Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
23 Sept 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (North)
GE (North) Meerut Cantt PIN 250001
MAINT AND REPAIRS TO EXTERNAL ELECTRIC SUPPLY AND CONNECTED WORKS AT EBS BABUGARH UNDER AGE EM I OF GE NORTH MEERUT CANTT
2021_MES_470812_1
8287/E8
Open Tender
Civil Works
Item Rate
180 days
Meerut
Class D
Category b ii
13 documents required · 13 mandatory
₹500
GE (North)
₹60,000
Yes
16 Oct 2021
26 Aug 2021
25 Sept 2021
26 Aug 2021
23 Sept 2021
9 Sept 2021
60 days
Amount
Testing and calibration of HT OCB / VCB 11 KV complete with primary and secondary test as required including checking of wiring of all electrical measuring instrument and resetting of relay and proper alignment mechanical system for smooth functioning and tripping at any type of fault developed in feeders complete all as specified and directed by Engr in Charge. Note :- Contractor will submit primary and secondary test record at the time of calibration of HT OCB , VCB, TR control panel duly signed by the technical rep of manufacturer/authorised dealer to Engineer In Charge. The rate quoted by tender shall deemed to include the cost of this provision incl T&P required for injecting regulated high current.
Disconnecting of HT supply from 11 KV VCB of any make/type/capacity for repair works, servicing and taking out trolley with complete decarburizing the contact points, cleaning with CRC solution and inner body clean with vaccum cleaner etc and repair/replacement of defective parts found during servicing. Reassembling and testing of relays for tripping time setting over current setting, earth fault setting etc including checking of vaccume intrupter, tripping mechanism etc after servicing complete all as directed by Engineer-in-Charge. Note for srl item 2 :- (i) Spare parts will be measured and paid for separatily under respective item and if copper wire and ferule required for wiring include in this items. (ii) For testing and calibration of relays will be measured and paid separately under respective items. (iii) The calibration and servicing shall be carried out by only qualified and experienced person and prior approval shall be obtained from GE.
S&F Male & female contact set, heavy duty for HT VCB fixed in repairs as per existing sample complete all as specified and directed
S&F VCB spring charging motor 24/220 Volt DC/AC for 11KV VCB, of existing make, type, size, capacity with driving gear suitable in repairs complete all as specified and directed
S&F open/closed auxiliary contacts suitable for upto 630 Amps HT VCB fixed in repairs. As per existing sample complete all as specified and directed
S&F Plug-Socket connectors of electrical accessories suitable for upto 630 Amps HT VCB fixed in repairs. As per existing sample. complete all as specified and directed
S&F door locking handle suitable for upto 630 Amps HT VCB fixed in repairs. As per existing sample. complete all as specified and directed
S&F trolly allingement lever suitable for upto 630 Amps HT VCB fixed in repairs. As per existing sample. complete all as specified and directed
S&F under voltage release suitable for upto 630 Amps HT VCB fixed in repairs. As per existing sample. complete all as specified and directed
S&F over voltage release suitable for upto 630 Amps HT VCB fixed in repairs. As per existing sample. complete all as specified and directed
S&F under/over frequency release suitable for upto 630 Amps HT VCB fixed in repairs. As per existing sample. complete all as specified and directed
S&F Shunt trip closing coil assembly 110/220 volts, DC/AC suitable for upto 630 Amps, HT VCB complete incl taking out old assembly of any type and make all as specified and directed by Engr-in-Charge. complete all as specified and directed
S&F Shunt trip tripping coil assembly 110/220 volts, DC/AC suitable for upto 630 Amps, HT VCB complete incl taking out old assembly of any type and make all as specified and directed by Engr-in-Charge. complete all as specified and directed
Supply & Fix spring charging Motor Cut of switch as per existing sample suitable for 11 KV VCB complete all as specified and directed
Supply & Fix Ratchet wheel Assembly (small, large & middle gear assy) as per existing sample suitable for 11 KV VCB complete all as specified and directed
Supply & Fix manual spring charging gear assembly complete as per existing sample suitable for 11 KV VCB complete all as specified and directed
S & F HRC fuse (link type) having capacity 2 to 6 amp, 415 V, 80 KA complete all as specified and directed
S & F HRC fuse (link type) having capacity 10 to 32 amp, 415 V, 80 KA complete all as specified and directed
S & F 11 KV, VCB, PT fuse 3.15 Amp complete all as specified and directed
S & F stud type terminals of 24V/110V DC suitable for 11KV VCB complete all as specified and directed
S & F Antipumping Contactor 4NO+4NC, 24V/110V DC, 6 Amp complete all as specified and directed
S & F Auxilary contactor for contact multiplication 4NO+4NC, 24V/110V, DC, 6 Amp complete all as specified and directed
S&F Master relay operating voltage 24V/110V DC or as per sample complete all as specified and directed
Vaccume interrupter bottle for vaccum circuit breaker of 630 Amps in HT panel 11000 volts grade incl taking out old interruter complete all as specified and directed
S&F Fixed contact for VCB, 11KV, suitable for 630Amp capacity fixed in repairs complete all as specified and directed
S&F moving contact for VCB, 11KV, suitable for 630Amp capacity fixed in repairs complete all as specified and directed
S&F Spring for trip lever fixed in repair complete all as specified and directed
Spout insulator incl hardware suitable for 11KV VCB, 630Amp capacity fixed in repairs complete all as specified and directed
S&F Spur gear off sizes as per sample suitable for upward or downward trolly movement mechanism with lock and bushing as required for 11KV VCB/OCB/bus coupler fixed in repairs complete all as specified and directed
Trip shackle lever suitable for existing electric system control complete all as specified and directed
Supply & Fix Ratchet Pin suitable for HT VCB (As per sample) complete all as specified and directed
Supply & Fix insulated dust proof cover frame suitable for HT VCB (As per sample) complete all as specified and directed
Supply & Fix Push Rod suitable for HT VCB (As per sample) complete all as specified and directed
Supply & Fix Electronic time delay device suitable for HT VCB (As per sample) complete all as specified and directed
Supply & Fix under voltage release mechanical override suitable for HT VCB (As per sample) complete all as specified and directed
Supply & Fix opening solenoid (MO3) device suitable for HT VCB (As per sample) complete all as specified and directed
Supply & Fix Rack in out mechanical rod with handle suitable for HT VCB (As per sample) complete all as specified and directed
Supply & Fix Trip Prop block Assy suitable for HT VCB (As per sample) complete all as specified and directed
Supply & Fix Drive Link Assy suitable for HT VCB (As per sample) complete all as specified and directed
S&F Rasin cast post type insulator suitable for 11KV VCB busbar pannel (As per sample) complete with stud bolt, nut bolt, washer etc complete all as specified and directed by Engr-in-Charge
S&F Current Transformer 11KV, single phase indoor resin cast, ratio 630/400/5,-5A class 1.0-5P 10 burden 15VA insulation level 28KV/75KV as per IS-2705 to suit VCB/OCB make complete incl taking out old CT complete all as specified and directed Engr-in-Charge.
S&F differential relay CT 11KV single phase out door oil cooled CT of ratio 630/400/5 -5 amps class 1.0 - 5P 10 burden 15 VA insulation level 70KV/170 KV as per IS : 2705 including check wiring from CT to Defferential relay complete all as specified and directed
S&F Indicator lamp of different colour (110 volt) LED type complete with holder to read RYB with necessary wiring complete incl taking out old indicator lamp complete all as specified and directed by EIC.
S&F Indicator lamp of different colour (24 volt) LED type complete with holder to read RYB with necessary wiring complete incl taking out old indicator lamp complete all as specified and directed by EIC.
Supply and fix Power Pack for 11 KV VCB suitable for incoming supply 220/110 volts AC/DC supply and output 110 volts DC supply all as per existing with wiring all connected VCB complete all as specified and directed by Engr-in-Charge. Note for item No 45 : Battery backup of Power Pack shall be not less than 45 minute.
M&L Wiring (shall be done by qualified & experience person of battery charger) to all connected 11KV VCB with 2.5 sqmm multi strand fluxible copper conducters and shall be properly bunched, tied, ferruled for proper indication and crimped with adequate size/types of lugs after wiring testing complete all as specified and directed
S&F PVC insulated and PVC sheathed cable galvanised steel stip or wire armoured electric control cables (Heavy duty) with stranded copper conductor of size 1.5 Sqmm 12 core 1100 volt grade incl taking out old cable of any size and type complete all as specified and directed
All as per item No 47 here-in-before but 1.5 Sqmm 8 core 1100 volts grade
All as per item No 47 here-in-before but 2.5 Sqmm 4 core 1100 volts grade
S&F Multi functional meter, digital type for HT panel 11KV complete with necessary copper wiring with proper thimbles to read amp, volt, power factor and frequency complete incl taking out old multifunctional meter of any type and make all as specified directed by Engr-in-Charge. Make:- AE/Havells/CG/ABB system & control. Note:- Rate quoted by tenderer shall be deemed to include the cost of modification if required for installation of multi functional meter in the equipment Complete all as specified and directed.
Supply & Fix VCB moveable service trolley to load and unload of VCB trolley during servicing/ general maintenance time period. The trolley suitable for 630/630 amp capacity for smooth and safe operation maintaning with the help above capacity VCB trolley complete all as specified and directed by Engr-in-Charge.
S&F heat shrinkable straight through cable joint for XLPE (earthed) 11KV volt grade of size 120 to 185 Sqmm 3 core aluminium conductor cable out door ype incl jointing kit complete incl taking out old jointing kit of any make and type complete all as specified and directed
All as per item No 52 here-in-before but for 70 Sqmm to 95 Sqmm cable Complete all as specified and directed.
All as per item No 52 here-in-before but end termination joint indoor type for 120 Sqmm to 185 Sqmm cable Complete all as specified and directed.
All as per item No 52 here-in-before but end termination joint indoor type for 240 Sqmm to 400 Sqmm cable Complete all as specified and directed.
All as per item No 52 here-in-before but end termination joint outdoor type for 120 Sqmm to 185 Sqmm cable Complete all as specified and directed.
All as per item No 52 here-in-before but end termination joint outdoor type for 70 Sqmm to 95 Sqmm cable Complete all as specified and directed.
Repair/replacement old unserviceable aluminium cable lugs of the following size in various location (VCB/OCB). (a) 240 to 400 Sqmm aluminium cable lugs Complete all as specified and directed.
All as per item No 58 here-in-before but 120 Sqmm aluminium cable lugs Complete all as specified and directed.
All as per item No 58 here-in-before but 70 to 95 Sqmm aluminium cable lugs Complete all as specified and directed.
All as per item No 58 here-in-before but 16 to 50 Sqmm aluminium cable lugs Complete all as specified and directed.
M&L Bus bar made at Copper strip (50mmX6mm is required size and shape, making holes in bus bar as required for fixing bus bar in VCB fixed in repairs complete all as specified and directed
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for laying of Cable or Pipe, electric pole, stay assembly etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft/ losse soil complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm. in soft/ losse soil complete all as specified and as directed.
Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point in soft/ losse soil complete all as specified and as directed.
Supply and spreading clean fine dry river sand in trenches for cushioning of under ground cable/ cable duct or inside the premises of transformer yard complete all as specified and as directed. Note: Only punned thickness shall be measured for payment purpose.
M&L for laying burnt clay fly ash old size bricks, straight or curved on plan, laid flat with width equal to length of brick, laid dry over under ground cable for protection complete all as specified and as directed.
Supplying laying and testing XLPE insulated ,armoured , electric cable (heavy duty) 1100 volt grade with staranded aluminium conductor, laid in trenches / ducts or fixed to walls / poles or passed through pipess complete all as specified of following sizes :- (a) 120 Sqmm,3.5 core cable
All as per Srl item No 68 here-in-before but 95 Sqmm, 3.5 core cable.
All as per Srl item No 68 here-in-before but 70 Sqmm, 3.5 core cable
All as per Srl item No 68 here-in-before but 50 Sqmm, 3.5 core cable
All as per Srl item No 68 here-in-before but 35 Sqmm, 3.5 core cable
All as per Srl item No 68 here-in-before but 25 Sqmm, 3.5 core cable
All as per Srl item No 68 here-in-before but 16 Sqmm, 4 core cable
All as per Srl item No 68 here-in-before but 10 Sqmm, 4 core cable
All as per Srl item No 68 here-in-before but 10 Sqmm, 2 core cable
All as per Srl item No 68 here-in-before but 6 Sqmm, 2 core cable
M&L for Galvanized steel tubing, light grade, with all fittings for protection of cable including taking down old, rusted & corroded unsv Galvanized steel tubing Makes: TATA / Jindal / Prakash. complete all as specified and as directed of the following sizes:- (a) 100mm bore.
All as per Srl item No 78 here-in-before but (b) 80mm bore
All as per Srl item No 78 here-in-before but (c) 50mm bore
All as per Srl item No 78 here-in-before but (d) 40 mm bore
M & L for cutting hard standing/ Road cutting for taking up or laying of LT UG cable upto a depth of 15 cm and after laying of cable, well ramming to the excavated soil and repair the cutting/ exvcavated portion of road as existing or by providing suitable mixture of PCC complete all as specified and as directed. Note: Excavation below the depth of 15 cm shall be measured and paid seperately under relevant items.
M&L for providing PCC 1:4:8, type D-2, using 40 mm graded stone aggregate as in foundation for erection of poles complete inclding breaking and removing the old concrete complete all as specified and as directed.
M&L for providing PCC 1:3:6, type C-2, using 40 mm graded stone aggregate as in foundation for stay assembly complete inclding breaking and removing the old concrete complete all as specified and as directed.
M&L for providing PCC 1:2:4, type B-1 using 20 mm graded stone aggregate as in coping to pole etc., including breaking and removing the old concrete and providing necessary form work complete all as specified and as directed.
M&L for lightning arresters expulsion type complete with all fittings, transmission class, max discharge capacity 65 kA suitable for 11000V grade including taking down existing unsv damaged lightening arrestor complete all as specified and as directed.
Dismantling unsv air break gang operated switches vertical/ horizontal mounted including insulators and operating mechanism complete all as specified and as directed.
M&L for switch air break, gang operated, triple pole, mechanically operated, vertical/ Horizontal out door type, mounted on insulators and steel frame with operating mechanism worked from ground level for current rating upto 200 Amps suitable for 11000 volts grade complete all as specified and as directed.
Dismantling air break gang operated switches vertical/ horizontal mounted including insulators and operating mechanism for maintenance & Servicing of gang operated switch from two/ four pole structure at elevated height and Replacing worn out unsv components, suitable size of nut, bolt & wahers including any minor spares required for maintenance and re-fixing after maintenance complete all as specified and as directed. Note: Component like Knife, male & female contact and copper jumper shall be measured and paid in relevant items.
M&L for brass Male moving Contact blade suitable for 11 kv Air break switch, Gang operated device complete all as specified and as directed.
M&L for brass female contact/ fixed contact jaw suitable for 11 kv Air break switch, Gang operated device complete all as specified and as directed.
M&L for tinned copper flexible jumpers suitable for 200 Amps rating 11 kv Air break switch, Gang operated device complete all as specified and as directed.
M&L for clamp including connecting accessories suitable for 200 Amps rating 11 kv Air break switch, Gang operated device complete all as specified and as directed.
M&L for 11000V grade, expulsion type fuses, single pole, mounted on insulators and steel frame of current rating 50 Amps including taking down old uunsv expulsion fuse unit complete all as specified and as directed.
Surface excavation not exceeding 30 cm deep and averaging 20 cm deep and getting out in soft/ loose soil, removing of bushes, roots etc., in the transformer/ sub station yard and surrounding of two or four pole structres, treating the excavated area with anti vegetation growth chemicals, complete all as specified and directed.
M&L for loose filling with aggregates of gauge 40 to 80 mm of broken stone or boulders, deposited, spread and levelled in layers not exceeding 20 cm thick, watered and rammed to a true surface of transformer/ sub station yard and two pole / four pole structure complete all as specified and as directed.
Isolating the transformer/ voltage stabilizer by carefully dismantling the HT / LT and earth connections, draining out the oil from transformer to the required level and storing in cleaned container, opening the top cover of transformer/ voltage stabilizer and conservator tank from transformer, rectifying the defects and dismantling & replacing burnt out LT/ HT bushes, making all HT / LT connections as per the original, re-filling the transformer oil to the required level, replacing required oil seals & top cover gasket including replacing rusted unsv nut, bolt & washers and testing on completion and refixing the same for capacity upto 250 KVA complete all as specified and as directed. NOTE: (i) LT/ HT bush, transformer oil for topping up and gasket will be measured and paid seperately as supply only itmes under relevant items of schedule.
Disconnecting the HT/ LT connection, taking out the transformer/ voltage stabilizer from its plinth at any situation with the help of suitable crane and transporting the transformer/ voltage stabilizer to workshop for carrying out necessary repairs and bringing back and re-install in its original place of capacity upto 250 KVA complete all as specified and as directed.
Taking out complete core from transformers/ Voltage stabilizer of capacity upto 250 KVA cutting and removing burnt out copper/ aluminium winding and re-winding the same with super enamelled copper conductor of existing gauge together with insulating materials, applying varnish, drying in heating chamber, re-assembling the transformer as per the original and testing on completion complete all as specified and directed. Note:- Shifting of transformers/ Voltage stablizer from installed position to Civil workshop and back will be measured and paid seperately under relevant items.
Filteration of transformer oil at site of 11KV / 433V, indoor /outdoor transformer/ voltage stabilizer of any capacity installed at various locations, with mobile type filtration plant to acheive minimum di-electric strength of 40 KV for 1 minute at 4 mm gap as per relevant I.S. and Topping up of transformer oil into the body / conservator tank of transformer/ voltage stabilizer upto required level, including testing and recording the values of di-electric strength of oil before and after filtration at site with transformer oil testing machine complete all as specified and as directed. NOTE: Transformer oil will be measured and paid seperately as ''supply only'' items under relevant items of schedule.
Supply only transformer oil for topping up in transformers/ Voltage stabilizer complete all as specified and as directed. Make:Poweroil/Transol GET.
Supply only bush of capacity 100 KVA Transformer suitable for 11000V.complete all as specified and directed
Supply only bush of capacity above 250 KVA suitable for 11000V. complete all as specified and directed
Supply only silica gel complete all as specified and directed
M&L for silica gel breather, suitable for transformer including sufficient quantity of silica gel complete all as specified and as directed for the following capacities of transformer:- (a) Transformer of capacity 100 KVA.
All as per Srl item No 105 here-in-before but Transformer of capacity 250 KVA.
M&L for preparation of old painted surfaces of HT 11 KV four pole structure and painting with two coats of aluminium paint over a coat of red oxide primer on all steel surfaces such as poles, channels, angles and clamps of any description and providing 04 Nos bands/ straps with synthetic enamel paint (black and white 30 cm wide each) from top of plinth block complete all as specified and directed.
All as per item No 107 here-in-before but of two pole structure.
Dismantling damaged steel tubalar poles/ struts of any size complete all as specified and as directed.
M&L for erection of steel tubular, swaged poles complete with cast iron base plate of size 300 x 300 mm finial taper plug, cap, bolts, nuts, washer and screws as specified confirming to IS type 410 SP-31 (9 M long), providing through hole of 14 mm diameter at a height of 300 mm above the planting depth for earthing arrangements, inclusive of coated with two coats of black bituminous paint throughout internally and externally up to the planting depth and the remaining portion of the exterior shall be painted with two coats of silver aluminium paint over one coat of red oxide primer complete all as specified and as directed. (Note : Excavation, earth work, PCC foundation, coping shall be measured and paid sepearately under relevnt items).
M&L for erection of steel tubular, swaged poles complete with cast iron base plate of size 300 x 300 mm finial taper plug, cap, bolts, nuts, washer and screws as specified confirming to IS type 410 SP-55 (11 M long), providing through hole of 14 mm diameter at a height of 300 mm above the planting depth for earthing arrangements, inclusive of coated with two coats of black bituminous paint throughout internally and externally up to the planting depth and the remaining portion of the exterior shall be painted with two coats of silver aluminium paint over one coat of red oxide primer complete all as specified and as directed. (Note : Excavation, earth work, PCC foundation, coping shall be measured and paid sepearately under relevnt items).
Dismantling unsv old, rusted & corroded cross-arms of M.S. channel or angle sections etc. of size size complete all as specifeid and as directed.
M&L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts in any shapes or size including painted with two coats of silver aluminium paint over one coat of red oxide primer complete all as specified and as directed.
Releasing the binding of ACSR conductor of LT/ HT OH lines comprsing 3 Phase 3/ 4 wire or single phase 2 wire inclduing street light conductor & earth wire of line from insulator, removing the jumper, connector, service wire, disconneting the connection of UG cables and restreching & stringing of existing LT/HT OH lines, any size, length and span upto desired sag and rebinding the ACSR conductor on insulator, reconnecting the UG cable etc with and including suitable binding/ jumper material with aluminium wire and trimming the tree barnches upto 1.5m distance around conductor to make the line functional complete all as specified and as directed. Note: (a) Jumper/ binding material shall be deemed incldued in the rate quoted by contractor. (b) Trimming of tree branches shall be measured and paid seperatly under relevant items. (c) Lenear length from centre to centre of the poles shall only be measured for the purpose of payment.
Material & Labour for attending break down/ emergent repair immediately on intimation and rectify the External electric supply complaint on LT/HT overhead lines/ under ground cable alongwith necessary T&P, safety devices etc. as per site requirement complete all as specifeid and as directed for the following:- (a) M&L for refreshing the jointing of wornout jumper of LT/ HT OH line by suitable jumper/ binding materials complete all as specified.
(b) Disconneting worn out under ground cable from over head conductor, cutting down worn out portion of under ground cable of any type and size for repairs and taking out under ground cable loop from ground by excavating and all neccessary earth work and making fresh connection for restoration of electric supply complete all as specified. Note: Excavation, earth work, taking out cable protection covers, & sand cushion and relaying the same shall be deemed incldued in the rate quoted by contractor complete all as specified and directed
(c) Disconnecting worn out under ground cable of any type and size from main switch board/ any type of switch gear system inclduing change over switch etc. for repair and taking out under ground cable loop from fround by excavating and all necessary earth work and making frersh connection by proving suitable size of lugs for restroring of electric supply complete all as specifeid. Note: Jointing material, Lugs etc and Excavation, earth work, taking out cable protection covers, & sand cushion and relaying the same shall be deemed incldued in the rate quoted by contractor complete all as specified and directed
Dismantling old unsv ACC or ACSR conductor complete all as specified and as directed.
M&L for ACSR conductor in OH lines of HT/ LT/ street light conductor (Squirrel/ Weasel) including jumper and binding material with aluminium wire complete all as specified and directed.
M&L for cradle guard, hexagonal/ rectangular or as per existing shape fabricated with galvanised steel wire 4 mm dia including binding the gaurds with cradle supproting GI wire inclduing taking down existing unsv gaurd wire complete all as specified and as directed.
M&L for trimming of tree branches around HT / LT overhead lines inclduing cutting and removing any foriegn material like bushes or shurbs complete and removing the trimmed/ cut down branches/ bushes/ shrubs and depositing where directed at a distance not less than 100m complete all as specified and directed.Note:- (a) The item will be measured in span length. The approx span length is 35M to 50M. (b) The rates for T&P and transportation required shall be deemed incldued in the rate quoted by contractor. complete all as specified and directed
Supply and replace PVC spacers suitable for 2 wire sagged ACSR conductor complete all as specified and as directed.
Supply and replace PVC spacers suitable for 4 wire sagged ACSR conductor complete all as specified and as directed.
Dismantling unsv broken insulators of any size & types complete all as specifeid and as directed.
M&L for Pin type, porcelain, vitreous, white, brown or green insulators including one galvanised mild steel spindle, two galvanized iron washers and one galvanized iron nut, 100 mm height, 65mm dia for 1100 volts grade complete all as specified and as directed.
M&L for shackle type, porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts and nuts, of size 100 mm height, 115mm dia for 1100 volts grade complete all as specified and as directed.
Dismantling unsv stay assembly complete all as specified and as directed.
M&L for Loop type insulator, vitreous porcelain, white, brown or green, Small size, with overall dimensions 65 x 90mm, clearance of hole 16mm complete all as specified and as directed
M&L for Stay strand of size 7/3.15 mm complete all as specified and as directed.
M&L for fixing MCCBs, 4 pole, 415 volts, of as existing type and model suitable for panel mounting of capacity from 63 Amps with breaking capacity 16 KA including taking down burnt unsv complete all as specified and as directed. Make: Legrand / L&T / HPL / Standard /Havells.
M&L for fixing MCCBs, 4 pole, 415 volts, of as existing type and model suitable for panel mounting of capacity from 100 Amps with breaking capacity 25 KA including taking down burnt unsv complete all as specified and as directed. Make: Legrand / L&T / HPL / Standard /Havells.
M&L for fixing MCCBs, 4 pole, 415 volts, of as existing type and model suitable for panel mounting of capacity from 125 Amps with breaking capacity 25 KA including taking down burnt unsv complete all as specified and as directed. Make: Legrand / L&T / HPL / Standard /Havells.
M&L for fixing MCCBs, 4 pole, 415 volts, of as existing type and model suitable for panel mounting of capacity from 160 Amps with breaking capacity 36 KA including taking down burnt unsv complete all as specified and as directed. Make: Legrand / L&T / HPL / Standard /Havells.
M&L for fixing MCCBs, 4 pole, 415 volts, of as existing type and model suitable for panel mounting of capacity from 250 Amps with breaking capacity 36 KA including taking down burnt unsv complete all as specified and as directed. Make: Legrand / L&T / HPL / Standard /Havells.
M&L for fixing MCCBs, 4 pole, 415 volts, of as existing type and model suitable for panel mounting of capacity from 400 Amps with breaking capacity 36 KA including taking down burnt unsv complete all as specified and as directed. Make: Legrand / L&T / HPL / Standard /Havells.
M&L for fixing MCCBs, 4 pole, 415 volts, of as existing type and model suitable for panel mounting of capacity from 630 Amps with breaking capacity 36 KA including taking down burnt unsv complete all as specified and as directed. Make: Legrand / L&T / HPL / Standard /Havells.
M&L for fixing onload change over switch, panel mounting type without enclosure, TPN, 415 volts, 50 Hz, AC of the following sizes of existing type / model including taking down existing burnt unsv change over switch complete all as specified and as directed:- Make: Legrand / L&T / HPL / Standard /Havells. (a) 100 Amps
All as per item No 137 here-in-before but 200 Amps
All as per item No 137 here-in-before but 630 Amps
M&L for fixing onload change over switch with sheet metal enclosure, TPN, 415 volts, 50 Hz, AC of the following sizes including taking down burnt unsv complete all as specified and as directed. Make: Legrand / L&T / HPL / Standard /Havells. (a) 63 Amps
All as per item No 140 here-in-before but 100 Amps
All as per item No 140 here-in-before but 200 Amps
M&L for Stay assembly complete with accessories as shown in electrical plate No. 1 with 16mm dia stay rod and stay clamp complete all as specified and directed. Note: loop type insulator, excavation and concrete measured separately. complete all as specified and directed
-----------BLANK-----------------
-----------BLANK-----------------
Supply only Bamboo ladder 30 feet long for repair of LT / HT cable pole for repair of line and rectification of fault.
Earthing complete with galvanised MS earth plate of size 600 x 600 x 6mm thick burried directly in ground not less than 2.25 Mtr below ground level, earth plate paced on all side with charcoal mixed with salt to a thickness of 150mm in layers, connected by GI earth strip of size 32 x 6mm thick, soldered and revetted to earth plate. GI earth strip will be protected by using 40mm bore GI pipe (light grade) from test point to main board. The earthing includes PCC pit chamber, RCC pit cover and frame, watering pipe 20mm bore, funnel with wire mesh with necessary earth work including disposal of surplus soil to a distance not less than 50 Mtr etc complete all as specified and shown in electrical plate No 3 of SSR Part-I. (Note : Main earth lead beyond 7.5 metre measured and paid for separately).
Earthing complete with galvanised MS earth plate of size 600 x 600 x 6mm thick burried directly in ground not less than 2.25 Mtr below ground level, earth plate paced on all side with charcoal mixed with salt to a thickness of 150mm in layers, connected by GI earth strip of size 25 x 4mm thick, soldered and revetted to earth plate. GI earth strip will be protected by using 40mm bore GI pipe (light grade) from test point to main board. The earthing includes PCC pit chamber, RCC pit cover and frame, watering pipe 20mm bore, funnel with wire mess with necessary earth work including disposal of surplus soil to a distance not less than 50 Mtr etc complete all as specified and shown in electrical plate No 3 of SSR Part-I. (Note : Main earth lead beyond 7.5 metre measured and paid for separately).
Earthing complete with galvanised MS earth plate of size 600 x 600 x 6mm thick burried directly in ground not less than 2.25 Mtr below ground level, earth plate paced on all side with charcoal mixed with salt to a thickness of 150mm in layers, connected, soldered and revetted to earth plated / galvanised earth lead wire 4.0mm dia by means of bolts, nuts , check nuts and washers of galvanised iron or steel. GI earth wire will be protected by using 15mm bore GI pipe (light grade) from test point to main board. The earthing includes PCC pit chamber, RCC pit cover and frame, watering pipe 20mm bore, funnel with wire mess with necessary earth work including disposal of surplus soil to a distance not less than 50 Mtr etc complete all as specified and shown in electrical plate No 3 of SSR Part-I. (Note : Main earth lead beyond 7.5 metre measured and paid for separately).
Shikha Enterprises
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .