Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.9 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹16.5 L+₹2.1 L (14.6%)Rejected-Finance | L2 | Rejected-Finance Other than Lowest Bidder |
Tender Value
₹17 L
EMD Value
₹34,000
Closing Date
4 Jan 2023, 6:00 pmClosed
CWE Jalandhar Cantt
HQ CWE Nalwa Road Jalandhar Cantt PIN-144005
Please refer tender documents
2022_MES_561809_2
8322/49/E8
Open Tender
Electrical and Maintenance Works
Item Rate
273 days
Jalandhar Cantt
Class E Category c(i) for contractors enlisted with MES
8 documents required · 8 mandatory
₹500
AGE (I) Suranussi
₹34,000
Yes
7 Feb 2023
14 Dec 2022
12 Jan 2023
14 Dec 2022
4 Jan 2023
22 Dec 2022
Amount
Material & Labour for carrying out the descaling of the shell & Tube condensers by isolation of each condenser by providing of dummy plate for inlet & outlet connection and separation of condenser from water circulation without disturbing the operation of the AC plant, carrying out the descaling by circulation of the diluted scale removing agent organic compound type chemical of RA III / chemtex Brand at the appropriate ratio depend upon the scale deposit inside copper tube by forced circulation and opening the end covers, manually brushing the copper tubes with nylon brushes of various size to remove complete scale, de-greasing with caustic soda solution and flushing out with fresh water, refixing all disconnected pipes lines, end covers with new rubber gasket and opening water line valves and checking of water leakages, apply grease to all M.S. Bolts & Nuts and put the condensers of the following capacities in operational complete all as directed :-
30 TR Capacity installed at 223 ABOD MSSD.
30 TR Capacity installed at 223 ABOD Dry Battery.
15 TR Capacity installed at 23 FAD Plinth 13.
27 TR Capacity installed at 23 FAD Mag No 24 & Mag No 25.
Maintenance, overhauling & servicing the Package Type A C Plants of capacity 11 TR at 23 FAD (27 A) Air cooled type complete including cleaning, greasing of blower motor etc of following Capacities by trained and qualified Mechanics of (OEM) including replacement of unserviceable Spare parts ,leak test by nitrogen gas and charging the refrigerant as required at site & test run for 24 hrs to achieve satisfactory complete all as specified and directed :-
All as per item No 2 above but of capacity 11 TR at 23 FAD (27 B) Water cooled type.
All as per item No 2 above but of capacity 11 TR at 23 FAD (Mag No 1) Water cooled type.
All as per item No 2 above but of capacity 11 TR at 23 FAD (Mag No 2) Air cooled type.
All as per item No 2 above but of capacity 22 TR at 23 FAD (Mag No 3) Air cooled type.
All as per item No 2 above but of capacity 22 TR at 23 FAD (Mag No 4) Air cooled type.
Material & Labour for carrying out the chemical servicing of the Air Handling units & cooling coils by applying the non-aciditic scale removing agent to the fins area of the cooling coil, copper tubes, remove the complete scale deposit across the coil, flushing through and complete blowing out the dirt, cleaning the fan impellers, filter section, fan section and complete cleaning of filters, tightening of all bolts & nuts, renew the rusted bolts & nuts checking the alignment of the drive set and testing & commissioning the Air Handling units of AC Plant complete all as directed by Eng-in-charge :-
60/54 TR Capacity .
30 TR Capacity.
M&L for Dismantling electrical connections , taking down existing cooling tower motor from cooling tower of the following capacity and carrying out the repairs by filling metal on the worn out portion of shaft,machining to the standard size of hub,removing the bend, checking the balancing and S&F new cooling tower hub and fan including fixing,testing and commissioning of various capacity of AC plants,complete all as directed by Eng-in-charge.
60/54 TR Capacity hub with blades.
30 TR Capacity hub with blades.
22 TR Capacity hub with blades.
11 TR Capacity hub with blades.
M&L for disconnecting electical/ mechanical connections and de-coupling Motor from pump/compressor, taking down the defective Induction Motor of any make / model shifted to work shop for dismantling motor , remove burnt out winding from stator and rewinding the stator with same gauge super enamelled copper conductor with necessary insulation materials , varnishing backing re-assembling motor including replacement of both end bearings complete after complete the job motor shifted to site and reinstalled at its original position including allignment with pump/compressor with electrical connections and testing for best performance complete all as directed of the following capacities :-
Motor upto 5 HP.
Motor 7.5 HP to 10 HP.
M&L for vacummising the complete system of various capacity of central type AC plants with vaccum pump as per the standard practice and charging refrigerant R-22 gas including checking of leaks and testing & commissioning of the system complete all as directed.
M&L for vacummising the complete system of various capacity of central type AC plants with vaccum pump as per the standard practice and charging refrigerant HFC R-407 a gas including checking of leaks and testing & commissioning of the system complete all as directed.
Supply and charge of compressor oil servo freeze in Package/ Central type AC plant of any capacity complete all as specified and directed.
Taking down unserviceable single phase preventer and S&F new single phase preventer, 6 wires,230 V complete all as directed.
Material & Labour for taking down the defective unserviceable solenoid valve coil and supply & fixing of new coil suitable to work in single phase, AC 220 V,50 Hz complete all as directed.
Material & Labour for taking down the defective/ unserviceable High Pressure & Low Pressure combination cut out switch and supply & fixing HP & LP combined switch including connecting the circuit wiring, pressure line connections and setting of the cut in & cut out pressure limits and testing complete all as directed.
Material & Labour for taking down the defective/ unserviceable High Pressure cutout switch and supply & fixing of new high pressure cutout switch including connecting up the Electrical & pressure line connections and setting the cutin & Cutout pressure limits and testing the cutout switch for AC plant compressor complete all as directed.
Material & Labour for taking down the defective unserviceable oil Pressure cutout switch and supply & fixing of new oil pressure cut out switch including connecting up the Electrical & Pressure line connection and setting the cutin & cutout pressure limits and testing the cutout switch for AC plant Compressor coplete all as directed.
Material & Labour for taking down the defective unserviceable timer and S&F of new on delay timer HSDT2 CON-230, 0 to 30 Sec connecting the wiring & testing complete all as directed.
Material & Labour for taking down the defective unserviceable power contactor of 3TF46 & burned out copper wire, lugs, and S&F of new power contactor 3 pole, 220-240 coil volt, including the copper wire & copper lugs and testing complete all as directed.
S&F MPD Power supplier of capacity 5-30 Amps auxilary supply,15 V,AC 230V,50Hz,AC supply as fixed in repairs complete all as directed.
S&F Digital Ammeter,3 phase,5 Amps,class 1, AC supply as fixed in repairs complete all as directed.
S&F Digital Voltmeter,3 phase,5 Amps,class 1, AC supply as fixed in repairs complete all as directed.
Taking down old unserviceable 100 mm dia CI butterfly valve and S&F 100 mm dia CI butterfly valve,PN 1.0,pneumatic double acting actuator with both sides flanges and gaskets complete all as specified and directed.
Painting air conditioning plant complete of a capacity 20 to 60 TR chiller water type including preparation of surface by cleaning /rubbing /scrapping as required and painting with two coats of synthetic enamel paint of existing color using spray gun and marking SM MES No etc as directed on the following parts/ equipments:- Compressor and compressor motor -3 Set Condenser /chiller pump /hot water pump -06 Nos LT panel complete -01 No Hot water generator -01 No Cooling tower complete -01 No CT fan motor -01 No Blower fan motor -02 Nos all water /gas pipe line -01 No
Material and labour repair to internal wiring / burnt out wiring of LT panel and supply and rewiring with suitable size single core PVC insulated, unsheathed multi stranded 1100 volts grade copper conductor cable of required sizes from bus bar to outgoing feeders/ starters properly lugged at end terminals , cleaning of panel board , tightening of all connections removing old burnt lugs and including replacement of Voltmeter digital type 0-500 V, Ampmeter 0-500 Amp and indicator lamp complete all as directed..
Supply and fixing in replacement shut off valve brass body of suitable size complete all as specified and directed.
Supply and fix in replacement, angle valve brass body of suitable size complete all as specified and directed.
Supply and fix in replacement, filter for package / Central type chiller unit of capacity 30 TR.
Maintenance ,servicing and testing of Split/window type AC capacity up to 2 tons any make complete all as directed by Engineer-in -charge. Note :- Supply only spares (in replacement) shall be measured and paid for separately under appropriate items of Schedule 'A'. However the unit rates quoted against this item shall include the cost of fixing al type of spares, minor parts such as bolts, nuts, washers etc
Supply and fix in replacement, new compressor for split/ window type AC up to 2 Ton capacity including disconnecting opening up taking out burnt compressor by cutting /opening the pipe connections fixing in position reassembling testing and commissioning including gas & oil charging after flushing the line with CO2 gas to avoid trapping the water vapor ensuring leak proof system complete all as specified and directed.
Finding out leakage with the pressure testing of condenser/cooling unit/compressor of split/ window type AC of 1/1.5/2 Ton cap including dismantling the same for recharging with R-32 gas or as per manufacturer's instruction and stop leakage by brazing /soldering including charging the gas to required level and complete all as specified and directed.
Supply only running capacitor 5 MFD 230 volts for blower motor all as specified and directed.
Supply and fix in replacement, starting capacitor clip type of cap 100-120 MFD 440 suitable for 1.50 Ton capacity window/ split type AC complete all as directed by Engineer -in-charge.
Supply and fix in replacement, starting relay suitable for AC up to 2 ton complete all as specified and directed.
Supply and fix in replacement, over load protection relay suitable for AC of capacity up to 2 ton complete all as specified and directed.
Supply and fix in replacement, blower motor 1/8 HP double shaft, single phase suitable for AC up to 2 ton capacity including testing complete complete all as specified and directed.
Supply and fix in replacement, 4 way reverse valve of make "RENCO" ISI marked in 1.5/ 2 ton AC including replacement of heating and cooling thermostat Make "PECIFIC" and two way heavy duty toggle switch make "GEC/SSK/KAY" with and including recharging the system with gas as required after fixing of four way reverse valve with remote control and sensor plate for heating and cooling system and testing complete all as specified and directed.
Supply and fix in replacement; thermostat switch hot & cold product no 2KSP-5010 all as specified and directed.
Supply and fix in replacement power circuit breaker (PCB) kit for window type AC complete all as specified and directed.
Material and labor for painting to exiting sign boards of approximate size 1.5 m X 1.8 m of the air conditioning installation including 2 Nos legs of 1.2 m height with two coats of synthetic enamel paint of existing color after preparation of old surface for painting and writing work with white paint name of installation and capacity complete all as specified and directed.
Supply and fix in replacement, switch socket combination 2 in 1, 6 pin, 3 & 15 Amp, Flush type complete all as specified
Supply and fix in replacement,sheet metal enclosure SPN enclosure with two pin and earth plug and socket with one single pole MCB 20 Amp complete all as specified
Supply and fix in replacement, 3 pin top plug, 15 Amp press type with and including 1.5 m copper conductor lead of 40/0.0076, 3 core, complete all as specified and directed.
Supply and fix in replacement, of Relative Humidity sensor complete all as specified and directed.
Supply and fix in replacement, of Temperature meter (Digital Type) as specified and directed.
Supply and fix in replacement, V Belt B-80 to 88 type complete all as specified & directed by Engineer-in-charge.
Supply and fix in replacement,V Belt B-72 type complete all as specified & directed by Engineer-in-charge.
Supply and fix in replacement, V Belt B-63 type complete all as specified & directed by Engineer-in-charge.
Supply and fix in replacement, V Belt A-20 to 30type complete all as specified & directed by Engineer-in-charge.
Supply and fix in replacement, gun metal globe or gate valve with iron wheel head screwed both ends for iron pipe, including provn of one union complete all as specified of size 25 mm bore pipe complete all as specified & directed.
Supply and fix in replacement, in repair, gun metal globe or gate valve with iron wheel head screwed both ends for iron pipe, including provn of one union complete all as specified of size 65 mm bore pipe complete all as specified & directed.
Supply and fix in replacement, 25 mm dia Ball valves made of gun metal, without strainer of PN 16 Rating as per engineering standards and specifications.(For Hot water system),complete all as specified and directed.
Supply and fix in replacement, 32/40 mm dia Balancing valves made of Cast iron/Gun metal of PN 16 Rating as per engineering standards and specifications.(For Hot water system), complete all as specified and directed.
Supply and fix in replacement, 50 mm dia Balancing valves made of Cast iron/Gun metal of PN 16 Rating as per engineering standards and specifications.(For Hot water system), complete all as specified and directed.
Supply and fix in replacement, MCB DP 20 A complete all as specified and directed.
Supply and charge gas R-32 in Split type AC of any capacity as directed and making the system leak proof complete all as specified and directed
Taking down old unserviceable 80 mm dia CI butterfly valve and S&F 80 mm dia CI butterfly valve,PN 1.0 pneumatic double acting actuator with both sides flanges and gaskets complete all as specified and directed.
Disconnecting, cutting and taking out unserviceable sealed unit compressor of Central type Air conditioner 12 Ton Capacity any make & model including removal, fitting/fixing of serviceable sealed unit compressor (brought against srl item No 60 here-in-after), soldering, welding, brazing as required including charging of refrigerant gas and oil in the exchanged compressor, making electric & mechanical connections at site and testing on load, complete all as specified and directed.
Supply only with provision of clean, exchange of unserviceable compressor (removed against item No 59 hre-in-before) with company made new one sealed compressor of central type air conditioner 12 Ton capacity, complete all as specified and directed. Note :- After fixing of new compressor testing will be done its own arrangement.
Disconnecting, cutting and taking out unserviceable sealed unit compressor of pckage type Air conditioner 5.5 Ton Capacity any make & model including removal, fitting/fixing of serviceable sealed unit compressor (brought against srl item No 62 here-in-after), soldering, welding, brazing as required including charging of refrigerant gas and oil in the exchanged compressor, making electric & mechanical connections at site and testing on load, complete all as specified and directed.
Supply only with provision of clean, exchange of unserviceable compressor (removed against item No 61 hre-in-before) with company made new one sealed compressor of package type air conditioner 5.5 Ton capacity, complete all as specified and directed. Note :- After fixing of new compressor testing will be done its own arrangement.
M & L for repair of PCB of control panel of chilling unit package / central unit of any capacity / make including checking the components, replacing demaged components with new ones, making the PCB fully functional till Engineer-in-Charge satisfaction complete all as specified and directed.
Supply and fixing of New PCB alongwith all accessories as per existing model / sample suitable for chilling unit of central type AC plant and duly fixed on existing system by any fixing method and making electrical connection including taking down of existing PCB complete and produce test certificate all as specified and directed by Engineer-in-Charge.
AGGARWAL ENGINEERING CO
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .