Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.9 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹15.5 L+₹2.7 L (20.9%)Rejected-AOC | L2 | Rejected-AOC Other then Lowest bidder |
Tender Value
₹9.6 L
EMD Value
₹19,300
Closing Date
6 Dec 2022, 6:00 pmClosed
COL S PRADEEP
Military Engineer Services, HQ Commander Works Engineer Jammu, PIN-900172
PROVN OF 250 KVA TRANSFORMER AT POONCH LINES AT DAMANA UNDER GE JAMMU
2022_MES_562442_1
CWE/JP-13/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE JAMMU
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE JAMMU
₹19,300
Yes
3 Aug 2023
10 Nov 2022
8 Dec 2022
10 Nov 2022
6 Dec 2022
24 Nov 2022
Amount
Supply, installation, testing and commissioning transformer step down outdoor type copper wound , oil cooled IP-43 plinth mounted powder coated capacity 250 KVA CL-I with latest feature complete with standard fitted HT 11 KV 3 Phase LT 433 V 3 phase 4 wire, 50 C/S oil immersed naturally cooled externally cooling tube delta connection on primary HT 11 KV side and star connection on secondary LT 433 V with tapping at +/- 2.5% to +/- 5% & +/- 7.5% on HV side and to be charged by means of hand operated off load/lap changing gear including first filling of new transformer oil of dielectric strength not less than 60 KV with all fiiting and accessories such as LT box at LT side,silica gel,brather, oil level indicator, conservator tank with oil level indicator,drain out valve (oil tank), exhaust vent,air release valve, temp gauge and cast iron wheel etc complete level-2 as per IS-1180(Part-1):2014, complete all as specified and directed.
XLPE insulated, screened, PVC bedded,galvanised steel strip or wire armoured, electric power cables (heavyduty) withaluminium conductor, 11000 volts, grade cross sectional area 95 sq. mm 3core complete all as specified and directed.
Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm to 120 sqmm complete all as specified and directed.
Construction of Plateform for installation of transformer with and including Earth work, Brick work, PCC, RCC, Plastering, chain link fencing, gate etc all as shown in Drawing No CWE/TD-230/2021 Sheet 1/1 dated 23 Jun 2021, complete all as specified and directed.
XLPE cable insulated screened PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 11 KV grade with stranded aluminium coductor of size 300 Sqmm 3.5 core and including suitable size of lugs all as directed by Engr-in-Charge.
XLPE cable insulated screened PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 11 KV grade with stranded aluminium coductor of size 120 Sqmm 3.5 core and including suitable size of lugs all as directed by Engr-in-Charge.
XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 Sq mm, 4 core, complete all as specified and directed by Engr-in-Charge.
XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 Sq mm, 3.5 core, complete all as specified and directed by Engr-in-Charge.
Material & Labour in replacement of ACSR conductor any size/any type drawn on fixed to insulator on the pole complete as with permissible sags for OH Conductor all as specified and directed.
Material & Labour in replacement of Cross arms bracing support clamps, back plate etc fabricated from structural steel section with bolts, nuts, washers,welding, bending cold or hot,drilling holes for bolts in any shape and size as directed or indicated and painted with one coat of red oxide primer and two coats of Silver paints, complete all as sepecified dirceted by engr-in-charge.
Pin type, porcelain, vitreous, white,brown or green insulator including one galvanised mild steel spindle,two galvanised iron washers and one galvanised iron nut, 100 mm height, 65 mm dia for 1100 volts grade, complete all as sepecified dirceted by engr-in-charge.
Earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to galvanized iron strip 25 x 4 mm size by mean of nut/bolt and washer of galvanized iron or steel as shown in electrical plate No 5 including 40 mm bore GI tubing for protection of earth strip upto test point of SSR part I including necessary excavation and earth work GI pipe 20mm bore light grade for watering and GI 15mm bore light grade pipe for protection of GI earth wire etc, PCC chamber with RCC cover in cement concrete 1:2:4 Type B1(20mm graded stone aggregate), funnel, wire mesh, charcoal dust, salt layers each layer thickness should be 15 cm (layer start from below the electrode plate to above plate) etc, connected to LT panel board as indicated including testing complete all as specified and as directed.
Earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to galvanized iron wire 4 mm dia by mean of nut/bolt and washer of galvanized iron or steel as shown in electrical plate No 5 including 20 mm bore GI tubing for protection of earth wire upto test point of SSR part I including necessary excavation and earth work GI pipe 20mm bore light grade for watering and GI 15mm bore light grade pipe for protection of GI earth wire etc, PCC chamber with RCC cover in cement concrete 1:2:4 Type B1(20mm graded stone aggregate), funnel, wire mesh, charcoal dust, salt layers each layer thickness should be 15 cm (layer start from below the electrode plate to above plate) etc, connected to LT panel board as indicated including testing, complete all as specified and as directed.
Replacement of lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp suitable for 11 KV all as specified and directed.
Replacement of switch air break gang operated triple pole mechanically operated from ground level, mounted on insulators and steel frame (12 insulator type) outdoor type suitable for vertical installation single break provided with locking arrangement consisting of MS channel, HT post top insulator with drop out fuses operating rod 25mm bore GI pipe medium grade confirming to relevant IS, current rating 200 Amp and voltage 11 KV including jumpering, lead of wire/cable as directed at site including taking down old/ unserviceable switch, complete all as specified and as directed.
Anti climbing device, spikes type, fabricated out of MS bars (round, square or flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the poles, spike welded to flat iron, including on primer coat, one under coat and two finishing coats of silver aluminium paint including preparation of surfaces, complete all as specified and as directed by Engr-In-Charge
Danger notice plate of 1.6mm thick MS sheet vitreous enamelled white with letters, figures and conventional skull and bones in signal Red colour and inclusive fixed with MS flat clamps 25x3mm 2 Nos, nuts, bolts for HT 11000 Volt of size 25x20cm, complete all as specified and as directed by Engr-In-Charge
Excavation in trenches not exc. 1.5 m wide and not exc. 1.5 m depth for foundation laying of cable etc or for shaft wells cesspits manholes per holes etc 10sqmm on plan and n.exe 1.5m in depth and getting out in any type of soil, complete all as sepecified & dirceted by EIC.
Sand cushioning to underground cables provided with a layer of sand 8cm thick before laying the cable in trenches and 15cm thick after laying the cable in trenches complete all as specified. Note:- 1. Dry fine sand of best available quality shall be used. 2. Punned thickness shall be made and paid.
Supply and laying well burnt old size sub class 'B' bricks laid flat with width equal to length of brick perpendicular to the direction of cable, adjacent/abutting each other complete all as specified and as sirected by Engineer-in-charge in trenches over the cable for protection.
Returning filling in, including spreading, leveling, watering and well ramming in layers not exc 25m thick all as specified and directed.
Removing excavated material from site to a distance not exc 50 metre away and depositing where directed not exc 1.5mtr from the starting point all as directed.
GI Pipe light grade 50 mm bore incl all accessories for cables protection/Mechanical protection, laid under plinth/floors/path culverts with complete accessories such as bends/sockets/reducers/saddles incl necessary threading/drilling works, complete all as specified and directed
Supply, installation, testing and commissioning LT panel powder coated vermin and weather proof of suitable size for 3 Phase 415 volt , outdoor double door type made out 3.15 mm thick CRCA sheet with angle iron frame of size 50x50 x6 mm cubical type front and back door operated complete with aluminium bus bar 600 Amp 4 way fitted on DMC insulation with color coding and internal panel with suitable size copper cable FRLS powder coated , with IP 54 as per IS 13947 protection, fault rating 50 KA/1Sec, complete and including with following items:-
MCCB 4 Pole, current rating 630 Amp, with adjustable thermal magnetic setting 70%-100% breaking capacity 36KA at 415V,50Hz, - 01 No as incomer
MCCB 4 Pole, current rating 200 Amp, with adjustable thermal magnetic setting 70%-100% breaking capacity 25KA at 415V,50Hz, - 01 No as outgoing
MCCB 4 Pole, current rating 160 Amp, with adjustable thermal magnetic setting 70%-100% breaking capacity 25KA at 415V,50Hz, - 01 No as outgoing
MCCB 4 Pole, current rating 100 Amp, with adjustable thermal magnetic setting 70%-100% breaking capacity 25KA at 415V,50Hz, - 02 Nos as outgoing
MCCB 4 Pole, current rating 63 Amp, with adjustable thermal magnetic setting 70%-100% breaking capacity 16KA at 415V,50Hz, - 02 Nos as outgoing
LED indicating Lamp-01 Set
M/S SHREE KRISHANA ENERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .