Tender Value
₹49.9 L
EMD Value
₹99,800
Closing Date
3 Aug 2022, 6:00 pmClosed
Garrison Engineer North Ahmednagar
Military Engineer Services Garrison Engineers (North) Nagar Pathardi Road Ahmednagar Fort Ahmednagar 414 002
Repairs / Maintenance of central / Package type AC Plants Cold storage No 1 and 2 at MH and repairing of ducting at various places and certain EM Works under GE (N) Ahmednagar
2022_MES_536496_1
8659 / E8
Open Tender
Miscellaneous Works
Item Rate
270 days
Ahmednagar
Class D Cat c(i)
8 documents required · 8 mandatory
₹500
Yes
Garrison Engineer North Ahmednagar
₹99,800
Yes
22 Aug 2022
8 Jul 2022
5 Aug 2022
8 Jul 2022
3 Aug 2022
22 Jul 2022
Amount
Material and labour for replacement of the following unserviceable parts / accessories of LT Panel board for compressor of central AC plant of capacity 25 TR including connecting testing tc complete all as specified and directed by Engineer-in-Charge
(a) Power contractor ML-2, 32 Amps, 415 Volts, 50 Hz, TP for compressor motor MAKE: L & T Cat No-SS90701 or equivalent makes mentioned in list of makes in Appendix `C' / approved by GE
(b) Over load relay, 20 to 32 Amps capacity, 415 Volts, 50 Hz Makes : SIEMENS Cat No:-SS94136OOEO or equivalent makes mentioned in list of makes in Appendix `C' / approved by GE.
(c) Operating coil, 230 Volts, 50 Hz Makes : SIEMENS Cat No-CS96384 or equivalent makes mentioned in list of makes in Appendix `C' / approved by GE.
(d) Switch fuse unit, TP, 63 Amps, 500 Volts, FN type with handle
(e) PVC moulded / backelite cut out with base, 63 Amps, 500 Volts etc complete all as specified and direted by Engineer-n-Charge. Male: Legrand / Hager/ Siemens
(f) MCCB, 200 Amps, TPN, 50 Hz, 500 Volts, 25 KA rupturing capacity 2022_MES_528914 etc complete all as specified and direted by Engineer-n-Charge.
(g) MCB, TPN, 32 Amps, 50 Hz, 500 Volts
(h) MCCB 100 Amps TP 50 Hz 500 Volts 25 KA
Material and labour for replacement of the following unserviceable parts / accessories of LT panel board of AHU motors and water circulating pumps for AC plant of capacity 25 TR including connecting testing etc complete all as specified and directed by Engineer-in-Charge
(a) Power contactor, 32 Amps (type 3 TA 21-11 A) TP for AHU motor MAKE: L & T Cat No-CS96552 or equivalent in L&T / Hager or equivalent makes mentioned in list of makes in Appendix `C'
(b) Over load relay, 10 to 16 Amps, 415 Volts, 50 Hz MAKE: SIEMENS Cat No-SS94135OOBO or equivalent in L&T / Hager or equivalent makes mentioned in list of makes in Appendix `C'
(c) Operating coil, 230 Volts, 50 Hz MAKE: Siemens Cat No-CS96384 or equivalent as approved by GE
(d) Switch fuse unit, TPN, 30 Amps fixed in and including sheet metal enclosure made out of 1.6 mm thick CRCA sheet Make : Legrand / Hager / Siemens or equivalent as approved by GE
Taking out unserviceable tefflon gasket of discharge and suction valves of AC plant of capacity 25 TR and replacing the same with new tefflon gasket etc complete all as specified and direted by Engineer-n-Charge.
Taking out old unserviceable pressure cut off cut out and replacing the same with new pressure cut out of any type, model, size required and testing for gas leakage etc complete all as specified and directed by Engineer-in-Charge
Material and labour for servicing compressor motor 30 HP, 3 Phase, 415 Volts 50 Hz by cleaning and greasing, Rewinding,tightening of all loosened parts etc complete all as specified and directed by Engineer-in-Charge
All as per item No 17 (here-in-before) but for motor of capacity 7.5 HP, 3 Phase, 415 Volts, 50 Hz of circulating pumps
Material and labour for overhauling of pump of 7.5 HP monoblock pump set including replacement of gland packing, gun metal bush bearing and water seal / gland packing ,rusted unserviceable bolts nuts, etc and testing etc complete all as specified and direted by Engineer-n-Charge.
All as per Sl item No 19 (here-in-before) but for 30 HP capacity.
Overhauling & Vaccumising of complete system of central AC plant capacity 25 TR with vaccum pump, descanning the refrigerent in suitable container with suitable precautions, isolating the reciprocating compressor by removing nuts and blocking plates of suction and discharge valves, opening compressor, removing the crankshaft & checking it , grinding of the crankshaft & for suitable size of bearing , replacement of unserviceable / damaged internal parts reassembling complete and leakage testing with and including nirogen gas arresting the leakage , charging compressor oil and refrigerent gas (R-22), reassembaling the complete system testing and commissioning of the compressor to the entire satisfaction of Engineer-in-Charge. NOTES: (i) Replacement of materials shall be measured and paid as supply only parts under the relevent items. (ii) Compressor oil and refrigerant gas will be measured and paid under the relevent items. (iii) Machining work as required deemed to be included in the unit rate quoted.
Supply only the following parts of central air conditioning palnt of 25 TR capacity Make : Kirloskar, Model - AC 470 or equivalent as approved by GE
(a) Gasket set
(b) Shaft seal assembly
(c) `O' Ring set
(d) Oil filter
(e) Main bush bearing
(f) Suction reeds
(g) oil pressure regulator
(h) Discharge reeds
(i) brass nozzel 3/4 inchs as per existing
(j) oil pressure cut out make:danfos
(k) pressure gauge (low / high / o )
(l) liquid indicator
(m) solonaid valve
(n) anti vibrational mountings
(0) Oil Pump
(p) Piston Ring
(q) Connecting Bearing
(r) compressor oil Make : CASTROL or equivalent as approved by GE
Descaling of condensor of 25 TR capacity central type AC plant by mechanical and chemical method till removal of scales completely including replacement of gasket and worn out nuts bolts etc complete all as specified and direted by Engineer-n-Charge.
Overhauling the cooling tower by scraping out algae scale formed or material deposited in bottom tank on fins nozzles etc by mechanical and chemical method complete including supply and fix M-Seal at leakage point etc complete all as specified and directed by Engineer-in-Charge
Overhauling the cooling tower by scraping out algae scale formed or material deposited in bottom tank on fins nozzles etc by mechanical and chemical method complete including supply and fix Metal sheet frame at the bottom of chiller plant with out any leakages point etc complete all as specified and direted by Engineer-n-Charge.
Supply & Charge F-22 gas to AC plant upto required pressure etc complete all as specified and directed by Engineer-in-Charge
Overhauling & Vaccumising of complete system of Package AC plant of capacity 3/5 TR with pump, descanning the refrigerent in suitable container with suitable precautions, replacement of unserviceable / damaged internal parts, leakage testing with and including nirogen gas arresting the leakages , charging compressor oil and refrigerent gas (R-22), reassembaling the complete system testing and commissioning of the compressor to the entire satisfaction of Engineer-in-Charge. NOTES: (i) Replacement of materials shall be measured and paid as supply only parts under the relevent items. (ii) Compressor oil and refrigerant gas will be measured and paid under the relevent items. (iii) Machining work as required deemed to be included in the unit rate quoted.
Supply only the following unserviceable accessories of complete package type AC plant of capacity 3 TR / 5 TR including connecting testing complete all as directed:-
(a) anti vibrational mountings
(b) brass pressure valve 1/2 inches
(c) gas filter 1/2 inches
(d) filter trier
(e) out door unit condencing coil
(f) out door unit condencing motor 1.5 HP 3 phase 415 Volts Cat No-1SEOO90-2NB70
(g) out door unit condencing motor's fan blade
(g) MCB, TPN, 32 Amps, 50 Hz, 500 Volts
(j) copper tubes 5/8' 1/2' as per existing
(k) solonaid valve
(l) Cooling coil
(m) Fan motor belt as per existing
(n) 4 core 4 sq mm cable MAKE : Polycab / Achor / Indoplus
(o) compressor heater
Material and labour for replacement of the following unserviceable parts / accessories of LT Panel board for compressor of PACKAGE AC plant of capacity 3/5 TR including connecting testing complete all as directed:-
(a) Switch fuse unit, TP, 63 Amps, 500 Volts, FN type with handle MAKE: Legrand / Hager / Siemens or equivalent as approved by GE
(b) PVC moulded / backelite cut out with base, 32 Amps, 500 Volts
(c) MCCB, 200 Amps, TPN, 50 Hz, 500 Volts, 25 KA rupturing capacity
(d) MCB, TPN, 32 Amps, 50 Hz, 500 Volts
(e) Power contactor, 32 Amps (type 3 TA 21-11 A) TP MAKE: Siemens / L&T Cat No-CS96552 or equivalent makes mentioned in list of makes in Appendix `C' / approved by GE.
(f) Over load relay, 10 to 16 Amps, 415 Volts, 50 Hz
(g) Timer switch,230 Volts, 50 Hz Siemens CAT NO-SS91270
(h) Operating coil, 230 Volts, 50 Hz
(j) Singal phase preventor 230 Volts, 50 Hz
Disconnecting Unserviceable compressor capacity 5.5 TR from existing electric and pipe line connections of any make, transporting and replacing the same with factory / company made reconditioned compressor including connecting suction and discharge lines by copper brazing, pressure testing with the help of nitrogen gas and flushing out the oil in condensor cooling coil and gas charging all as directed:- Make : Blue star NOTES: 1) The make of the compressor to be replaced shall be same as that of the existing make in the cooling appliance. 2) Gas charging will be measured and paid separately under the relevent item
Material and labour for cleaning with blower of air filters and micro filters, condensor coil / cooling coil and servicing of blower motor with oil grease etc of 3 to 11 TR capacity package AC plants washing of air filters with liquid soap and high pressure water till all dirt is removed etc complete all as specified and directed by Engineer-in-Charge.
M&L for taking out blower motor of 3 to 8.75 TR package type AC plant, transporting to work shop,opening the motor, taking out burnt winding, preparing motor for winding and rewidning of motor with same guage superior enamelled copper wire, replacement of bearings if required, assembling and transporting back, installing on foundation connecting and testing etc complete all as specified and directed by Engineer-in-Charge
Material and labour for leak testing of package AC 3/8.75 TR capacity by using nitogen gas if required repairing to leakage as required by copper brazing etc and testing for pressure drop for 24 hrs etc complete all as specified and directed by Engineer-in-Charge
Disconnecting unserviceable compressor capacity 8.75 TR from existing electric and pipe line connections of any make, transporting and replacing the same with factory / company made reconditioned compressor including connecting suction and discharge lines by copper brazing, pressure testing with the help of nitrogen gas and flushing out the oil in condensor cooling coil and gas charging all as directed:- Make : Blue star NOTES: 1) The make of the compressor to be replaced shall be same as that of the existing make in the cooling appliance. 2) Gas charging will be measured and paid separately under the relevent item
Overhauling & Vaccumising of complete system of Package AC plant of capacity 8.75 TR with pump, descanning the refrigerent in suitable container with suitable precautions, replacement of unserviceable / damaged internal parts, leakage testing with and including nirogen gas arresting the leakages , charging compressor oil and refrigerent gas (R-22), reassembaling the complete system testing and commissioning of the compressor to the entire satisfaction of Engineer-in-Charge. NOTES: (i) Replacement of materials shall be measured and paid as supply only parts under the relevent items. (ii) Compressor oil and refrigerant gas will be measured and paid under the relevent items. (iii) Machining work as required deemed to be included in the unit rate quoted.
Supply only for replacement of the following unserviceable accessories of complete package type AC plant of capacity 8.75 TR including connecting testing etc complete all as specified and direted by Engineer-n-Charge.
(a) PCB with digital display 230 Volts, 50 Hz
(b) brass pressure valve 1/2 inches
(c) gas filter 1/2 inches
(d) filter trier
(e) out door unit condencing coil
(f) out door unit condencing motor 2 HP 3 phase 415 Volts CAT NO- 1SE00902NB70 or equivalent as approved by GE.
(g) out door unit condencing motor's fan blade
(h) MCB, TPN, 32 Amps, 50 Hz, 500 Volts
(j) copper tubes 5/8' 1/2' as per existing
(k) solonoid valve
(l) Cooling coil
(m) fan motor belt as per existing
(n) 4 core 4 sq mm cable
(o) compressor heater
(p) anti vibrational mountings
Material and labour for replacement of the following unserviceable parts / accessories of LT Panel board for compressor of PACKAGE AC plant of capacity 8.75 TR including connecting testing complete all as directed:-
(a) Switch fuse unit, TP, 63 Amps, 500 Volts, FN type with handle
(b) PVC moulded / backelite cut out with base, 32 Amps, 500 Volts
(c) MCCB, 200 Amps, TPN, 50 Hz, 500 Volts, 25 KA rupturing capacity
(d) MCB, TPN, 32 Amps, 50 Hz, 500 Volts
(e) Power contactor, 32 Amps (type 3 TA 21-11 A) TP Make: L&T Cat No-CS96552 or equivalent as approved by GE.
(b) Over load relay, 10 to 16 Amps, 415 Volts, 50 Hz
(g ) Timer switch,230 Volts, 50 Hz
(h) Operating coil, 230 Volts, 50 Hz
(j) Singal phase preventor 230 Volts, 50 Hz
(k) Rotary switch
Overhauling & Vaccumising of complete system of Package AC plant of capacity 11 TR with pump, descanning the refrigerent in suitable container with suitable precautions, replacement of unserviceable / damaged internal parts, leakage testing with and including nirogen gas arresting the leakages , charging compressor oil and refrigerent gas (R-22), reassembaling the complete system testing and commissioning of the compressor to the entire satisfaction of Engineer-in-Charge. NOTES: (i) Replacement of materials shall be measured and paid as supply only parts under the relevent items. (ii) Compressor oil and refrigerant gas will be measured and paid under the relevent items. (iii) Machining work as required deemed to be included in the unit rate quoted.
Supply only for replacement of the following unserviceable accessories of complete package type AC plant of capacity 11(5.5x2) TR including connecting testing etc complete all as directed as specified and directed by Engineer-in-charge
(a) PCB with digital display 230 Volts, 50 Hz
(b) brass pressure valve 1/2 inches
(c) gas filter 1/2 inches
(d) filter trier
(e) out door unit condencing coil
(f) out door unit condencing motor 2 HP 3 phase 415 Volts
(g) out door unit condencing motor's fan blade
(h) MCB, TPN, 32 Amps, 50 Hz, 500 Volts
(j) copper tubes 5/8' 1/2' as per existing
(k) solonoid valve
(l) Cooling coil
(m) fan motor belt as per existing
(n) 4 core 4 Sqmm cable
(o) compressor heater
(p) anti vibrational mountings
Material and labour for replacement of the following unserviceable parts / accessories of LT Panel board for compressor of PACKAGE AC plant of capacity 11 TR including connecting testing complete all as directed:-
(a) Switch fuse unit, TP, 63 Amps, 500 Volts, FN type with handle
(b) PVC moulded / backelite cut out with base, 32 Amps, 500 Volts
(c) MCCB, 200 Amps, TPN, 50 Hz, 500 Volts, 25 KA rupturing capacity
(d) MCB, TPN, 32 Amps, 50 Hz, 500 Volts
(e) Rotary switch
(f) Power contactor, 32 Amps (type 3 TA 21-11 A) TP Make : L&T Cat No-CS96552 or equivalent as approved byGE
(g) Over load relay, 10 to 16 Amps, 415 Volts, 50 Hz
(h) Timer switch,230 Volts, 50 Hz
(j) Operating coil, 230 Volts, 50 Hz
(k) Singal phase preventor 230 Volts, 50 Hz
supply & fix ball bearing DE/NDE for 30 HP coupled pump
supply & fix ball bearing DE/NDE for 7.5 HP coupled pump
Repair of voltage stabilizer for automatic opration single phase naturally air cooled indoor type and desinged for input variation b/t 170 v to 280 v with output voltage stabilized at 230 v with accuracy of + 2.5 % and of capacity 4 / 5 KVA etc complete all as specified and directed by Engineer-in-Charge
Repair of voltage stabilizer for automatic opration single phase naturally air cooled indoor type and desinged for input variation b/t 170 v to 280 v with output voltage stabilized at 230 v with accuracy of + 2.5 % and of capacity 0.5 KVA to 2 KVA etc complete all as specified and directed by Engineer-in-Charge
M&L for cleaning with the help of blower, painting of the Central AC plant 25TR -02 Nos including AHU followewd colour coading surface of entire AC plant at VDS plants including supports/Brackets with 2coats of synthetic enamel paint over a coat of red oxides primer including preparation of surfaces,minor repairing of is done all as directed by Engr-in-charge.
M&L for 5 micron fine filter of size 610*610*150mm (LXBXT) made of HDPE for 25 TR central AC lant all as specified and directed by Engr-in-charge
M&L for pre filter of size 510*610mm made of cellulose pad for 25 TR central AC plant all as specified and directed by Engr-in-charge
Disconnecting unserviceable compressor capacity 11TR from existing electric and pipe line connections of any make,transporting and replacing the same with factory/company made reconditioned compressor including connecting suction and discharge lines by copper brazing, pressure testing with the help of nitrogen gas and flushing out the oil in condensor cooling coil and gas charging all as directed :- Notes: 1. The make of the compressor to be replaced shall be same as that of the existing make in the cooling appliance. 2. Gas charging will be measured and paid seperately under the relevant item
Supply and intallation of terminal insulation for the supply air ducting (to avoid condensation) with 18mm thick, closed cell elastomeric nitirile rubber insulation sheet, class-O as per BS 476 part 6, fire retardant, co-efficient of thermal conductivityK=0.037W/m.k@20 degree celsius.density 60-85 kg/Cum operating range between -40 degree celsius and +85 degree celsius complete all as specified and directed Make: Superlon/A-flex/Aeroflex/K-flex or equivalent as approved by GE.
Supply and installation testing and commissioning of galvanised steel sheet square/rectangular fabricated from galvanised steel sheet of 22 gauge thick(0.80mm having zink coating of 180gm/sqm total on both side complete with gaskets,elbows,spliters,vaens,supports etc as per IS:655/1963 (Revised upto date ) all as specified including taking down existing duct of any type. Note:- Quoted rate shall include the cost of hanging of duct with GI nuts, bolts and MS angles as required including cutting of wall and making good the distributed surfaces as required for fixing duct at site.
M &L for Periodical maint of washing Machine and Dryer DER-30 and Dryer Thumbler once in three month which includes the following works etc complete all as specified and directed by Engineer-in-Charge
a) Descalling of drying chamber by descalling solution MAC b) Oiling, Greasing of bearing of motors and shaft c) Laying and tighting of panel wiring with proper thinbles /PVC Clamper d) Overhauling of washing machine chamber Note:- (i) Rate Includes for writing in White paint Date of Cleaning and Capacity.(ii) Contractor Should attend day day Complaint of Machine regularly and maintenance shall be Carried out accordingly for smooth functioning and the same shall be deemed to be include in the above quoted rates.(iii) Parts are measured and paid separately
Supply Only following parts:-
a) V Belt size A-69
b) HRC Fuse upto 32 Amps
c) Hose pipe for Drain 1.2 Mtr length
d) Water Solonoid valve 1"
e) Contactor 3 Phase 63 Amps for starter of main drive motor
f) Heating Contactor
g) Electric Heater
h) Idler Shaft
j) Sequence Controller
k) ignition Transformer
l) Air filter cum Regulator
m) single phase preventor
n) Drying Thumbler timer
o) Tension spring
p) Breaking contactor
M & L for rewinding of 3 Phase electric motor of washing machine main drive 3 HP incl taking down and reinstalling at site incl connecting electric point and commissioning complete all as specified and directed by Engr-in-charge
M&L for periodical maint of Air Compressor once in three month which includes the following works.(03 Nos of Air compressor)
(a) Checking the compressed air pipe for leakage. (b) Checking V belt and repair and replace it (c ) Oil,Greasing of bearing of motors and shaft (d) Checking of pressure valve switch for automatic control of compressor. e) checking of non return valve of compressor and if damage repair it. f) Overhauling of compressor motor g) Tighting and checking of panel wiring with proper thimble h) Painting of Air compressor with synthetic enamel paint ,one coat after cleaning scrubing the surfaces incl writing by paint the capacity ,marking of fuel level indicator etc complete as directed by Engineer in charge. Nore:- (i) Rate includes for writing in white paint Date of cleaning and capacity.(ii) contractor should attend day to day complaint of machine regularly and maintenance shall be carried out accordingly for smooth functioning and the cost for the same shall be deemed to be include in the above quoted rates.(iii) Parts are measured and paid Seperately.
Supply Only following parts:-
(a) V Belt suitable for Air compressor to motor main drive pully
(b) Compressed Air pipe of 10 mm Dia of Heavy Duty
(c ) Head gasket
(d) Piston Ring
(e ) Connecting Ring
(f) Oil Seal
S&F DOL Starter of Air Compressor motor Main Drive 3 HP incl taking down and reinstalling with new starter 415 volt 50 Cycle current rating 8 Amps incl connecting to electric point and commissioning etc complete alla as directed.
Supply and fix voltage stabilizer for automatic opration single phase naturally air cooled indoor type and desinged for input variation b/t 170 v to 280 v with output voltage stabilized at 230 v with accuracy of + 2.5 % and of capacity 4 / 5 KVA Suitable for Split,Window AC.
Supply and fix voltage stabilizer for automatic opration single phase naturally air cooled indoor type and desinged for input variation b/t 170 v to 280 v with output voltage stabilized at 230 v with accuracy of + 2.5 % and of capacity 0.5 KVA to 2 KVA Suitable for summer cooling Appliances.
Supply and fix Industrial type ultra slim square profile LED lighting fixture, environmental friendly, energy efficient ready to use pack Industrial type LED Tube light fitiing 20 Watt with LED light source 6500 K with uniform light output, with all accessories including its connection with and including 2 core sheathed copper conductor cable of size 0.5 Sqmm with complete with all accessories etc complete all as specified and directed by Engineer-in-Charge.
Supply and fix Worm white LED Tube light fitiing 20 Watt with uniform light output, with all accessories including its connection with and including 2 core sheathed copper conductor cable of size 0.5 Sqmm with complete with all accessories etc complete all as specified and directed by Engineer-in-Charge
Supply & fix 10 Watt Inverter LED batten with square profile and polycarbonate channel.lithium ion battery with charging time 8-10 hours and back up time upto 4 hrs with LED light source 6500 K with uniform light output, with all accessories including its connection with 2 core seathed copper conductor cable of size 0.5 Sqmm with etc complete all as specified and directed by Engineer-in-Charge
Supply & fix in replacement energy saving and environmental friendly long life LED street light 25 Watt (Bldg security light) made up of pressure die cast aluminium housing with mild power LED as lighting source and PC cover having TOP Opening seperate driver compartment with IP65 protection and impact resistance of IK07 fixed on wall with GI pipe of suitable dia and all fixing accessories including connecting up with & including twin core twisted flexible copper conductor cable of suitable size of 230V , 50 HZ etc complete all as specified and directed by Engineer-in-Charge
Supply & fix replacemnt industrial type switch socket for Geysers with 20 Amp MCB etc complete all as specified and directed by Engineer-in-Charge
S&F sub main wiring with two single core PVC insulated,unsheathed, FRLS stranded copper conductor cable 4 Sqmm with 4 Sqmm PVC insulated, unsheathed, FRLS stranded copper conductor cable as earth wire drawn through and including PVC Casing and capping ISI Marked with its all necessary accessories and earth wire connected to common earth dolly etc complete all as specified and directed by Engineer-in-Charge Note : 1. Porper colour coding shall be adopted for wiring (For Phase- Red, Yellow, Blue, For Earth - Green and For Neutral- Black) 2. Two run of 4 Sqmm cable i.e for one run for phase, one run for neutral with one run of 4 Sqmm cable for earth and one run of PVC Casing & caping shall be measured as one unit
S&F sub main wiring with two single core PVC insulated,unsheathed, FRLSH stranded copper conductor cable 6 Sqmm with 6 Sqmm PVC insulated, unsheathed, FRLSH stranded copper conductor cable as earth wire drawn through and including PVC Casing and capping ISI Marked with its all necessary accessories and earth wire connected to common earth dolly etc complete all as specified and directed by Engineer-in-Charge Note : 1. Porper colour coding shall be adopted for wiring (For Phase- Red, Yellow, Blue, For Earth - Green and For Neutral- Black) 2. Two run of 6 sq.mm cable i.e for one run for phase, one run for neutral with one run of 6 Sqmm cable for earth and one run of PVC Casing & caping shall be measured as one unit
S&F sub main wiring three phase with 6 Sqmm single core,4 Run PVC insulated,unsheathed, FRLSH stranded copper conductor cable with 6 Sqmm,one Run PVC insulated, unsheathed, FRLSH stranded copper conductor cable as earth wire drawn through and including PVC Casing and capping ISI Marked with its all necessary accessories and earth wire connected to common earth dolly etc complete all as specified and directed by Engineer-in-Charge Note : 1. Porper colour coding shall be adopted for wiring (For Phase- Red, Yellow, Blue, For Earth - Green and For Neutral- Black) 2. Three run of 6 sq.mm cable i.e for three run for phase, one run for neutral with one run of 6 Sqmm cable for earth and one run of PVC Casing & caping shall be measured as one unit
S&F service cable 1100V grade heavy duty cable PVC insulated stranded aluminium conductor served with inner sheathing of PVC tape and overall PVC sheathed in service connection suspended with insulating hanger not more than 1 m apart including 4 mm dia suspension wire alongwith 4 Sqmm twin core flat cable etc complete all as specified and directed by Engineer-in-Charge
Material & labour for earthing complete with galvanised steel earth plate electrode 600x600x6mm thick burried directly in ground. Earth pit not less than 2.25 m depth and top edge of the earth plate not less than 1.5 m below normal ground level connected to galvanised earth lead wire 4.0 mm dia by means of nuts, bolts & washer etc. Earth wire connected upto main earth point / DBs alongwith 15mm dia earth protection pipe from top edge of the earth plate to main earth point to be connected and 20mm dia watering pipe light grade with funnel and provn of PCC using cement concrete (1:2:4) mix type B1 using granded stone aggregate and RCC pit cover 50 mm thick precost RCC (1:2:4) mix type B1 duly reinforced with 8 mm dia of TMT bar @ 100 mm CIC, both way, lifting arrangement complete including all necessary earth work etc complete all as specified and directed by Engineer-in-Charge
Taking down carefully copper/aluminum point wiring (light/fan/bell/socket, power point etc) complete , including fixture and fitting such as switches, ceilling roses, pendants, regulators, sockets, light fittings etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per condition seperately) and making good disturbed surfases of walls, floors etc complete all as specified and directed Engineer-in-Chage
M&L for point wiring complete on surface of wall (open) type with two runs of 1.5 sq mm for phase and neutral single core multistranded copper conductor of 1100 volts grade PVC insulated and unsheathed FRLSH cable drawn in and incl PVC Casing and capping ISI Marked with its accessories with provn of PVC boxes and fixed with brass screws cup washer for fixing switches/socket/regulators etc incl 1.5 sq mm single core multistranded copper conductor of 1100 volts grade PVC insulated and unsheathed FRLSH cable as earth continuity conductor to common earth & connecting to earth dolly for the following, all as specified and directed. Note : 1. Porper colour coding shall be adopted for wiring (For Phase- Red, Yellow, Blue, For Earth - Green and For Neutral- Black) 2. All points are required to earthed upto fixtures i.e. Holders, Tube lights, Wall lights, bulkhead lights, bldg security light etc 3.Wiring shall be done as per complaints recd from user only on required basis it is not necessary to do whole wiring of any whole bldg
One light point controlled by switch 5 Amp single pole one way
One fan point controlled by switch 5 Amp single pole one way
One bell point controlled by switch 5 Amp single pole one way on independent board
One 3 pin 5 Amp socket outlet on same board controlled by one, one way 5 Amp switch
One socket outlet 5/3 pin 5 Amp controlled by one switch on independent board
One light point controlled by switch 5 Amp single pole two way
All as per Item No 184 (here-in-before) but with 2.5 Sqmm Copper conductor cable for Phase, Neutral and Earth for one 3 pin, 15 Amp socket outlet on independent board
M&L for point wiring complete on surface of wall (open) type with two runs of 1.5 sq mm for phase and neutral single core multistranded copper conductor of 1100 volts grade PVC insulated and unsheathed FRLSH cable drawn in and incl PVC Casing and capping ISI Marked with its accessories PVC boxes (upto 18 module suitble for Mylinc series of Legrand including white plates with frame upto 18 module of make suitable for Mylinc Series ) for fixing switches/socket/regulators etc incl 1.5 sq mm single core multistranded copper conductor of 1100 volts grade PVC insulated and unsheathed FRLS cable as earth continuity conductor to common earth & connecting to earth dolly for the following, all as specified and directed. Note : 1. Porper colour coding shall be adopted for wiring (For Phase- Red, Yellow, Blue, For Earth - Green and For Neutral- Black) 2.Wiring shall be done as per complaints recd from user only on required basis it is not necessary to do whole wiring of any whole bldg 3. All points are required to earthed upto fixtures i.e. Holders, Tube lights, Wall lights, ceiling lights, bulkhead lights, bldg security light etc
One light point controlled by switch 5 Amp single pole one way
One fan point controlled by switch 5 Amp single pole one way
One bell point controlled by one switch 5 Amp single pole, one way on independent board
One 3 pin 5 Amp socket outlet on same board controlled by one, one way 5 Amp switch
One socket outlet 5/3 pin 5 Amp controlled by one switch on independent board
One light point controlled by switch 5 Amp single pole two way
All as per Item No 192 (here-in-before) but with 2.5 Sqmm Copper conductor cable for Phase , Neutral and Earth for one 3 pin, 15 Amp socket outlet on independent board
S&F switch piano flush type single pole, one way 5/6 Amp etc complete all as specified and directed by Engineer-in-Charge
S&F switch piano flush type single pole, two way 5/6 Amp etc complete all as specified and directed by Engineer-in-Charge
S&F Switch socket combination two in one, 5 Amp flush type 230V AC etc complete all as specified and directed by Engineer-in-Charge
S&F Switch socket combination 5 Amp / 16Amp, five in one, 5 / 15 Amp 230V AC etc complete all as specified and directed by Engineer-in-Charge
S&F bell push piano flush, single pole, one way 5/6 Amp etc complete all as specified and directed by Engineer-in-Charge
S&F bell ding dong elelctric 230V AC single pole etc complete all as specified and directed by Engineer-in-Charge
S & F stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc. as required etc complete all as specified and directed by Engineer-in-Charge.
S & F electronic dimmers,as per existing wattage, 250V flush type on the exiting phenolic laminated sheet etc. as required etc complete all as specified and directed by Engineer-in-Charge
S&F Modular Switch, 6 Amp, one way, one Module. etc complete all as specified and directed by Engineer-in-Charge
S&F Modular Switch, 6 Amp, two way, one Module. etc complete all as specified and directed by Engineer-in-Charge
S&F Modular Switch, 16 Amp, onw way, one Module. etc complete all as specified and directed by Engineer-in-Charge
S&F Modular Socket Outlet 6 Amp, 2/3 pin, combined two module etc complete all as specified and directed by Engineer-in-Charge.
S&F Modular Socket Outlet 6 Amp / 16 Amp - 2/3 pin combined two module etc complete all as specified and directed by Engineer-in-Charge
S&F Modular Bell push, 6 Amp, one module etc complete all as specified and directed by Engineer-in-Charge
S&F Modular Fan Regulator Fan step regulator, 120 Watt - two module etc complete all as specified and directed by Engineer-in-Charge
Supply & fixing lamp holder (Angular/Straight ), insulated body, with back plate for batten fitting etc complete all as specified and directed by Engineer-in-Charge
M&L ceiling rose 3 terminal / PVC / polycarbonate, isolated body etc complete all as specified and directed by Engineer-in-Charge
S&F Socket outlet 2 in 1,3 Pin ,5A etc complete all as specified and directed by Engineer-in-Charge
S & F in replacement double door Sheet metal enclosures factory made Vertical DBs Concealed in wall 4 way TPN, 415 volts ,protection class IP-42, including 63 Amps MCCBs Input and suitable for fixing of outgoing MCBs, etc, confirming As per IEC 61439-3 ,Suitable for Flush Mounting and Surface Mounting, With 100 A Copper Busbar ,With Neutral bar, Earthbar and Cable ties for Cable management,Fully shrouded Neutral bars, Prefitted masking sheet etc complete all as specified and directed by Engineer-in-Charge.
S & F in replacement double door Sheet metal enclosures factory made DBs 4 way TPN, 415 volts ,protection class IP-42, suitable for fixing of MCBs, etc, confirming As per IEC 61439-3 ,Suitable for Flush Mounting and Surface Mounting, With 100 A Copper Busbar ,With Neutral bar, Earthbar and Cable ties for Cable management,Fully shrouded Neutral bars, Prefitted masking sheet etc complete all as specified and directed by Engineer-in-Charge.
S & F in replacement double door Sheet metal enclosures factory made DBs SPN, 8 way ,240 volts ,protection class IP-42,Concealed in wall suitable for fixing of MCBs, Isolators etc, confirming As per IEC 61439-3 ,Suitable for Flush Mounting and Surface Mounting, With 100 A Copper Busbar ,With Neutral bar, Earthbar and Cable ties for Cable management,Fully shrouded Neutral bars, Prefitted masking sheet etc complete all as specified and directed by Engineer-in-Charge.
S & F in replacement double door Sheet metal enclosures factory made DBs 4 way SPN, 240 volts ,Concealed in wall protection class IP-42, suitable for fixing of MCBs, Isolators etc, confirming As per IEC 61439-3 ,Suitable for Flush Mounting and Surface Mounting, With 100 A Copper Busbar ,With Neutral bar, Earthbar and Cable ties for Cable management,Fully shrouded Neutral bars, Prefitted masking sheet etc complete all as specified and directed by Engineer-in-Charge.
Taking out old PVC/Wooden/metal switch board ,wire connection Cocealed in wall and fix new Acrylic PVC Plate including connecting wire,Screw suitable for fixing switch/Socket/fan regulater of following sizes .(Note.Damaged Switch/Socket/regulator will be measured and paid Sepereately)
(a) 4x4 inches
(b) 4x6 inches
(c) 6x8 inches
(d) 8x10 inches
(e)10x12 inches
Supply & fixing MCB , SP, AC, 240 Volts of 06 to 40 Amp capacity 16KA, 'C' series and making connections with suitable size of copper lugs etc complete all as specified and directed by Engineer-in-Charge
Supply & fixing MCBs, TPN, AC, 415 volts of 63 Amps capacity 16 KA, 'C' series and making connections with suitable size of copper lugs etc complete all as specified and directed by Engineer-in-Charge
Supply & fixing MCBs, SPN, AC, 240 volts of 40 Amps capacity 16 KA, 'C' series and making connections with suitable size of copper lugs etc complete all as specified and directed by Engineer-in-Charge
Supply & fixing MCBs, SPN, AC, 240 volts of 63 Amps capacity 16 KA, 'C' series and making connections with suitable size of copper lugs etc complete all as specified and directed by Engineer-in-Charge
Taking out old PVC/Wooden/metal switch board ,wire connection from the wall and fix new PVC Cutting sheet board box including connecting wire suitable for fixing switch/Socket/fan regulater of following sizes. (Note. Damaged Switch / Socket / regulator will be measured and paid Sepereately)
(a) 4x4 inches
(b) 4x6 inches
(c) 6x8 inches
(d) 8x10 inches
(e)10x12 inches
S&F switch piano flush type single pole Including box, one way 5/6 Amp etc complete all as specified and directed by Engineer-in-Charge
M & L for Supply,laying ,connecting ,testing and commissioning and jointing , LT underground cable in replacement ,1100 volts grade, XLPE insulated, armored with galvanized round steel wire or steel strip, electric power cables heavy duty, with multi stranded aluminum conductor, laid in ducts, fixed on poles/walls with proper size saddles and clamp etc complete all as specified and directed by Engineer-in-Charge of following Sizes :-
(a) LT cable 16 Sqmm, 4 core.
(b) LT cable 25 Sqmm, 3.5 core.
(b) LT cable 35 Sqmm, 3.5 core.
Excavation in trenches n. exc 1.5 m wide and n. exc 1.5 m in depth and getting out in hard/dense soil etc complete all as specified and directed by Engineer-in-Charge .
Returnig, filling in including spreading, levelling, Watering and well ramming in layers, n exc 25 cm thick in soil etc complete all as specified and directed by Engineer-in-Charge .
Removing exacavated soil to a distance n. exc 50 m and depositing where directed at a level n. exc 1.5 m above the starting point etc complete all as specified and directed by Engineer-in-Charge .
Supply &lay HDPE pipe 40 mm bore light weight with 0.95 gm/cm2 PN 2.5 for laying of LT cable complete with all accessores etc complete all as specified and directed by Engineer-in-Charge .
An amount of Rs 69,192.00 shall be deducted from BOQ on account of schedule of credit
E M CONSTROL SYSTEM
BHAVIN INFRA
Bidder Name
E M CONSTROL SYSTEM
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .