Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹4.4 CrAdmitted-Finance | -27.77% | ₹4.4 Cr | L1 | Admitted-Finance |
| 2 | L2₹5.0 CrAdmitted-Finance | -17.99% | ₹5.0 Cr | L2 | Admitted-Finance |
| 3 | L3₹5.8 CrAdmitted-Finance | -5.21% | ₹5.8 Cr | L3 | Admitted-Finance |
Tender Value
₹6.1 Cr
EMD Value
₹12.2 L
Closing Date
28 Jan 2026, 6:00 pmClosed
XEN PWD Udhampur
Udhampur
BOQ
2026_PWDJK_299867_1
e-NIT No. 120 of 2025-26 dated 03.01.2026
Open Tender
Civil Works
720 days
Udhampur
NIT
2 documents required · 2 mandatory
₹6,000
S.E PWD (RandB) Udhampur-Ramban, Udhampur
₹12.2 L
Udhampur
11 Feb 2026
3 Jan 2026
29 Jan 2026
3 Jan 2026
28 Jan 2026
6 Jan 2026
15 Jan 2026
Surface dressing of the ground including removing vegetation and in-equalities not exceeding 15 cm deep and disposal of rubbish, lead upto 50 m and lift upto 1.5 m in -All kinds of soil
Earth work in bulk excavation by mechanical means (hydraulic excavator) over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 m2 on plan) including disposal of excavated earth lead upto 50 meters and lift upto 1.5 m, as directed by Engineer-in-Charge all kind of soil.
Earth work in excavation by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed: 1 meter from cutting edge All kinds of soil
Extra for every additional lift of 1.5 m or part thereof in excavation/ banking excavated or stacked material in all kinds of soil.
Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level with 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)
Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level with 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in charge. all works upto plinth level
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in charge. All works above plinth level upto floor V level
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto & above plinth level Thermo-Mechanically Treated bars of grade Fe-500D or more.
Centering and shuttering including strutting, propping etc. and removal of form work for :-
Foundations, footings, bases of columns etc. for mass concrete
Columns, pillars, piers, abutments, posts and struts
Lintel, beams, plinth beams, girders, bressumers and cantilevers
Suspended floors, roofs, landings, balconies and access platforms.
Edges of slabs and breaks in floors and walls upto 20cm wide.
Weather shades, chajjas, corbels etc. including edges.
Wall (any thickness) including attached pilasters, buttresses, plinth and string courses fillets etc
Stairs (excluding landings) except spiral stair cases.
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc. including cost of de-shuttering and decentring at all levels, over a height of 3.5m, for every additional height of 1 mtr. of part thereof (Plan area to be measured). Suspended floors, roofs landing, beams and balconies (Plan area to be measured)
Providing and laying damp-proof Course 50 mm thick with cement concrete 1:2:4 (1 cement:2 coarse sand: 4 graded stone aggregate 20 mm nominal size) and curing complete
Applying a coat of residual petroleum bitumen of grade VG-10 of approved quality using 1.7 kg per square meter on damp proof courses after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil.
Brick work with common burnt clay (non-modular) bricks of class designation 7.5 in foundation and plinth including curing in Cement mortar 1:4 ( 1 cement : 4 coarse sand)
Brick work with common burnt clay (non-modular) bricks of class designation 7.5 in foundation and plinth including curing in Cement mortar 1:6 ( 1 cement : 6 coarse sand)
Extra for brick work with common burnt clay bricks/cement concrete bricks in superstructure above plinth level upto floor five level
Half brick masonry with common burnt clay (non-modular) bricks of class designation 7.5 in foundations and plinth including curing in Cement mortar 1:4 ( 1 cement : 4 coarse sand)
Extra for half Brick masonry in superstructure above plinth level upto floor V level.
Extra for providing and placing in position 2 Nos. 6mm dia. M.S. bars at every third course of half brick masonry.
6 mm cement plaster to ceiling of mix 1 : 3 (1 cement : 3 fine sand)
12mm Cement Plaster of Mix 1:6 (1 Cement :6 coarse Sand)
15mm Cement Plaster on the rough side of single or half brick wall of Mix 1:6 ( 1 Cement: 6 coarse Sand)
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead upto 50 m and lift upto 1.5 m.
Supplying and filling in plinth with fine sand under floors including, watering, ramming, consolidating and dressing complete
Making of grove 12mm x 10mm between brick and RCC.
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm bed of dry brick ballast 40mm nominal size well rammed and consolidated and grouted with fine sand including finishing the top smooth and curing complete
Brick edging 7cm wide 11.4cm deep to plinth protection with common burnt clay (non modular) bricks of class designation 7.5 including grouting with cement mortar 1:4 (1 Cement : 4 fine sand) and curing complete.
Providing and laying integral cement based water proofing treatment including preparation of surfaces as required for treatment of roofs, balconies, terraces etc consisting of following operations. a) Applying a slurry coat of neat cement using 2.75kg/sqm of cement admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge over the RCC Slab including adjoining walls upto 300mm height including cleaning the surface before treatment. b) Laying brick bats with mortar using broken bricks/ Brick Bats 25mm to 115mm size with 50% of Cement mortar 1:5 (1 Cement : 5 coarse sand) admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge over 20mm thick layer of cement mortar of mix 1:5 (1 Cement : 5 coarse sand) admixed with water proofing compound conforming to IS 2645 and approved by Engineer in-charge to required slope and treating similarly the adjoining walls upto 300mm height including rounding of Junctions of walls and slabs) c) After two days of proper curing applying a second coat of cement slurry using 2.75kg/sqm of cement admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge. d) finishing the surface with 20mm thick joint less cement mortar of mix 1:4(1 cement: 4 coarse sand) admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300mm/sq 3mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by Engineer in-charge. With average thickness of 120mm and minimum thickness at khurra as 65 mm
Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement: 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete
Providing & laying water proofing treatment to vertical and horizontal surfaces of depressed portions of W.C., kitchen & the like consisting of: (i) Ist course of applying cement slurry @ 4.4 kg/sqm mixed with water proofing compound conforming to IS 2645 in recommended proportions including rounding off junction of vertical and horizontal surface. (ii) IInd course of 20 mm cement plaster 1:3 (1 cement: 3 coarse sand) mixed with water proofing compound in recommended proportion including rounding off junction of vertical and horizontal surface. (iii) IIIrd course of applying blown or residual bitumen applied hot at 1.7 kg. Per sqm of area. (iv) IVth course of 400 micron thick PVC sheet. (Overlaps at joints of PVC sheet should be 100 mm wide and pasted to each other with bitumen @ 1.7 kg/sqm).
Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchors blocks, plain window sills, fillets etc upto floor V level, including curing but excluding the cost of centring, shuttering and finishing with. 1:5:10 (1 cement : 5 coarse sand : 10 graded brick aggregate 40 mm nominal size
Providing and fixing 16mm thick Durastone tile 600x600mm (Geo stone/tex stone finish) of NITCO, ORIENT, SCMANY, KAJARIA or equivalent make in colour such as white, Ivory, Grey, Fume Red, Brown etc laid on 20mm thick bed of cement mortar 1:4 (1 cement : 4 coarse sand) including pointing the joints with white cement and matching pigment etc. complete.
Providing and laying vitrified floor tiles in Size of tile 600x1200 mm (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622 of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1cement :4 coarse sand) including grouting the joints with white cement and matching pigments etc. complete
Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
Providing and fixing 18 mm gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels Granite of any colour or shade (Area of slab over 0.5 sqm)
Providing edge moulding to 18 mm/16 mm thick marble stone counters, Vanities etc. including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge. Granite Work
Extra for providing opening of required size and shape for wash basin/ kitchen sink in kitchen platform, vanity counters and similar location in marble/granite / stone work including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete
Providing and laying Ceramic glazed floor tiles 300x300 mm (thickness to be specified by the manufacturers) of 1st quality conforming to IS: 15622 of approved make, laid on 20 mm thick bed of cement mortar 1: 4 ( 1 cement : 4 coarse sand) including pointing the joints with white cement and matching pigment etc., complete. In colour such as White, Ivory, Grey, Fume Red Brown
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer- in-Charge, in skirting, risers of steps and dados over 12 mm thick bed of cement mortar 1:3 ( 1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3 kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia and length (hold fast lugs or with dash fasteners shall be paid for separately) Sal wood
Providing and fixing 35 mm glazed shutters for doors, windows and clerestory windows using 4mm thick float glass panes including ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws. Second class deodar wood
Providing and fixing 35 mm wire gauze shutters using galvanized M.S. wire gauze of average width for aperture 1.4 mm in both directions with wire of dia. 0.63 mm for doors, windows and clerestory windows with ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws as per direction of Engineer-in-charge Second class deodar wood
Providing and fixing of block door shutters in pine wood filling and finished with 1mm thick laminated on both sides. Door held with 4 No.S.S but hinges with necessary S.S screws as per directions of Engineer-in-charge with deodar wood beading of 4mm x 37mm section all around door.
Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc including priming coat with approved steel primer all complete. Fixed to openings / wooden frames with rawl plugs screws etc
Providing and fixing of glass panes, with wooden deodar fillets Float glass panes of thickness 5.0 mm (weight not less than 12.5 kg/sqm)
Providing and fixing bright finished brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles of approved quality with necessary screws etc. complete
Providing and fixing aluminum tubular handle bar 32mm outer dia, 3.0mm thick & 2100mm long with SS screw etc. complete as per direction of Engineer-in-charge Powder coated minimum thickness 50 micron aluminum tabular handle bar
Providing and fixing aluminum hanging floor door stopper, ISI marked, anodized (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete Twin rubber stopper
Providing and fixing aluminum tower bolts ISI marked anodized (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete
Providing and fixing aluminum sliding door bolts ISI marked anodized (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc. complete 300x16 mm
Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embeddings in cement concrete block 30x10x15 cm 1:3:6 mix ( 1 cement : 3 coarse sand : 6 gradedstone aggregate 20 mm nominal size)
Providing and fixing bright /matt finished Stainless Steel handles of approved quality & make with necessary screws etc all complete. 100 mm
Providing and fixing on wall face un-plasticized Rigid PVC rain water pipes conforming to IS: 13592 Type A including jointing with seal ring conforming to IS: 5382 leaving 10 mm gap for thermal expansion. (i) Single socketed pipes 110 mm diametre
Providing and fixing on wall face un-plasticized - PVC moulded fittings/accessories for un plasticized Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.
Coupler 110 mm
Single tee without door 110x110x110 mm
Bend 87.5° 110 mm bend
Providing and fixing un-plasticised -PVC pipe clips of approved design to un-plasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. 110 mm
Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diametre and weighing not less than 440 grams.
Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes channels, plates etc. including welding ,grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete ,including fixing the railing with necessary accessories and stainless steel dash fasteners, stainless steel bolts etc. of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.).
Applying priming coat With ready mixed pink or grey primer of approved brand and manufacture on wood work (hard and soft wood)
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade Two or more coats on new work
Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface
Providing and applying white cement based putty of specified thickness, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. 1 mm thick
Finishing walls with textured exterior paint of required shade on New work (two or more coats applied @ 3.28 liter/10sqm) over and including base coat of exterior primer applied @ 2.20kg/10sqm
Finishing walls with acrylic smooth exterior paint of required shade on New work (Two or more coats applied @ 1.67 liter/10sqm over and including priming coat of exterior primer applied @ 2.20kg/10sqm)
Wall Painting with acrylic emulsion paint of approved brand and manufacture to give an even shade. Two or more coats on new work
Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement: 2 coarse sand: 4 stone aggregate 10 mm and down gauge), including finishing with cement mortar 1:3 (1 cement: 3 fine sand) as per standard design. In 75x75 mm deep chase.
Providing and laying 60mm thick factory made cement concrete interlocking paver block of M-30 grade made by block making machine with strong vibratory compaction and of approved size and design/shape laid in required colour and pattern over and including 50mm thick compacted bed of fine sand, filling the joints with coarse sand etc. all complete as per direction of Engineer-in-charge.
Providing, fixing and applying Plaster of Paris (POP) false ceiling consisting of frame work made with 50mm sq M.S. tubes of 18 G thickness as main runner at 600 mm c/c both ways, suspended/ supported with M.S. flats 25x4 mm from existing R.C.C. slab, finished smooth to line and level including necessary supports, scaffolding etc. as required and also including applying a coat of red oxide zinc chromate primer over the M.S. frame work and suspenders complete. Including providing and fixing expanded metal of size 5.25 mm x 1.25 mm thickness welded to main runners and applying POP (calcium sulphate semi hydrate variety) to the expanded metal of thickness not less than 10 mm
Supplying and stacking of good earth at site including royalty (earth measured in stacks will be reduced by 20% for payment)
Supplying and stacking at site dump manure from approved source including carriage complete (manure measured in stacks will be reduced by 8% for payment)Screened through sieve of I.S. designation 4.75 mm .
Fine dressing of the ground.
Mixing earth and sludge or manure in proportion specified or directed by officer in charge.
Demolishing brick work manually/by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 meters lead as per direction of Engineer-in-charge in cement mortar
Demolishing R.C.C. work manually/by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 meters lead as per direction of Engineer-in-charge.
Demolishing cement concrete manually/by mechanical means including disposal of material within 50 meters lead as per direction of Engineer-incharge 1:3:6 or richer mix (i/c equivalent design mix)
Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 meters lead of area of 3 sqm and below.
Dismantling steel work in built up sections in angles, tees, flats and channels including all gusset plates, bolts, nuts, cutting rivets, welding etc. including dismembering and stacking within 50 meters lead.
Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 meters lead. For thickness of tiles 10 mm to 25 mm
Carriage of Building Rubbish/Material at an average lead of 5KM by Mechanical Transport including loading, unloading and stacking.
Carriage of material by Mechanical Transport including loading / unloading and stacking at site complete.
Sand for an average lead of 15 Kms.
Stone aggregate below 40mm size for an average lead of 15 Kms.
Stone aggregate above 40mm size for an average lead of 15 Kms.
Bricks for an average lead of 50 Kms
Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) (Essel Cat No-76031011 / Kerovit Cat No- KS112 / CERA CAT NO- S1053121) with seat and lid, 10 liter low level white P.V.C. flushing cistern (Essel Cat No- 402101 / Kervoit Cat No- KO1005 / CERA CAT NO- B1010110), including flush pipe with manually controlled device (handle lever), conforming to IS:7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: W.C. pan with ISI marked white solid plastic seat and lid. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing wash basin (Essel Cat No-72001140 / Kerovit Cat No- KS234 / CERA CAT NO- S2040120) with C.I. brackets, 15 mm dia CP Brass single hole basin mixer (Essel Cat No-113001 / Kerovit Cat No- KB1311010 / CERA CAT NO- F1020451) of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:- (a) White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing white vitreous china pedestal (Essel Cat No-72011071 / Kerovit Cat No- 305 / CERA CAT NO- S2090113) for wash basin completely recessed at the back for the reception of pipes and fittings. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per I.S. 13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required : Kitchen sink with drain board 510x1040mm bowl depth 250mm (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing CP Brass Single lever telephonic wall mixer (Essel Cat No 113067-307001 / Kerovit Cat No.KB411020-KA510002 & CERA CAT NO- F1020403-F7030101AB) of quality & make as approved by Engineer in charge. (a) 15 mm nominal dia. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing 15 mm nominal bore C.P. brass bib cock of approved quality conforming to IS : 8931. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing 15 mm nominal bore C.P. brass long nose bib cock of approved quality conforming to IS standards and weighing not less than 810 gms. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing C.P. brass shower rose with 15 or 20 mm inlet 150 mm diameter (MAKE:- Kerovit, Essel, CERA, Hindware).
Providing and fixing 15 mm nominal bore C.P. brass angle valve (Essel Cat No 113052, Kerovit Cat No- KB2111003 & CERA CAT NO- F1023201) for basin mixer and geyser points or wherever required as per the direction of Engineer Incharge of approved make conforming to IS : 8931. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing C.P. Brass extension nipple (size 15mmx50mm) of approved make and quality as per direction of Engineer-incharge.(MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing 8 mm dia C.P. / S.S. Jet with flexible tube upto 1 metre long with S.S. triangular plate to European type W.C. of quality and make as approved by Engineer - in - charge. (MAKE:- Kerovit, Essel, CERA Hindware)
Providing & fixing C.P. hand spray with lever control (health faucet) (ESSEL CAT NO- 309004, Kerovit CAT NO- KA580007 & CERA CAT NO- F8030106AB) and flexible hose 1 m long connection with C.P. holder for hand spray complete in all respects as per direction of Engineer-Incharge. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing P.V.C. waste pipe for sink or wash basin (ESSEL CAT NO- 301206) including P.V.C waste fittings complete: Flexible pipe . 40 mm dia (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing toilet paper holder (ESSEL CAT NO - 113027, KEROVIT CAT NO - KA93007 & CERA CAT NO- F5015109CH) C.P. brass. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing Waste Coupling for wash basin and sink, of approved quality and colour: Waste coupling 31mm of 79 mm length and 62 mm breadth weighing not less than 45gms. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing Bottle Trap for Wash basin and sink: Bottle trap 31 mm single piece moulded with height of 270 mm, effective length of tail pipe 260 mm from the centre of the waste coupling 77 mm breadth with 25 mm minimum water seal, weighing not less than 260 gms. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with brackets of the same materials with snap fittings of approved quality and colour, weighing not less than 105 gms. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing towel ring trapezoidal shape 215 mm long, 200 mm wide with a minimum distance of 37 mm from wall face with concealed fittings arrangements of approved quality and colour, weighing not less than 88 gms. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fitting arrangement of approved quality and colour: 450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 gms. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing shelf 440 mm long, 124 mm width and 36 mm height of approved quality and colour, weighing not less than 300 gms. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing G.I. inlet connection for flush pipe connecting with W.C. pan.or wherever required as per the direction of Engineer Incharge. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing soap dish holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106gms. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. (MAKE:- Kerovit, Essel, CERA, Hindware)
Providing, Installing, testing & commissioning of Kent Supreme Plus Alkaline+ Copper Ro water purifier, suitable for borewell/ tanker/muncipal water supply, with following specification: Purification Technology- RO+UV+UF+Alkaline+ copper + TDS Control, storage capacity with 8 litres , Flow rate 20Lph. Advanced features: auto flush, UV LED tank, retains Essential Minerals, Alkaline & copper enriched water Brand/ Model Kent Supreme Plus ( or Equivalent approved make)
Providing and fixing Polyethylene- Aluminum- Polyethylene (PE-AL-PE) Composite Pressure Pipes conforming to IS: 15450, U.V. stabilized with carbon black having thermal stability for hot and cold water supply, capable to withstand temperature upto 80ºC, including all special fittings of composite material (engineering plastic blend and brass inserts wherever required) e.g. Elbows, tees, reducers, couplers and connectors etc.This includes testing of joints complete as per direction of the Engineer-in-charge:( Make : Kitec, Vista, Prayag, Supreme.) Internal work-exposed on wall with clamps at 1.00 meter spacing
1216 (16mm OD) pipe.
1620 (20mm OD) pipe.
Providing and fixing Polyethylene- Aluminum- Polyethylene (PE-AL-PE) Composite Pressure Pipes conforming to IS: 15450, U.V. stabilized with carbon black having thermal stability for hot and cold water supply, capable to withstand temperature upto 80ºC, including all special fittings of composite material (engineering plastic blend and brass inserts wherever required) e.g. Elbows, tees, reducers, couplers and connectors etc.This includes testing of joints complete as per direction of the Engineer-in-charge:( Make : Kitec, Vista, Prayag, Supreme.) Internal work concealed with clamps at 1.00 meter spacing including cutting the chases and making good the wall etc.
1216 (16mm OD) pipe.
1620 (20mm OD) pipe.
Providing and fixing G.I. pipes complete with G.I. fittings excluding trenching and refilling etc. (external work)
25 mm dia. nominal bore (Medium)
32 mm dia. nominal bore (Medium)
40 mm dia. nominal bore (Medium)
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete.
15 mm nominal bore
20 mm nominal bore
25 mm nominal bore
Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end)
25 mm dia. nominal bore
32 mm dia. nominal bore
40 mm dia. nominal bore
Painting G.I. pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work.
25 mm diameter pipe
32 mm diameter pipe
40mm diameter pipe
Making connection of G.I. distribution branch with G.I. main of following sizes by providing and fixing Tee, including cutting and threading the pipe etc. complete
25 to 40 mm nominal bore
Providing and fixing G.I. Union in G.I. pipe including cutting and threading the pipe and making long screws etc. complete (new work).
15 mm dia. nominal bore
20 mm dia. nominal bore
25 mm dia. nominal bore
32 mm dia. nominal bore
40mm dia. nominal bore
Earthwork in all kinds of soil excavation by manual means in trenches for foundations, drains, pipes, cable etc. (not exceeding 1.5 in width) and for shafts, wells, cesspits and the like not exceeding 10 Sqm on plan, depth upto 1.5 Mtr including disposal of excavated earth upto 1 Mtr from cutting edge, disposed earth is to be levelled and neatly dressed.
Providing and fixing on wall face unplasticised-Rigid PVC pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10mm gap for thermal expansion. MAKE Supreme, asirwad, jain with. All necessary fittings and Accessories as per the Direction of Engineer Incharge.
75MM dia
110MM dia
150MM dia
Constructing brick masonry chamber for underground C.I. inspection chamber and bend with common burnt clay (non modular) bricks of class designation 7.5 in cement mortar 1:4 ( 1 cement : 4 coarse sand) C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg ) R.C.C. top slab with 1:1 ½ : 3 mix ( 1 cement : 1 ½ coarse sand : 3 graded stone aggregate 20 mm nominal size),foundation concrete 1:5:10 (1 cement: 5 fine sand: 10 graded stone aggregate 40mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 ( 1 cement : 3 coarse sand) finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete as per standard design Inside dimensions 455x610 mm and 45 cm deep for single pipe line-
Constructing brick masonry chamber for underground C.I. inspection chamber and bend with common burnt clay (non modular) bricks of class designation 7.5 in cement mortar 1:4 ( 1 cement : 4 coarse sand) C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg ) R.C.C. top slab with 1:1 ½ : 3 mix ( 1 cement : 1 ½ coarse sand : 3 graded stone aggregate 20 mm nominal size),foundation concrete 1:5:10 (1 cement: 5 fine sand: 10 graded stone aggregate 40mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 ( 1 cement : 3 coarse sand) finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete as per standard design inside dimensions 600x850 mm and 45 cm deep for single pipe line with three or more inlets.
Providing and fixing heavy class SS grating plane including setting in floor with cement motor to match with floor finish as per direction of Engineer-Incharge (Size 100 mm dia) (ISI Marked)
Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked indicating the BIS License No. with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank (Sintex, Electroplast, star, Lotous or equivalent having valid ISI license) (1000 ltr. Capacity.).
Making soak pit 2.5 m diameter 3.0 meter deep with 45x45 cm dry brick honey comb shaft with common burnt clay (non modular) bricks of class designation 7.5 bricks and S.W. drain pipe 100 mm diameter, 1.8 m long complete as per standard design.
Supply, assembly, erection, testing and commissioning of pumping system comprising the following: Vertical/Horizontal centrifugal pumps with mechanical seal, SS Volute casing and SS impeller connected to suitable capacity TEFC induction motor suitable for 415 ± 10 % volts, Single phase, 50 cycles A.C. supply with 80/ 80 mm dia. pressure gauges including MS skid and mounting of the pumps on the skid. (Motor to be of the same make as the pump) (Make:- Crompton,Wilo, Ebara and Matherplatt etc.) Model MBQ32(1PH)-15, Capacity 3 H.P, Suction -80mm x Delivery 80mm (Domestic water relift pump).
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group A
Wiring for Light /Power Plug with 2 x 4 sq.mm FRLS PVC Insulated Copper Conductor single core cable in surface / Recessed medium class PVC Conduit along with 1 No. 4 sq.mm FRLS PVC Insulated copper conductor single core cable for loop earthing as required.
Wiring for Circuit /Submain Wiring along with earth Wire with the following Sizes of FRLSPVC insulated copper conductor,single core Cable in surface / Recessed medium class PVC conduit as required.
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
4 X 16 sq. mm + 2 X 6 sq. mm earth wire
2 X 6 sq. mm + 1 X 6 sq. mm earth wire
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel / PVC conduit as required.
1 x 1.5 sq. mm
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
Bell push
Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Supplying and fixing modular blanking plate on the existing modular plate and switch box excluding modular plate as required.
Supplying and Fixing suitable size G.I box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps modular switch, connection, painting etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required.
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required. (For Geyser and A.C)
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
6 way (4 + 18), Double door
12 way (4 + 36), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single Pole
Single pole and neutral
Supplying and fixing 40 A to 63 Arating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole and neutral
Supplying and fixing following rating, Four pole, 415 V, 10 Ka M.C.B in the existing MCB DB complete with connections, testing and commissioning etc. as required.
63 A F.P MCB 10 Ka "C" Curve
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required.
12 way , Double door
16 way , Double door
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying, installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K / 6000°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminum Body including trim
Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminum body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP 66,IK-10, CRI >80, under voltage and over voltage protection, EMI/ EMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin),SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). 120 watt
Supply installation testing and commissioning of Ceiling Fan 3 Star Rated with Voltage Range 90 V to 300 V,Min. Air Delivery 212 CMM,Service Value 5.3 Cu.m/min/watt,Aluminium Blades ,including wiring the down rods of standard length(Upto 45 cm)with 1.5 sq.mm FR PVC insulated,copper conductor,single core cable including providing and fixing phenolic laminated sheet cover on the Fan Box etc as Required. 1200 MM
Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm) 40 watt
Supply,Installation,Testing and Commissioning 486 Cu.m/Hr. AC 220-240 Volts, 50 Hz exhaust fan made out of Metal Body with inbuilt thermo cutoff Protection and Noise Level not exceeding 37 dB of Following Sizes including connection etc. complete as required .
Supply installation testing and commissioning of IP65 led Bulk head 8-10 Watt +/- 1 W LED Surface Pressure Die Cast Aluminum system lumen efficacy of 100 lm/W with Polycarbonate Opal Diffuer and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80, IK rating IK08. The LED with Useful life of 50000 Hrs at L70. The Input voltage range shall be 150V to 265V. The Fixture should have In-built Surge Protection of 2.5kV Certification:- LM79 & LM80 test report should be from govt approved Inhouse NABL lab/ government of India authorised lab. (>105< 120 /m /wattt).
Supply installation testing and commissioning of decorative Mirror Light IP:20 10W-12 W +- 1 W LED Surface Mounted 2 ft. with system lumen efficacy of 100 lm/W and P.F >0.9 THD <20% CCT 6500K,CRI 80 .The LED should have life of 50000 Burning Hours at L70.The input voltage shall be 150 V to 270 V.The fixture should have inbuit surge protection of 2KV.Certification-LM 79 and LM 80.The test report should be from Govt. Approved Lab/inhouse NABL Lab.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Supplying,Installation,Testing and Commissioning of Cubical Type Outdoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars etc. as required as per the Following Description. (IP:65) ( Transformer Panel Board ) .The successful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel.Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating.The Panel Builder Shall be CPRI /ERDA/ANY NABL ACCREDITED LAB approved. Refer SLD.
INCOMER
Adj. TMR Based MCCB 400 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH
TMR Based MCCB 125 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH
500 A,415 Volts 50Hz Aluminium Busbar set of 4 strips
150 A,415 Volts 50Hz Aluminium Busbar set of 4 strips
OUTGOINGS
Manual Changeover Switch 125 A F.P 415 Volts Ac-23 Duty
TMR Based MCCB 320 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH
TMR Based MCCB 125 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH
Adj. TMR Based MCCB 100 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH
Adj. TMR Based MCCB 63 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH
Load Bearing Members to be made out of 2.0 mm CRCA Sheet.
Partitions to be made out of 1.6 mm CRCA Sheet
Gland Plates to be 3.0 mm Thick.
Supplying,Installation,Testing and Commissioning of Cubical Type Indoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers, Out Goings,Bus Bars etc. as required as per the Following Description .(IP:42) ( Non-Essential Distribution Panel ) .The successful tenderer shall take prior approval for the panel builder/ fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel. Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating. The Panel Builder Shall be CPRI /ERDA/ANY NABL ACCREDITED LAB approved.Refer SLD
INCOMER
Adj. TMR Based MCCB 320Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH
400 A,415 Volts 50Hz Aluminium Busbar set of 4 strips
OUTGOINGS
MCB 63 A F.P "C" Curve 10 Ka
Load Bearing Members to be made out of 2.0 mm CRCA Sheet.
Partitions to be made out of 1.6 mm CRCA Sheet
Gland Plates to be 3.0 mm Thick.
Supplying,Installation,Testing and Commissioning of Cubical Type Indoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars etc. as required as per the Following Description. (IP:42) ( Essential Distribution Panel ) .The successful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel.Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating. The Panel Builder Shall be CPRI /ERDA/ANY NABL ACCREDITED LAB approved.Refer SLD
INCOMER
Adj. TMR Based MCCB 100Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH
150 A,415 Volts 50Hz Aluminium Busbar set of 4 strips
OUTGOINGS
Adj. TMR Based MCCB 63 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH
D.P 25 A 10 Ka "C" Curve MCB
D.P 32 A 10 Ka "C" Curve MCB
Load Bearing Members to be made out of 2.0 mm CRCA Sheet.
Partitions to be made out of 1.6 mm CRCA Sheet
Gland Plates to be 3.0 mm Thick.
Supplying and Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in groundin Existing DWC Pipe including excavation, sand cushioning, protective covering and refilling the trench etc as required.
3.5 C X 300 Sq.mm A2XFY
3.5 C X 35 Sq.mm A2XFY
3.5 C X 25 Sq.mm A2XFY
Supply and Making end Termination with Brass Compression Gland and Aluminium Lugs for the Following Sizes of PVC insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 KV Grade as Required (Comet)
3½ X 300 sq. mm (70mm)
3½ X 35 sq. mm (32mm)
3½ X 25 sq. mm (28mm)
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. complete as required.
200 mm dia (OD-200 mm & ID-175 mm nominal)
63 mm dia (OD-63 mm & ID-51 mm nominal)
Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required.
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For horizontal run)
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For vertical run)
Supplying and Fixing Surface Mounting Socket Outlet with Plug Top with MCB Provision IP:67 63 A 5 Pin including connection,painting etc. as required.
Supplying,Testing and Commissioning of 12 V 1.5 KVA Sine Wave Inverter with 1 Nos of Tall tubular inverter battery 150 Ah.
Supply,Installation,Testing and commissioning of 10 W Strip Light indoor Application
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
1 or 2 Module (75mmX75mm)
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
Telephone socket outlet
Computer Socket RJ45 Modular type
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.
Supply, installation, testing and commissioning of Junction Boxes/DB-10 Pairs with Original Krone module and Back Mount Frame and have Lock -n- key, complete in all respect as per specification and desired by EIC
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.
1 run of cable
Supply & Erection of lockable 12 U rack with 5A strip and two fan for distribution, mounting of patch panels, hubs, switches etc,, complete as per specification and as desired by EIC.
Supply, installation, Testing & Commissioning of 'Silent Type Diesel Generating set as per CPCB IV + or better norms along with having Prime Power Rating of KVA as below, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor, including testing at factory and site with fuel, load for test and other necessary arrangements Complete as per CPWD specifications, should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location, rating plate as per relevant IS Code etc. and consisting of the followings:
(A) Diesel Engine: Turbocharged Diesel engine 4 stroke water cooled, multi cylinder, dynamically balanced fly wheel, electric start of suitable BHP at 1500 RPM suitable for above output of alternator at 40 Degree C, 50% RH & at 1000 Meter MSL , capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be with Electronic governor, Dry type Air filter with service indicator, first filling of engine fuel (after commissioning) lubricating Oil, Coolant and other consumables complete with all the required accessories, the Electronic governor shall be as per ISO 8528.The engine shall comply to the latest CPCB norms (CPCB IV + or better) and Conforming to BS 5514, BS 649, IS 10000, IS 10002, IS 13018 and as per CPWD specifications.
(B) Engine mounted Instrument Panel fitted with and having digital display for following: (i) Start-stop switch with key (ii) Water temperature indication (iii) Lubrication oil pressure indication (iv) Lubrication oil temperature indication (v) Battery charging indication and Voltage indication (vi) RPM indication (vii) Over speed indication (viii) Low lubricantion Oil trip indication (ix) Engine Running Hours indication (x) Fuel Level
(C) Alternator: Synchronous alternator rated of appropriate KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 Degree C, 50% RH & at 1000 Meter MSL. The alternator shall be having Screen Protected Drip Proof (SPDP) enclosure IP23, brushless, continuous duty, dynamically balanced rotor, capable of taking 10% over loading for one hour after 12 hours of continuous operation, self cooled,self-excited and self-regulated through AVR conforming to IS13364(Part 2)/IS: 4722/BS 2613 suitable for tropical conditions and with class- H insulation.
(D) Base Frame & Foundation: Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer.
(E) FUEL TANK: Daily service fuel tank of suitable liters capacity as per CPWD Specifications, fabricated out of 3 mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class 'C' pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications.
(F) Exhaust System: Dry exhaust manifold with hospital type exhaust silencer and catalytic convertor.
(G) Starting System: 12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries (180 AH capacity lead acid SMF type) as required as per specifications. The battery shall be housed inside the acoustic enclosure of DG Set.
(H) Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere and the temperature rise inside the enclosure, noise level outside enclosure. The acoustic enclosure should be suitable for cable connection/ connection through bus-trunking. Such arrangements on acoustic enclosure should be water proof & dust-proof conforming to IP-65 protection. The enclosure shall be as per CPCB IV + or better norms etc. and as per CPWD specifications.
9. Main supply failure monitor. 10. Supply failure timer. 11. Restoration timer 12. Control unit with three impulse automatic engine start/stop and failure to start lockout. 13. Impulse counter with locking and reset facility. 14. ON/OFF/Control circuit switch with indicator 15. Audio/Video annunciation for (i) High water temperature (ii) Low lubricating oil pressure (iii) Engine over speed (iv) Engine fails to start (v) Full load/maximum load warning 16. Protection for over/under Frequency, Loss of AC sensing, Over Current, Unbalancing load with suitable number of relays and accessories 17. Maintenance notification based on Engine Run Hour & due date. 18. Load Management through PLC to achieve auto opening and closing of incomer breakers, bus coupler switching of essential panel, interlocking providing signal to AMF Panel for load status and AMF shall give command to DG Set to auto start / auto stop depending upon load status and requirement etc. and necessary hardware and software required to perform the operation shall be provided by the contractor including all control wiring.
HVAC Equipments; VARIABLE REFRIGERANT FLOW SYSTEM Supply, Installation, Testing and Commissioning of Variable Refrigerant Flow modular type air- conditioning system suitable for Cooling/Heating by inverter driven capacity control compressor complete with indoor and outdoor units with individual controller and with fittings etc., as per quantity given below including full charging of R-410A refrigerant gas inside the Outdoor/Indoor units and inside all the Copper Piping between all the Otdoor and Indoor units complete with duly powder coated. The system shall be capable to operate automatically back to normal state after power shutdown and power restoration. Make : CARRIER /Toshiba /Mitsubishi Heavy AIR COOLED VRF OUTDOOR UNITS
GF + FF+SF TF+FF(40 HP)
EVAPORATIVE VRF INDOOR UNITS Supply, Installation, Testing and Commissioning of variable refrigerant flow modular type indoor units comprising of all accessories as per the specifications. The indoor units shall be suitable to work on cooling as well as heating mode. The indoor units shall be suitable for operation on 220±6% /415±6% volts, 50Hz, 1/3 phase AC power supply. Ductable indoor units shall be suitable to handle extent of ductwork as shown in the design drawings and and the indoor units shall be of following capacities: Make : CARRIER /Toshiba /Mitsubishi Heavy .
Hi Wall Units 2.0 HP
Hi Wall Units 1.25 HP
Supply installation , testing commissioning of INSULATED REF JOINTS / Y-JOINTS, CONTROL BOX, SPLITTERS, PIPE FITTINGS, headers, ACCESSORIES ETC. for all the above VRF IDU/ODU units. complete with all accessories
Corded/Cordless Remote for Indoor units as required
CENTRAL CONTROLLER With PC Monitoring Systems - Centralised Control Compliant Manager/ Smart Manager including all Hardware/Software system, USB Adaptors, Telephone Line connectivity, Allied cabling between centralized control system with Outdoor/Indoor units and other allied accessories , etc complete job. System should have facilities for start, stop,temperature setting,fan speed control,mode control,Group control,emergency start & stop, and fault Diagnosis. Make : CARRIER /Toshiba /Mitsubishi Heavy .
REFRIGERANT PIPING , Supply, Installation, Testing & Commissioning of high pressure copper refrigerant piping suitable for R 410a refrigerant of suitable size as required and duly insulated with 19mm/13mm thick closed cell elastomeric insulation in tubing form. External Refrigerant piping shall be laid on GI cable trays. Refrigerent pipes on terrace or platform shall be installed on raised GI Cable tray and finally covered with GI Sheet Cover for protection. Entire refrigerant piping work be carried out in accordance with the specifications. Piping shall be of following sizes :
6.35 mm dia with 13mm thick nitrile rubber insulation
9.53 mm dia with 13mm thick nitrile rubber insulation
12.7 mm dia with 13mm thick nitrile rubber insulation
15.8 mm dia with 13mm thick nitrile rubber insulation
19.0 mm dia with 13mm thick nitrile rubber insulation
22.2 mm dia with 19mm thick nitrile rubber insulation
28.6 mm dia with 19mm thick nitrile rubber insulation
31.8 mm dia with 19mm thick nitrile rubber insulation
38.0 mm dia with 19mm thick nitrile rubber insulation
PVC DRAIN PIPING Supply, installation, testing and commissioning of rigid PVC piping complete with fittings, supports as per specifications and duly insulated to the nearest drain point marked.
40 mm dia
32 mm dia
25 mm dia
GI CABLE TRAY Supply and installation of lader type GI 'U' shaped channel cable tray of following sizes. 40 x 300 x 40 x 2 mm
Supply, installation, testing and commissioning of control cum transmission wiring of 2 core x 1.5 sqmm copper cable between indoor and out door unit including conduit pipes
Supply, installation, testing and commissioning of control cum transmission wiring of 2 core x 4 sqmm copper cable between Control Panel and Outdoor/Indoor units including conduit pipes
Supply, fabrication and Installation of MS base frame/Stand for Outdoor Units duly painted. ODU Stand
Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. Electrical switch panel having all necessary accessories & safety devices of standard specifications. (Panels with sump pumps near terrace fire pump . 900 lpm at 35 m Head
Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required.
150 mm. Dia
Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required Note: Pipe upto 50 mm dia shall be threaded joints, with Ductile iron fitting above 50 mm shall be welded joints As per NBC 2016 & IS Code 15105
80 mm dia
100 mm dia
150 mm dia
Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal / Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal / Stainless Steel cap and chain as required :
Single headed Gunmetal
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze / gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
80 mm dia
100 mm dia
150 mm dia
Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze / gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required : for pump room
80 mm dia.
100 mm dia.
150mm dia.
Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc. as required.
150mm dia
Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange.
150mm dia
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (Type-A) as required :
Gun Metal
Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) Type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 40 m
Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :
4 way - 150 mm dia M.S. Pipe
Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required.
Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.
Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required.
150mm dia
Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required (E&M)
Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked indicating the BIS License No. with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank (Sintex, Electroplast, star, Lotous or equivalent having valid ISI license) (5000 ltr. Capacity 2 No.). MAKE (PRAYAG)
Providing and fixing of 1 no of Shovel and 1 No/ of Beater and Mild Steel Fire Sand Bucket, Capacity 5 Kg thickness not less than 6mm painted in Red with "Fire" written in Black Pasint (Refer IS: 2546-1974) mounted on MS painted structure to carry/ hold 4 fire buckets made out of Angle 40mm
Providing and fixing standard fire man's axe with heavy insulated rubber handle conforming to IS: 926 complete.
Supplying, Installation, Testing and Commissioning of Cubical Type Outdoor LT Panel Board Suitable for 415 V3 Phase 4 Wire 50HZ AC supply system including Incomers, Out Goings, Bus bars etc. As required as per the following Description.(IP:55) (Terrace Panel). The successful tenderer shall take prior approval for thepanel builder/ fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel. Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating. The Panel builder Shall be CPRI/ERDA/ANY NABL ACCREDITED LAB approved Refer SLD
INCOMER
FF /P M.C.B 63 A 10 KA "D" CURVE
OUTSOINGS
MPCB 19-25 A With STD magnetic Release
Power Contactor 40 A415 Volts, AC-3 Duty
Start/Stop Push Button
Size of wiring for CTS:- 2.5 sqmm
Size of wiring for voltage sensing Metering- 4.0 Sq.mm
Size of wiring of all Push buttons, indicating lamps :- 1.5 sq.mm
Types of wires :- PVC insulated 1100V grade, Multistrand copper conductor Flexible FR-LSH
Hinged door earthing:- Device mounted hinged doors connected to cubicles body by means of 2.5 sq.mm green copper flexible wire.
The Complete Panel Shall be Made out of 2.0 mm CRCA sheet including Frame/parttions/ Doors etc.
Gland Plates to be 3.0mm Thick.
Supplying and laying of one number PVC insulated and PVC Shealther / XLPE power cable of 1.1 kv grade of following size direct in ground in Existing DWC Pipe including excavation, sand cushioning, protective covering and refilling the trench etc as requied. (4.0 C X 25 sq.mm A2XFY)
Supplying and Making end Termination with Brass Compression Gland and Aluminium Lugs for the Following Sizes of PVC insulated and PVC Sheathed/ XLPE Aluminium Conductor Cable of 1.1 KV Grade as required (Comet) (4 x 25sq.mm (28mm)
Supplying and Installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended form the ceiling with G.I including G.I. bolts & nuts, etc. as required. (150mm width x 50mm x 1.6mm thickness)
Earthing with G.I earth plate 600mm x 600mm x 6mm thick including accessories, providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc with charcoal/ coke and salt as required.
Supplying and lating 25mm x 5mm G.I strip at 0.50 metre below ground as strip earth electrode, including connectin/ terminating with G.I nut, bolt, spring, washer etc. As required. ( Jointing shall be done by overlapping and with 2 sets of G.I nut bolt & spring washer spaced at 50mm)
Providing and fixing 25mm x 5mm G.I strip in 40mm dia G.I Pipe form earth electrode including connection with G.I nut, bolt, spring, washer excavation and re-filling etc. As required.
Providing and fixing Weather proof hose cabinets fabricated from 16g MS Sheet with full glass door and locking arrangement, suitable to accommodate one hydrant valve, 2 nos 15m long hose, 1 no branch pipe and one fireman's axe. The cabinet shall be painted with one coat of primer and finished stove enamelled "FIRE RED", "FIRE HOSE" written on front including suitabley mounted on a raised masonry platform as required. (Approx 0.75m x 0.6m x 0.25m).
Supplying and installing of in position the following type of sign boards made out of 3mm thick "Opaque" PVC foam board with computer cut, PVC Non-reflective self adhesive vinyle painted foam board, complete with mirror fasteners.
Signage with printed " IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE" OF 1.5 CM HEIGHT LETTERS IN RED WITH WHITE BACKGROUND. The size of the board shall be 25cm x 30 cm and shall be fixed at the height of 2 mts. From finished floor near manual call points.
Floor identification signage ( i.e GROUND FLOOR, ETC) at each stair enclosure on every floor, indicating the floor number in words, lettering size shall be 7.5 cm with contrasting color from background. Size shall be 15cm x 60cm
Fire exit signage at each stair on every fooor indicating the direction of fire exit, lettering size shall be 7.5cm with contrasting color form back ground. Size shall be 15cm x 60cm.
Providing & fixing of ISI marked (IS:15683) portable fire extinguisher, carbondioxide type flat base including valve, discharge hose of not less than 10 mm dia. 1 M long & complete in all respects including initial fill with CO2 gas confirming to IS:307-1966 filled to a filling ratio of not more than 0.667 of not more than 0.667 and wall suspension bracket
Capacity 4.5 kg
6 Kg. ABC Powder type fire extinguishers are manufactured and marked to Indian standard IS: 15683. Suitable first aid appliance for fighting fires in Class A, B & C fire that is wood, textile, flammable liquids & gases.
Providing and fixing carbon-di-oxide fire extingushers trolley mounted with all accessories internal discharge tube,high pressure discharge hose,discharge nozzle, ISI marked as per IS:2878 finished externally with red enamel paint.
Capacity 22.5 kg.
Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required.
Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required.
Supplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required.
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required
2 x 1.5 sq. mm
Supplying and Fixing of Following sizes of PVC Conduit along with Accessories in surface/Recess including painting in case of surface conduit,cutting the wall and making good the same in case of recessed conduit as required.
20 mm PVC Conduit
Supplying,Installation,Testing and Commissioning of CO2 Type Fire Extinguisher 4.5 Kg. Capacity ISI Mark (IS:15683)suitable for 'B' and 'C' class fires - inflammable liquids, gaseous fires like L.P.G. and acetylene, and electrical fires
Supplying,Installation,Testing and Commissioning of MAP 90 ABC Type Fire Extinguisher 4.0 Kg. Capacity ISI Mark (IS:15683)suitable for Class A/B/C Type Fires .
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.11 MB
BOQ_972828.xls
BOQ • 0.80 MB
Download all tender documents and submit your bid