including S & F HDPE pipe "heavy duty " of size 100mm bore fixed in repairs complete all as specified and directed.
M&L unwashed Sand cushioning to under ground cable provided with a layer of 8 cm deep before laying and 15 cm covering above the top edge of cable after laying complete all as specified. Note : Measurement shall be done after puning down of sand.
M&L Brick covering with width equal to length of bricks as mechanical protection to cable with well burnt sub class `B` old size bricks laid dry and flat complete all as specified and as directed.
Relaying old dismantaled Bricks covering with width equal to length of bricks as mechanical protection to cable complete all as specified and as directed.
Taking down of faulty LT UG cable of size upto 3.5x120 Sqmm from trenches /pole/wall etc for detecting fault including repair and jointing at site including relaying at the same location complete. Note:- Excavation/earth work and cable jointing & jointing kit shall be measured and paid separately under relevent item of schedule.
S&F LT Joint cable, jointing kit straight through joint heat shrinkable type of size 10 Sqmm 4 core to 16 Sqmm 4 core cable size complete all as specified and directed. Make : M Seal/ Denson/Reychem/Cab seal
S&F LT Joint cable, jointing kit straight through joint heat shrinkable type of size 25 sqmm 3.5 core to 50 sqmm 3.5 core cable size complete all as specified and directed. Make : M Seal/ Denson/Reychem/Cab seal
S&F LT Joint cable, jointing kit straight through joint heat shrinkable type of size 70/ 95 sqmm 3.5 core cable size complete all as specified and directed. Make : M Seal/ Denson/Reychem/ Cab seal
Taking down partly unserviceable/unserviceable security/street/gate/flood light fittings from poles/towers/Perimeter Fencing of any type upto 9 m height by manual or mechanical means and for necessary repair and make srviceable as per complaint given by department (E/M service cell) through job card/complaint register on day to day basis all to the satisfaction of Engr in charge & complete all as specified and directed Note :- Ballast, Lamp holder, capacitor, ignitor, covers and lamps of required wattage/type shall be measured and paid separately.
Fixing only repaired serviceable fitting of any size, and any make complete all specified and directed by engr-in-charge
S&F in repairs Lamp holder porcelain suitable for street light fitting Screw type E-40 base Make: Bajaj/Havells/Crompton
S&F in repairs Lamp holder porcelain suitable for street light fitting Screw type E-27 base Make: Bajaj/Havells/Crompton
Taking Down of street light Bracket including clamps of any type/any size from to pole/wall including necessary nut & bolts as directed complete all as specified and directed.
S&F GI pipe bracket made of light Grade tubing of size 40 mm bore, duly bended by hot forgoing length 1.20 mtr including two sets of clamps made of 30mm x 5mm thick Flat iron with GI bolt,nuts & washers complete all as specified and directed
S&F GI pipe bracket made of light Grade tubing of size 32 mm bore, duly bended by hot forgoing length 1.20 mtr including two sets of clamps made of 30mm x 5mm thick Flat iron with GI bolt,nuts & washers complete all as specified and directed
S&F LED street light lumanaries of size 100 W pressure die cast aluminium housing with heat resistance toughed glass & IP66 protection Make: Bajaj/Wipro/ Havells/Crompton
S&F LED street light lumanaries of size 90 W pressure die cast aluminium housing with heat resistance toughed glass & IP66 protection Make: Bajaj/Wipro/ Havells/Crompton
S&F LED street light lumanaries of size 72 W pressure die cast aluminium housing with heat resistance toughed glass & IP66 protection Make : Bajaj/Wipro/ Havells/Crompton
S&F LED street light lumanaries of size 60 W pressure die cast aluminium housing with heat resistance toughed glass & IP66 protection Make: Bajaj/Wipro/ Havells/Crompton
S&F LED street light lumanaries of size 45 W pressure die cast aluminium housing with heat resistance toughed glass & IP66 protection Make: Bajaj/Wipro/ Havells/Crompton
S&F LED street light lumanaries of size 25 W pressure die cast aluminium housing with heat resistance toughed glass & IP66 protection Make: Bajaj/Wipro/ Havells/Crompton
S&F in repairs post of lantern fitting made out of black ABS plastic spigot & spun alluminium funnel shaped with clear acraylic cover suitable for 1x45w LED lamp including fitting complete all as specified. Make : Bajaj/Wipro /Havels/Crompton
S&F in repairs PVC insulated 3 core 2.5sqmm multistranded COPPER conductor for connection of Security light from JN BOX to Security light /OH conductor to security light all complete as specified and directed Make: finolex/plaza/havells/CCI/PARAGON
S&F in repairs PVC insulated 3 core 1.5sqmm multistranded COPPER conductor for connection of Security light from JN BOX to Security light /OH conductor to security light all complete as specified and directed Make: finolex/plaza/havells/CCI/PARAGON
S&F in repairs Astrorex D-22, Multifunctional digital time switches Make : Legrand/L & T/ GIC
S&F in repairs galvanized earth strip 32 mm x 6 mm for earthing from earth plate to equipment complete fixed on pocelain insulator every 1 meter interval complete all as specified and as directed.
Supply and fix ALLUMINIUM earth strip 25 mm x 4 mm for earthing from earth plate to equipment complete fixed on pocelain insulator every 1 meter interval all as specified and as directed.
Supply and fix COPPER earth strip 20 mm x 3 mm for earthing from earth plate to equipment complete fixed on pocelain insulator every 1 meter interval all as specified and as directed.
S&F MCCB 250 A 35 KA, 4 POLE ,thermal magnetic relese, Ics=100% Icu complete all as specified Make : L&T / Schneider/Hager
S&F MCCB 200 A 35 KA,4 POLE ,thermal magnetic relese, Ics=100% Icu complete all as specified Make : L&T / Schneider/Hager
M&L for Preparation for surface of existing PCC poles including cross arms, nuts, bolts, for painting LT pole 7.5 mtr long above ground level and applying one coat of approved quality Exterior grade apex paint all as directed by Engr in charge.
Schedule of Credit amounting to Rs. 2,04,760.50 to be deducted during AOC.
Sachdeva Enterprises
shri krishna traders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .