Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.2 LAccepted-AOC 1 6 620 CHAITANYAPURI INDRA NAGAR DILSUKHNAGAR HYDERABAD TELANGANA 500060 UDYAM TS 09 0007870 37AAEPO0535A1Z8 B 36AAEPO0535A1ZA R MSME STATUS AS VERIFIED | RANGA REDDY | TELANGANA | 500060 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹10.9 L+₹63,511.52 (6.22%)Rejected-Finance H NO 3 1 197 P58 MYTINAGAR COLONY LB NAGAR HYDERABAD 500 074 | HYDERABAD | HYDERABAD | TELANGANA | 500074 | L2 | Rejected-Finance Not L1 | |
| 3 | L3₹11.1 L+₹88,967.52 (8.71%)Rejected-Finance NO 133 RASHTRAPATHI ROAD SECUNDERABAD 500 003 | SECUNDERABAD | HYDERABAD | TELANGANA | 500003 | L3 | Rejected-Finance Not L1 | |
| 4 | Rejected-Technical | - | Rejected-Technical due to not enlisted in category b(ii) |
Tender Value
₹9.9 L
EMD Value
₹20,000
Closing Date
20 May 2022, 6:00 pmClosed
CWE No 2 Secunderabad
CWE No 2 Secunderabad, Mudfort, MES Complex, Secunderabad-03
PROVISION OF TRANSFORMER, MAIN PANEL FOR SWIMMING POOL AT ARTY CENTRE UNDER GE GOLCONDA
2022_MES_519404_1
81099/E8
Open Tender
Civil Works
Item Rate
180 days
GOLCONDA
As per Tender Documents
7 documents required · 7 mandatory
₹500
GE Golconda Hyderabad
₹20,000
Yes
20 Jun 2022
22 Apr 2022
27 May 2022
22 Apr 2022
20 May 2022
6 May 2022
Amount
Supply, laying, connecting and testing XLPE insulated (Earthed) cable laid in trenches/or fixed on pole etc in screened PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 11000 Volt grade, cross sectional area 95 Sqmm, 3 Core Conforming to IS-7098 (Part-II)-1985 Complete all as specified and as directed. (Note: Excavation & earth work will be measured and paid separately under relevant items. )
Supply and Fixing of cable jointing kit for 11 KV (Earthed) grade cable for outdoor end termination heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specifide and as directed.
Supply and fixing triple pole mechanically operated air break isolator (GOD), Horizontal mounting, rotating type, mounted on insulator and steel frame with operating mechanism worked from one meter above ground level complete in all respect such as gun metal moving contacts and spring loaded gun metal fixed jaws, knife copper jumper strip etc, suitable for 11000 Volts grade, 50 Hz, with 9 insulator of rating upto 200 Amps complete all as specified and as directed.
Supply, installation, Testing and commissioning of double wound copper step down Transformer of capacity of 125 KVA, outdoor type complete with standard fittings, primary voltage of HT 11000 Volts and secondary LT 433 volts, 3 Phase 4 wire with frequency 50 c/s. Provided with suitable No of off load tappings on HT side to vary secondary voltage within range of +5% to - 10% (in steps of 2.5%), star delta connections with vector group of Dyn 11, Impedance of 4.5% and including first filling of transformer oil as per IS:335 and colour coating with one coat of primer and two coats of BS grey colour. Losses all as per IS:1180 (Level - i) with all standard accessiories required proper functioning of Transformer including RR masonry pedestal of size 1.80x1.50x1.20Mtr (1.00 above GL and 0.20 m below GL) over PCC 1:2:4 foundation of 100 mm thick (above GL) and 75 mm thick PCC 1:2:4 coping all as specified and as directed and the following: -
(a) Rating and Terminal marking plate- one (b) Earthing Terminal- Two (c) Lifting Lugs- Two (d) Drain valve with Blanking plate - One (e) Filter Valve with blanking plate- One (f) Conservator-One (g) Oil Level indicator with minimum marking (h) Dyhydrating breather-One (j) Air Release devise - One (k) Thermometer Pocket-One (l) Pressure relief valve - One (m) Roller unidirectional-Four (n) Both side (HV and LV) cable Box (o) Separate Brought out Neutral Terminal (p) Off Circuit Tap Changer (q) 100 MM dia stem type Thermometer Make: Essenor/HIT/ABB/Schneider/BHEL Note: Commissioning of the transformer to be done in the presence of SEI / EI as detailed . Contractor should intimate one month in advance for commissioning of the same. All necessary arrangement for testing to be done by the contractor. Rates for the same are deemed to be included in the quoted rate.
Supply , lay and testing in trenches/ fixed to walls/ poles etc., testing and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor complete of size 3.5 Core, 95 Sqmm complete all as specified and as directed.
Supply , lay and testing in trenches/ fixed to walls/ poles etc., testing and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor complete of size 4.0 Core 16 Sqmm complete all as specified and as directed.
Supply , lay and testing in trenches/ fixed to walls/ poles etc., testing and commissioning XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor complete of size 2.0 Core 10 Sqmm complete all as specified and as directed.
Supply & Fix MCCB Load line Distirbuiton board 415 Volts, 4 pole, 6 Way, suitable for 250 Amps incomer MCCB complete all as specified and as directed.
Supply & Fix MCCB 415 Volts, 4 pole, adjustable thermal type, 200 Amps, with breaking capacity 26 KA complete all as specified and as directed.
S&F MCB Four Pole , 50 Amp, 415 Volts AC complete all as specified and as directed.
S&F MCB Four Pole , 0-32A Amp, 415 Volts AC complete all as specified and as directed.
Excavation in trenches not exceeding 1.50 m wide and n.exc 1.5 m in depth for foundation of poles, cable etc, not exc 10 sqm on plan and getting out in hard/dense soil complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25cm thick complete all as specified and as directed.
Removing excavated materials (soils) not exc. 50m and depositing where directed at a level not exc. 1.5m above the starting point complete all as specified and as directed.
Supply and spread sand in trenches as sand cushioning to under ground cable for protection with M Sand/Robo Sand and provide required cover after punning down complete all as specified and as directed.(Note: Only Punned thickness after punning will be measured and paid)
Supplying and laying reinforced precast concrete cable cover class HV, Type 1 flat of size 300x180x40 mm all as specified and as directed.
M&L brick protection with common burnt bricks sub class ‘B’ of size 230 x 115 x 75mm for cable protection complete all as specified and as directed.
Supply and Fix 80mm dia galvanised steel tubes 'light grade', with all fitting and fixtures complete to walls and ceilings or laid in floors all as specified and as directed.
Supply and Fix 40mm dia galvanised steel tubes 'light grade', with all fitting and fixtures ed complete to walls and ceilings or laid in floors all as specified and as directed.
M & L for cutting of road, hard standing made of concrete or premix carpet, WBM, soiling and morrum filling including excavation for laying of cable/pipe all as directed and making good the road/hard standing by using all old/new materials and with 100 mm thick PCC (1:2:4) etc, required to match with the existing surface complete all as specified and as directed.
M&L for earthing with galvanized mild steel earth plate electrode 60 centimetre x 60 centimetre x 6.3 mm thick buried directly in ground vertically to a depth not less than 2.25 metres below ground level, the top edge of the earth plate at a depth of not less than 1.5 metres below ground level connected to galvanized steel strip of 32 x6 mm size by means of bolts, nuts and washers made out of GI / steel earth wire protected by GI light grade pipe 40 mm bore, 20mm dia medium grade galvanised iron watering pipe perforated at bottom 1.75m long with funnel and wire mesh, common salt and charcoal filling complete and connecting to main switch board / control board all s shown in electrical plate of SSR Part - I connected to earthing test point and including testing on completion complete all as specified and as directed. NOTE: The unit rate shall also include for excavation, earth work in hard/dense soil, plain cement concrete 1:2:4 type C1 by using 20 mm graded aggregate in pit, 75 mm thick reinforced cement concrete 1:2:4 type B1 using 20 mm graded aggregate cover duly reinforced with 6 mm dia TMT bars @ 75mm centre to centre both ways with 12mm dia MS bar handle made to shape, GI pipe & GI earth lead 7mm dia upto 7.50m length, wire mesh, salt, charcoal complete.
M&L for earthing with galvanized mild steel earth plate electrode 60 centimetre x 60 centimetre x 6.3 mm thick buried directly in ground vertically to a depth not less than 2.25 metres below ground level, the top edge of the earth plate at a depth of not less than 1.5 metres below ground level connected to galvanized iron earth wire of 4 mm dia by means of bolts, nuts and washers made out of GI / steel earth wire protected by GI light grade pipe 15 mm bore, 20mm dia medium grade galvanised iron watering pipe perforated at bottom 1.75m long with funnel and wire mesh, common salt and charcoal filling complete and connecting to main switch board / control board all s shown in electrical plate of SSR Part - I connected to earthing test point and including testing on completion complete all as specified and as directed. NOTE: The unit rate shall also include for excavation, earth work in hard/dense soil, plain cement concrete 1:2:4 type C1 by using 20 mm graded aggregate in pit, 75 mm thick reinforced cement concrete 1:2:4 type B1 using 20 mm graded aggregate cover duly reinforced with 6 mm dia TMT bars @ 75mm centre to centre both ways with 12mm dia MS bar handle made to shape, GI pipe & GI earth lead 7mm dia upto 7.50m length, wire mesh, salt, charcoal complete.
veerender constructions
THE DECAN ENGINEERING AND REFRIGERATION COMPANY
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .