Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.3 LAccepted-Finance | L1 | Accepted-Finance Being lowest | |
| 2 | L2₹28.4 L+₹3,438.40 (0.12%)Accepted-Finance | L2 | Accepted-Finance Being not lowest | |
| 3 | L3₹33.3 L+₹5.0 L (17.5%)Accepted-Finance 1 225 5 6 SADAR BAZAR DELHI CANTT 110010 | NEW DELHI | DELHI | 110010 | L3 | Accepted-Finance Being not lowest | |
| 4 | L4₹35.3 L+₹7.0 L (24.6%)Accepted-Finance | L4 | Accepted-Finance Being not lowest |
| Sl No | Description | Qty | Unit | M/s S.G. BUILDERS L2 | M P TYAGI ENGINEERS AND CONTRACTORS L3 | Pall Associates L1 | yameen enterprises L4 |
|---|---|---|---|---|---|---|---|
| 1.00 | Dismantling and taking out old unserviceable LT panel of any type and shape after breaking of PCC foundation/platform and taking away from exisiting location after necessary disconnection of all out going and incomming cable joints, earth strips and making the surface smooth etc. complete all as specified and directed by Engr-in-Charge. | 4 | Each Job | 255 ₹1,020 Lowest | 4,999 ₹19,996 | 500 ₹2,000 | 900 ₹3,600 |
| 2.00 | Supply,installation,testing,commissioning of factory made and tested, CPRI approved LT Panel, in door type, wall mounted of size 1700x400x1200 mm (LxWxH) suitable for 415 Volts 3 phase and neutral, 4 wire, 50 Hz, AC supply system having bus bar chamber with duly insulated electrolytic copper bus bar of capacity 400 amps rating insulated on DMC insulators with busbar chamber.The Panel shall be dust and vermin proof IP 42 class protection and made out of 2.00 mm thick CRCA sheet, front opening type with approns for cable entry, with proper ferrule and cable gland , internal wiring with PVC insulated multistranded copper conduction FRLS cable of adequate size but not less than 1.5 sqm. All steel metal works including frame shall be with anticorrossive coating with seven tank process and finally epoxy polyster powder coating of siemens grey RAL-7035 Shade complete all as specified and directed. The scope of work also comprising of the following:-
(a) MCCB 250A, 4 pole,adjustable thermal magnetic type,415volts ,25 KA=01 No (for incoming)
(b) MCB SPN 63 Amps 240 volts, 10KA, C series -13 Nos (Out going)
(c) Insulated Copper Bus bar 400 Amp TPN, copper conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combbustible, track resist, high strenth DMC material. interconnection of all incomming & out goings =1 set of four
(d) Voltmeter Digital 0-500 volts with integrated selector switch and PTS - 01 No
(e) Ammeter Digital 0-400 Amps with integrated selector switch and CTS - 01 No
(f) Set of indicating lamp(RYB) LED type -01
Note :- (i) The single phase prepaid KWh energy meter retreaved from existing LT panel must be fitted in the provisional space for prepaid meter in the new LT Panel - 011 nos (ii) Time duration for replacement of LT Panel should not be more than 4 Hours. (iii) All out going feeder should be marked with quarter number. (iv) Testing certificate must be provided before installation (v) Rate quated are deemed to inclusive of all the fixture / fitting cater above. | 2 | Each | 2,25,000 ₹4,50,000 | 2,49,999 ₹4,99,998 | - | 1,75,000 ₹3,50,000 Lowest |
| 3.00 | M&L for disconnecting all the cable connection from indoor LT Panel and servicing to Panel board of any size, opening up all cubical doors, cleaning with air blower, removing the burnt out unserviceable copper wiring kit and burn out unserviceable extended copper terminals/copper cable and replacing terminal with suitable size along with required nut bolt, washers and cleaning with air blower to serviceable parts like MCCB's, all terminals, replacement of damaged aluminium/copper lugs any discription of LT UG cable/ copper wire incomming and out going, welding of broken door with suitable hinges, replacement of defective copper wiring with suitable copper conductor with circuit indiator replacement of defective rubber beading,writing various feeder complete all as specified and as directed. | 10 | Each Job | 99 ₹990 Lowest | 1,999 ₹19,990 | - | 1,500 ₹15,000 |
| 4.00 | Material and labor for demolished the old floor and scrabing the wall surface, Removing the dust and waste material from site and making the good/smooth suface of floor/wall of LT panels Room by concreate and cement work (Hard standing and Plaster ) and applying two coat paint as per direction with white colour complete all as directed. NOTE :- (I) Contractor is advised to visit the site before quoting the rates. | 10 | Each Job | 900 ₹9,000 | 499 ₹4,990 Lowest | - | 9,000 ₹90,000 |
| 5.00 | Supply,installation,testing,commissioning of factory made and tested, CPRI approved LT Panel, in door type, wall mounted of size 1200x300x800 mm (LxWxH) suitable for 415 Volts 3 phase and neutral, 4 wire, 50 Hz, AC supply system having bus bar chamber with duly insulated electrolytic copper bus bar of capacity 250 amps rating insulated on DMC insulators with busbar chamber.The Panel shall be dust and vermin proof IP 42 class protection and made out of 2.00 mm thick CRCA sheet, front opening type with approns for cable entry, with proper ferrule and cable gland , internal wiring with PVC insulated multistranded copper conduction FRLS cable of adequate size but not less than 1.5 sqm. All steel metal works including frame shall be with anticorrossive coating with seven tank process and finally epoxy polyster powder coating of siemens grey RAL-7035 Shade complete all as specified and directed. The scope of work also comprising of the following:-
(a) MCCB 160A, 4 pole,adjustable thermal magnetic type,415volts ,25 KA=01 No (for incoming)
(b) MCB SPN 63 Amps 240 volts, 10KA, C series -04 Nos (Out going)
(c) Insulated Copper Bus bar 250 Amp TPN, copper conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combbustible, track resist, high strenth DMC material. interconnection of all incomming & out goings =1 set of four
(d) Voltmeter Digital 0-500 volts with integrated selector switch and PTS - 01 No
(e) Ammeter Digital 0-400 Amps with integrated selector switch and CTS - 01 No
(f) Set of indicating lamp(RYB) LED type -01
Note :- (i) The single phase prepaid KWh energy meter retreaved from existing LT panel must be fitted in the provisional space for prepaid meter in the new LT Panel - 04 nos (ii) Time duration for replacement of LT Panel should not be more than 4 Hours. (iii) All out going feeder should be marked with quarter number. (iv) Testing certificate must be provided before installation (v) Rate quated are deemed to inclusive of all the fixture / fitting cater above. | 2 | Each | 95,000 ₹1,90,000 | 2,49,999 ₹4,99,998 | 75,000 ₹1,50,000 Lowest | 1,10,000 ₹2,20,000 |
| 6.00 | M&L for fixing/ installation of Anti Corrosion with Hot Dip Galvanized (HDG) wire mesh Type cable tray of size 300 x 50 mm with 4-6 mm thick dia including all connecting accessories for fixing/installation in the wall, hang from the roof by using the joints plates, coupler, fast lock, fast fix splicer, strengtheng bar (SBR), corner strength Bar, Hanging Bracket, Tray holder, hanging hooks, hold down coupler, central hold down clip etc, for cable management, feataring open design, for cooling, dust, resistence and easy adaptation for low voltage/data cables, supporting diffrent load capacities with specific support spans and standered like NEMA VE 1, GB/T 33630-217, and size of mesh grid 50x100 mm complete all as specified and directed by Engr-in-charge. This work alos incluudes the following tasks which are considered part of the same project, which are as follows:- (i) The existing XLPE or PVC insulated cables will be excavated from the trench or wall , and the cable will be routed through a wire mesh cable tray, which will be properly laid and suspended from the roof or fixed to the wall. The cable will be run inside a conduit, and the conduit will be fitted into the wire mesh, all the rate of cable and conduit are included in this work. (ii) If some runing meter cable has to be added to the cable while connecting it to the LT Panel , then that will also be added in this job, the cable has to be connected properly using lugs/ cable joints etc. This cable can be of diffrent types and size of XLPE / PVC insulated copper FRLS cable etc, cable connection accessories will also be installed accordingly. NOTE :- (I) All the work mentioned above and all the rate for these above points will be considered as Runing meter for this job. (II) Contractor is advised to visit the site before quoting the rates. | 300 | RM | 900 ₹2,70,000 | 799 ₹2,39,700 Lowest | 1,500 ₹4,50,000 | 2,650 ₹7,95,000 |
| 7.00 | S & F in repair factory made epoxy powder coated Load line Distribution Board VTPN-4 ways with metal door (IP-43 protection) fabricated from minimum 1.6mm thick CRCA sheet and fixed flush to wall and suitable for universal mounting and including insulated 200 Amp copper bus bar, Isolated neutral bar, standard DIN rail, Earth bar and cable ties for cable management, top and bottom removeable gland plates with knockouts and suitable for one TPN- MCCB 125/160 Amp as incomer and 32 to 63 Amp SP MCBs outgoing complete all as specified. | 3 | Each | 7,555 ₹22,665 | 9,999 ₹29,997 | 8,500 ₹25,500 | 5,500 ₹16,500 Lowest |
| 8.00 | Dismantling unserviceable burnt out MCCB by disconnecting the cable and Supply & Fix new MCCB's in the existing panel boards with new bolts, nuts,lugs& glands etc of the following capacities copmlete all as specified and directed. Note For items No. 6 to 9 , MCCB make may varies due to existing LT Panel Space for MCCB fitting , Make of MCCB as per site space/existing make.
(a) MCCB 100 Amps,4 pole 16KA, 440 Volts | 2 | Each | 2,995 ₹5,990 Lowest | 2,999 ₹5,998 | - | 4,500 ₹9,000 |
| 9.00 | MCCB 125 Amps,4 pole 16KA, 440 Volts | 6 | Each | 3,500 ₹21,000 Lowest | 3,999 ₹23,994 | - | 5,000 ₹30,000 |
| 10.00 | MCCB 160 Amps,4 pole 16KA, 440 Volts | 8 | Each | 3,900 ₹31,200 Lowest | 4,999 ₹39,992 | - | 8,000 ₹64,000 |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
11 Aug 2026, 6:00 pmClosed
LT COL MANISH E WASNIK
GE (CENTRAL) DELHI CANTT-10
8826/TOKEN-20/2026-27
2026_MES_778561_1
GE/TOKEN-20/2026-27
Open Tender
Civil Works
Item Rate
240 days
GE (CENTRAL) DELHI CANTT-10
AS PER NIT
9 documents required · 9 mandatory
₹500
Yes
GE (CENTRAL) DELHI CANTT-10
₹80,000
Yes
18 Aug 2026
14 Jul 2026
13 Aug 2026
14 Jul 2026
11 Aug 2026
28 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Dismantling and taking out old unserviceable LT panel of any type and shape after breaking of PCC foundation/platform and taking away from exisiting location after necessary disconnection of all out going and incomming cable joints, earth strips and making the surface smooth etc. complete all as specified and directed by Engr-in-Charge. | 4 | Each Job | - | - |
| 2 | Supply,installation,testing,commissioning of factory made and tested, CPRI approved LT Panel, in door type, wall mounted of size 1700x400x1200 mm (LxWxH) suitable for 415 Volts 3 phase and neutral, 4 wire, 50 Hz, AC supply system having bus bar chamber with duly insulated electrolytic copper bus bar of capacity 400 amps rating insulated on DMC insulators with busbar chamber.The Panel shall be dust and vermin proof IP 42 class protection and made out of 2.00 mm thick CRCA sheet, front opening type with approns for cable entry, with proper ferrule and cable gland , internal wiring with PVC insulated multistranded copper conduction FRLS cable of adequate size but not less than 1.5 sqm. All steel metal works including frame shall be with anticorrossive coating with seven tank process and finally epoxy polyster powder coating of siemens grey RAL-7035 Shade complete all as specified and directed. The scope of work also comprising of the following:-
(a) MCCB 250A, 4 pole,adjustable thermal magnetic type,415volts ,25 KA=01 No (for incoming)
(b) MCB SPN 63 Amps 240 volts, 10KA, C series -13 Nos (Out going)
(c) Insulated Copper Bus bar 400 Amp TPN, copper conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combbustible, track resist, high strenth DMC material. interconnection of all incomming & out goings =1 set of four
(d) Voltmeter Digital 0-500 volts with integrated selector switch and PTS - 01 No
(e) Ammeter Digital 0-400 Amps with integrated selector switch and CTS - 01 No
(f) Set of indicating lamp(RYB) LED type -01
Note :- (i) The single phase prepaid KWh energy meter retreaved from existing LT panel must be fitted in the provisional space for prepaid meter in the new LT Panel - 011 nos (ii) Time duration for replacement of LT Panel should not be more than 4 Hours. (iii) All out going feeder should be marked with quarter number. (iv) Testing certificate must be provided before installation (v) Rate quated are deemed to inclusive of all the fixture / fitting cater above. | 2 | Each | - | - |
| 3 | M&L for disconnecting all the cable connection from indoor LT Panel and servicing to Panel board of any size, opening up all cubical doors, cleaning with air blower, removing the burnt out unserviceable copper wiring kit and burn out unserviceable extended copper terminals/copper cable and replacing terminal with suitable size along with required nut bolt, washers and cleaning with air blower to serviceable parts like MCCB's, all terminals, replacement of damaged aluminium/copper lugs any discription of LT UG cable/ copper wire incomming and out going, welding of broken door with suitable hinges, replacement of defective copper wiring with suitable copper conductor with circuit indiator replacement of defective rubber beading,writing various feeder complete all as specified and as directed. | 10 | Each Job | - | - |
| 4 | Material and labor for demolished the old floor and scrabing the wall surface, Removing the dust and waste material from site and making the good/smooth suface of floor/wall of LT panels Room by concreate and cement work (Hard standing and Plaster ) and applying two coat paint as per direction with white colour complete all as directed. NOTE :- (I) Contractor is advised to visit the site before quoting the rates. | 10 | Each Job | - | - |
| 5 | Supply,installation,testing,commissioning of factory made and tested, CPRI approved LT Panel, in door type, wall mounted of size 1200x300x800 mm (LxWxH) suitable for 415 Volts 3 phase and neutral, 4 wire, 50 Hz, AC supply system having bus bar chamber with duly insulated electrolytic copper bus bar of capacity 250 amps rating insulated on DMC insulators with busbar chamber.The Panel shall be dust and vermin proof IP 42 class protection and made out of 2.00 mm thick CRCA sheet, front opening type with approns for cable entry, with proper ferrule and cable gland , internal wiring with PVC insulated multistranded copper conduction FRLS cable of adequate size but not less than 1.5 sqm. All steel metal works including frame shall be with anticorrossive coating with seven tank process and finally epoxy polyster powder coating of siemens grey RAL-7035 Shade complete all as specified and directed. The scope of work also comprising of the following:-
(a) MCCB 160A, 4 pole,adjustable thermal magnetic type,415volts ,25 KA=01 No (for incoming)
(b) MCB SPN 63 Amps 240 volts, 10KA, C series -04 Nos (Out going)
(c) Insulated Copper Bus bar 250 Amp TPN, copper conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combbustible, track resist, high strenth DMC material. interconnection of all incomming & out goings =1 set of four
(d) Voltmeter Digital 0-500 volts with integrated selector switch and PTS - 01 No
(e) Ammeter Digital 0-400 Amps with integrated selector switch and CTS - 01 No
(f) Set of indicating lamp(RYB) LED type -01
Note :- (i) The single phase prepaid KWh energy meter retreaved from existing LT panel must be fitted in the provisional space for prepaid meter in the new LT Panel - 04 nos (ii) Time duration for replacement of LT Panel should not be more than 4 Hours. (iii) All out going feeder should be marked with quarter number. (iv) Testing certificate must be provided before installation (v) Rate quated are deemed to inclusive of all the fixture / fitting cater above. | 2 | Each | - | - |
| 6 | M&L for fixing/ installation of Anti Corrosion with Hot Dip Galvanized (HDG) wire mesh Type cable tray of size 300 x 50 mm with 4-6 mm thick dia including all connecting accessories for fixing/installation in the wall, hang from the roof by using the joints plates, coupler, fast lock, fast fix splicer, strengtheng bar (SBR), corner strength Bar, Hanging Bracket, Tray holder, hanging hooks, hold down coupler, central hold down clip etc, for cable management, feataring open design, for cooling, dust, resistence and easy adaptation for low voltage/data cables, supporting diffrent load capacities with specific support spans and standered like NEMA VE 1, GB/T 33630-217, and size of mesh grid 50x100 mm complete all as specified and directed by Engr-in-charge. This work alos incluudes the following tasks which are considered part of the same project, which are as follows:- (i) The existing XLPE or PVC insulated cables will be excavated from the trench or wall , and the cable will be routed through a wire mesh cable tray, which will be properly laid and suspended from the roof or fixed to the wall. The cable will be run inside a conduit, and the conduit will be fitted into the wire mesh, all the rate of cable and conduit are included in this work. (ii) If some runing meter cable has to be added to the cable while connecting it to the LT Panel , then that will also be added in this job, the cable has to be connected properly using lugs/ cable joints etc. This cable can be of diffrent types and size of XLPE / PVC insulated copper FRLS cable etc, cable connection accessories will also be installed accordingly. NOTE :- (I) All the work mentioned above and all the rate for these above points will be considered as Runing meter for this job. (II) Contractor is advised to visit the site before quoting the rates. | 300 | RM | - | - |
| 7 | S & F in repair factory made epoxy powder coated Load line Distribution Board VTPN-4 ways with metal door (IP-43 protection) fabricated from minimum 1.6mm thick CRCA sheet and fixed flush to wall and suitable for universal mounting and including insulated 200 Amp copper bus bar, Isolated neutral bar, standard DIN rail, Earth bar and cable ties for cable management, top and bottom removeable gland plates with knockouts and suitable for one TPN- MCCB 125/160 Amp as incomer and 32 to 63 Amp SP MCBs outgoing complete all as specified. | 3 | Each | - | - |
| 8 | Dismantling unserviceable burnt out MCCB by disconnecting the cable and Supply & Fix new MCCB's in the existing panel boards with new bolts, nuts,lugs& glands etc of the following capacities copmlete all as specified and directed. Note For items No. 6 to 9 , MCCB make may varies due to existing LT Panel Space for MCCB fitting , Make of MCCB as per site space/existing make.
(a) MCCB 100 Amps,4 pole 16KA, 440 Volts | 2 | Each | - | - |
| 9 | MCCB 125 Amps,4 pole 16KA, 440 Volts | 6 | Each | - | - |
| 10 | MCCB 160 Amps,4 pole 16KA, 440 Volts | 8 | Each | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.42 MB
BOQ_872005.xls
BOQ • 0.33 MB
tenderpage.pdf
Tender Documents • 0.92 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .