Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.7 LAccepted-AOC | L1 | Accepted-AOC Accepting being lowest | |
| 2 | L2₹25.1 L+₹11,386 (0.46%)Rejected-Finance | L2 | Rejected-Finance Rejected being other than lowest | |
| 3 | L3₹26.5 L+₹1.5 L (6.11%)Rejected-Finance | L3 | Rejected-Finance Rejected being other than lowest | |
| 4 | L4₹27.6 L+₹2.6 L (10.6%)Rejected-Finance | L4 | Rejected-Finance Rejected being other than lowest | |
| 5 | L5₹29.0 L+₹4.0 L (16.1%)Rejected-Finance | L5 | Rejected-Finance Rejected being other than lowest |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
7 Feb 2023, 6:00 pmClosed
Maj Pramod Kumar Tripathi
Military Engineer Services, Garrison Engineer (South) Ahmednagar - 414002
REPAIRS/REPLACEMENT TO EXTERNAL ELECTRIC SUPPLY, UG CABLES, LT PANELS, STREET LIGHTS, EARTH PITS AND PAINTING OF LT PANELS AT MIL STN BHUSAWAL UNDER GE (S) AHMEDNAGAR
2023_MES_574120_1
8942/E8
Open Tender
Miscellaneous Works
Item Rate
270 days
Bhusawal
Class D Cat b (i)
8 documents required · 8 mandatory
₹500
Garrison Engineer (South) Ahmednagar
₹60,000
Yes
17 Feb 2023
10 Jan 2023
9 Feb 2023
10 Jan 2023
7 Feb 2023
24 Jan 2023
10 Jan 2023 - 17 Jan 2023
Amount
Excavation in trenches n exc 1.50 m wide and n exc 1.50 m deep for foundation, laying of cables, pipe or for shafts, wells cesspits,man holes etc not exc 10 Sqm on plan and n exc 1.5m in depth and getting out in soft / loose soil complete all as specified and as directed.
Returning, filling, in soil including spreading, levelling, watering and well ramming in layers n.exc. 25cm thick complete all as specified and as directed.
Removing excavated soil to distance n exc. 50 m and depositing where directed at a level n exc. 1.5 m above the starting point etc complete all as specified and as directed.
M&L for PCC 1:3:6 , type C1, (using 20 mm graded stone aggregates) as in coping of pole including necessary form work, weathering, slightly rounded or chamfered angles & throating including demolition of existing damaged coping of poles complete all as specified and as directed.
S&F XLPE insulated, LT armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 120 sq mm, 3.5 core complete including taking out existing unserviceable cable along with brick protection all as specified and as directed.
All as per serial item No 5 but cross sectional area 70 sq mm, 3.5 core.
All as per serial item No 5 but cross sectional area 50 sq mm, 3.5 core.
All as per serial item No 5 but cross sectional area 35 sq mm, 3.5 core.
All as per serial item No 5 but cross sectional area 16 sq mm, 4 core.
All as per serial item No 5 but cross sectional area 6 sq mm, 2 core.
S&F XLPE insulated, LT armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 25 sq mm, 3.5 core complete for conversion of overhead line to under ground cable all as specified and as directed.
All as per serial item No 11 but cross sectional area 10 sq mm, 4 core.
All as per serial item No 11 but cross sectional area 6 sq mm, 4 core.
M&L for dry river sand in trenches for cushioning of underground cable including spreading, levelling, hand punning complete all as specified and as directed. Note:Punned thickness only will be measured and paid.
Laying only bricks obtained from taking down under item Nos 5 to 10 here-in-before, laid dry in trenches for protection of underground cable, laid flat with length for brick perpendicular to length of cable complete all as specified and as directed.
Supply and laying well burnt, old size, sub class ‘B’ bricks locally available best quality, laid dry in trenches for protection of underground cable, laid flat with length for brick perpendicular to length of cable complete all as specified and as directed.
S&F in repairs, 40 mm bore dia GI pipe, light grade, laid in trenches / fixed to Pole / wall for cable protection complete all as specified and as directed.
S&F in repairs, 50 mm bore dia GI pipe, light grade, laid in trenches / fixed to Pole / wall for cable protection complete all as specified and as directed.
S&F in repairs, HT cable route indicator, made out of 45 mm x 45 mm x 6 mm size mild steel angle of length 60 cm and bolted with round CI plate of suitable size indicating HT cable 11000 V complete all as specified and as directed. Make : Goyal Electric or equivalent make as approved by GE.
S&F in repairs, LED flood light fitting, 120 watt, 230V AC outdoor type with thermal management in multiple optics and equipped with IP65/66 protection with impact and corrosion resistant complete with driver and lamp complete all as specified and as directed.
S&F in repairs, LED flood light fitting, 70 watt, 230V AC outdoor type with thermal management in multiple optics and equipped with IP65/66 protection with impact and corrosion resistant complete with driver and lamp complete all as specified and as directed.
S&F in repairs, LED Flood Light 50 watt luminaire (Amaze LED) with secondary optics made in pressure die-cast housing with heat sink & aluminum extrusion with IP 66 including necessary wire connection complete all as specified and as directed.
S&F in repairs, LED street light fitting, 70 Watt, 230 Volt, AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp, braket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection all as specified and as directed. Make : Bajaj cat No BRTFG 70/72W LED or equivalent model in Cromption/ Phillips/ Havells/ Wipro/ Luker/ SURYA Roshni/ Halonix/ SYSKA
S&F in repairs, LED street light fitting, 60 Watt, 230 Volt, AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp, braket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection all as specified and as directed. Make : Bajaj cat No BRTFG 60W LED or equivalent model in Cromption/ Phillips/ Havells/ Wipro/ Luker/ SURYA Roshni/ Halonix/ SYSKA
S&F in repairs, LED post top dome light with LED, 20 watt, 230 Volt AC outdoor with decorative post top 360 degree indirect light, IP 65 protection with impact and corrosion resistant complete all as specified and as directed.
S&F in repairs, garden dome light 8" in spherical shape white light with base fittings including 10 Watt LED bulb complete all as specified and as directed.
S&F in repair, PVC insulated flexible industrial cables 2 core, 4 Sqmm aluminum cable, 1100 Volts conforming to IS:694 for connection from Junction box of pole to street light connection and cable to be protect with suitable size of PVC conduit complete all as specified and directed.
S&F in repairs, LED driver, 45 watt complete all as specified and as directed. Make : Bajaj, Cat No BGD 70 065 5Y or equivalent make as per list of makes specified in PS.
S&F in repairs, LED driver, 72-80 watt complete all as specified and as directed. Make : Bajaj, Cat No BGD 36 220 5Y or equivalent make as per list of makes specified in PS.
M&L for filtration of transformer oil with the help of filtration machine including draining out low viscocity carbonised transformer oil so as to achive 40 KV dielectric strength and testing of the same before and after filtration, submitting of test results for any type any capacity of transformer upto 400 KVA transformer complete all as specified and as directed.
Supply and top up transformer oil conforming to IS superior qualiy low viscocity having dielectric strength not less than 55 KV upto required level complete all as specified and as directed.
Disconnect primary, secondary cable, earth connection of 11000 volt of capacity 200 KVA transformer, opening the top and including repacement of top cover gasket-02 Nos, HT porcelain bushing with stud (suitable dia and length) with MS nut and bolts, and washers including replacement of rubber seal, oil level indicator, pressure gauge and cleaning of the conservator & explosion vent complete all as specified and as directed.
S&F in repairs, LT bushing with stud and corksheet washer upto 200KVA transformer and provide silica gel complete all as specified and as directed.
M&L in repairs/replacement earthing complete with galvanized steel earth plate electrode 60 cm X 60 cm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below ground level, connecting to the GI strip 32mm x 6mm by means of nut bolts, check nuts and washer upto and including test point made out of 40mm x 6mm aluminium flat including provision of concrete pit in PCC (1:2:4) type B-1 using 20 mm graded stone aggregates with 40 mm thick RCC (1:2:4) cover with reinforced with XPM (weight not less than 4 Kg / Sqm) and frame of angle iron 25mm X 25 mm X 3mm with lugs 2 Nos and with 6 mm dia MS bar handle made to shape, GI medium grade 40 mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, test point made out of phosphorus bronze with fixing arrangement, funnel, wire mesh and earth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exceeding than 50 mtr, all as per electric plate No 3 of SSR Part I 2009 and connection to earth test point made out of 40mm x 6mm aluminium flat all as specified including testing on completion.
S&F in repairs, earth continuity galvanised iron strip 32mm x 6mm fixed to pole or walls or both or burried in ground or drawn through pipe etc. as required for earthing complete all as specified and as directed
M&L for repair of existing earthing pit chamber as under : (a) Repair to damaged plaster in cement mortar 1:6, 10mm thick to match with existing. (b) Provision of RCC (1:2:4, type B1 using 20mm graded stone aggregates) cover with reinforced with XPM (weight not less than 4 Kg / Sqm) with lugs 2 Nos and with 6 mm dia MS bar handle made to shape (c) Provision of funnel and wire mesh.
S&F lighting arrestor, expulsion type complete with all fitting, transmission class, discharge capacity 65 Kilo Amps current rating 5 KA suitable for 11000 Volts complete including taking down of existing lightening arrestor complete all as specified and as directed.
S&F in repairs, drop out fuse unit suitable for 11000 volt, mounted on MS channel complete with post insulator fuse barrel (fibre glass tube) etc for 3 phase complete all as specified and as directed
S&F in repairs, air break gang operated triple pole switch for current rating upto 200 amps, 11KV, mechanically operated mounted on insulator and steel frame out door type suitable for vertical installation single brake provided with locking arrangement, consisting of MS channel , HT post type insulator connected with cupper rod/frame complete including taking down of existing unsv air break switch complete all as specified and as directed.
S&F in repairs, cable jointing kit for 11 KV, outdoor termination, heat shrinkable of size 50-95 sqmm 3 core cable size suitable for XLPE armoured aluminium cable complete all as specified and directed.
S&F in repairs, cable jointing kit for 11 KV indoor termination heat shrinkable of size 50-95 sqmm 3 core cable size suitable for XLPE armoured alu cable complete all as specified and directed.
S&F in repairs, Pin type, porcelain, vitreous, white, brown or green insulator ,150 mm height, 150 mm dia for 11000 volts grade including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut complete all as specified and directed.
M&L for preparation of old painted steel or iron surfaces of any description over 10cm in width or girth and apply two coats of aluminium paint on electric poles and LT panels complete all as specified and as directed.
S&F in repairs, MD-XL Double metalized paper ( Extra low loss) capacitor bank for 3 phase 440 volts and 50 Hz system for permissible non leaner load 20 % of capacity 25 KVAr complete all as specified and as directed. Make : L&T/Havells/C&S/Cromption/Schneider
S&F in repairs, fully automatic star delta motor starter with enclosure type ML-4 FASD, 415 volt, 3 phase, relay range 45-75 A (Size ML2F) suitable for 75 HP motor, complete all as specified and as directed.
S&F in repairs, overload protection relay suitable for ML-4 FASD starter , MN-5, relay range 45-75, direct mounting on MNX 45-80 and currenct cap 160 A Max complete all as specified and as directed.
S&F in repairs, 3 pole power contactors ML-4, IS/IEC-60947-4-1 and IEC-60947-4-1 type, 100A AC-1 and 70A-AC-3 type, 415V, 50 HZ complete all as specified and as directed.
S&F in repairs, 3 pole power contactors block ML-3, 40A, AC3, 415V, 50 HZ and 45Amps-AC-1 type and IS/IEC-60947-4-1 complete all as specified and as directed.
S&F in repairs, MCCB, 415 Volts, 36 KA breaking capacity, 4 pole, 200 Amps complete with fixed thermal magnetic setting all as specified and as directed.
S&F in repairs, MCCB, 415 Volts, 36 KA breaking capacity, 4 pole, 250 Amps complete with fixed thermal magnetic setting all as specified and as directed.
S&F in repairs, MCCB, 415 Volts, 36 KA breaking capacity, 4 pole, 160 Amps complete with fixed thermal magnetic setting all as specified and as directed.
S&F in repairs, MCCB, 415 Volts, 36 KA breaking capacity, 4 pole, 400 Amps complete with fixed thermal magnetic setting all as specified and as directed.
S&F in repairs, solar sensor timer, 240V for street light/high mast light (as per sample) complete all as specified and directed.
S&F in repairs, wall/pole mounting junction boxes (DB) factory made out of MS heavy duty with min dimension 250mm x 200mmx2mm with cable glands comprising of MCB, SPN 20 Amps, 240 volts, mounted on din rails with and including fixing clamps made out of MS flat iron 40 x 3mm thick with nut bolts and terminal block suitable for LT UG cables complete all as specified and directed.
S&F in repairs, 63A main switch unit, 4 pole, 415V with MS sheet enclosure complete all as specified and as directed.
S&F in repairs, aluminium strip 25 x 3 mm with size , alongwith the AC sheet roof and fixing to wall etc complete with suitable aluminium saddles and fixing with screws complete all as specified and as directed.
S&F in repairs, single pointed air termination copper rod 12 mm dia, 300 mm long duly supported and fixed with GI light grade 25 mm dia pipe 0.30 m long with suitable clamp, nut , bolt etc complete all as specified and as directed.
S&F in repairs, terminal box made of phosporous bronze of size 75mm x 75mm x 25 mm complete dirlled,screwed,including 3 nos. 8 mm dia 25 mm long hex. head screw complete all as specified and as directed.
Dismantling of unserviceable ACSR conductor, any size including copper / aluminium binding wire to overhead conductor complete all as specified and as directed.
Dismantling earth wire/GI guarding with cradle complete all as specified and as directed.
Dismantling unserviceable existing cross arms of MS channel or angle sections etc from LT poles complete and setting aside for re-use within 50m distance complete all as specified and directed.
Dismantling insulators, any type and any size from LT poles complete all as specified and as directed.
M&L for installing, testing and commissioning feeder pillar box factory made of suitable size weather/verming proof outdoor type from CPRI type approved panel Board of size 75cm x 60cm x 45cm made out of 3mm thick CRCA sheet, duly powder coated with inner shutter & outer double door with locking arrangement both side openable installing with 40mm x 40mm x 5mm size MS angle iron frame, fixed on 45cm high from ground level & 30cm below the ground grounted in & including PCC 1:3:6 type C1 (using 20mm graded stone aggregates) including necessay outgoing cable connections, cable glands, thimbles & cable termination connector strip of required and consisting the following accessories including dismantling existing feeder pillar box complete all as specified and as directed. Incoming : a) MCCB 160 Amps, 4 pole 415 volt, breaking capacity 36 KA -01 No Outgoing : b) MCCB 100 Amps 4 poles 415 Volt -02 Nos breaking cap 36 KA with copper busbar capacity 150 rated (RYB and neutral colour coding) all as spd and directed. (c) RYB indicator (d) Coy made Name plate (Location : LT feeder to be fixed at pole near P2, Pole near Foot ball ground, Amn dump near High mast , near Guard room & BSO yard pole)
Bhirud Electric Stores
M/s. Gurudatt Electricals And Engineers, Aurangabad
CHAUDHARY AND ASSOCIATES
JANARDHANANDSONS
KESARI AND SONS
stage.html
html • 0.06 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .