Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.8 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹31.4 L+₹4.5 L (16.9%)Rejected-Finance | L2 | Rejected-Finance Not Being Lowest Bidder | |
| 3 | L3₹32.6 L+₹5.8 L (21.4%)Rejected-Finance | L3 | Rejected-Finance Not Being Lowest Bidder | |
| 4 | L4₹34.9 L+₹8.0 L (29.9%)Rejected-Finance 111 YADAV ELECRIC MARKET GB MARG LUCKNOW LUCKNOW UTTAR PRADESH 226018 | LUCKNOW | UTTAR PRADESH | 226018 | L4 | Rejected-Finance Not Being Lowest Bidder | |
| 5 | L5₹36.6 L+₹9.8 L (36.3%)Rejected-Finance | L5 | Rejected-Finance Not Being Lowest Bidder |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
27 Oct 2021, 6:00 pmClosed
GE E/M Lucknow
Garrison Engineer E/M, 36 LBS Marg, Lucknow Cantt, Lucknow (U.P.) PIN 226002
REPAIR/MAINT/REPLACEMENT OF LT INFRASTRUCTURE, UNSV STREET LIGHT, FLOOD LIGHT, HIGH MAST LIGHT, GATE LIGHT, FOCUS LIGHT, GARDEN LIGHT IN THE AREA OF BASE HOSP, SOI AND PD AUDITORIUM UNDER GE E/M LUCKNOW
2021_MES_478632_1
GE/EM/LKO/HOSP/T-44 OF 2021-2022
Open Tender
Miscellaneous Works
Item Rate
180 days
Lucknow
Class D or above category b (i)
8 documents required · 8 mandatory
₹500
GE E/M Lucknow
₹80,000
Yes
13 Nov 2021
29 Sept 2021
29 Oct 2021
29 Sept 2021
27 Oct 2021
14 Oct 2021
Amount
Supplying and laying or fixing in replacement, jointing and testing LT under ground electric power cable crossed linked polyethylene ( XLPE) insulated, galvanised steel strip or wire armoured, ISI-7098 Marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 10 sqmm cross sectional area, 2 core ,complete all as specified laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts , bolts, washers complete all as specified and directed. Note :- Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items.
All as per item No 1 above but size 10 Sqmm 4 core
All as per item No 1 above but size 16 Sqmm 4 core
All as per item No 1 above but size 25 Sqmm 3.5 core
All as per item No 1 above but size 35 Sqmm 3.5 core
All as per item No 1 above but size 50 Sqmm 3.5 core
All as per item No 1 above but size 70 sq mm 3.5 core
All as per item No 1 above but size 95 Sqmm 3.5 core
All as per item No 1 above but size150 Sqmm 3.5 core
All as per item No 1 above but size 240 Sqmm 3.5 core
S & F Straight through joints (Heat Shrink Kits) for 3.5 core cable 25 to 50 Sq mm LT underground cable complete for Armoured ,PVC sheathed Aluminium conductor cables Including excavating earth, identifying the fault, making proper joint of cable after rectification & returning soil back to earth, complete all as specified and directed.
All as per item No 11 above but 3.5 core cable 70 to 150 Sq mm
All as per item No 11 above but 3.5 core 185 sqmm to 300 sqmm
Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cables, pipes etc. and getting out including trimming the sides and forming bottom surfaces to required levels in soft/loose soil complete all as specified and directed.
Returning, filling in, including spreading, levelling, and well ramming in layer not exceeding 25 cm thick in soft/loose soil complete all as specified and directed.
Removing excavated material ( soils) not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed.
Material and labour for river sand, washed and screened dry for cushioning to under ground cable in trenches below and around under ground cable including spreading and levelling complete all as specified and directed. Note :- Punned thickness shall only be considered for payment
M&L laying well burnt old size bricks, sub class "B" bricks, straight or curved on plan , laid flat with width equal to length of brick , laid dry over electric cable for protection complete all as specified and directed.
Boring/Drilling ( horizontally) manually under existing road ( maximum 10 M in width) suitable for passing GI tubing of 40 to 100 mm bore complete all as specified and directed.
S & F GI tubing 'Light' grade 40 MM for cable protection fixed in poles/walls/laid under roads/crossing etc incl taking out the rusted pipes of following sizes, complete all as specified and directed.
All as per item No 20 above but size 50 mm bore dia
All as per item No 20 above but size 80 mm bore dia
Labour for taking out the unserviceable / faulty cable after meggering , finding the fault , cutting the cable , jointing with jointing kit using extra cable if required ,relaying of cables upto 300 sqmm 3.5 core ,connecting, rate included of excavation works, using old bricks complete all as specified and directed. Note :- cable joints will be measured and paid seperatly under respective item of schedule.
Material & Labour for preparation of old painted surface of steel tubular pole 9 meter long above coping) and applying two coat of aluminium paint, making of strip of 300mm width (balck and yellow in alternate band) upto 1500 mm height with one synthetic enamel paint , rewriting pole No by painter with enamel paint, and painting the existing MS clamp with one coat of aluminum paint complete all as specified and directed.
Material and labour for writting of Pole Nos on existing pole with stencil out with white colour in black colour background of 80 mm hight around the radius of pole and complete all as specified and directed.
Supplying and fixing in repair flat twin core ,1.5 sqmm nominal cross sectional area multistranded aluminium conductor cable, over all PVC sheathed, 1100 Volts grade heavy duty cable PVC insulated and PVC sheathed complete all as specified and directed.
Supplying and fixing in repair flat twin core ,2.5 sqmm nominal cross sectional area multistranded aluminium conductor cable, over all PVC sheathed, 1100 Volts grade heavy duty cable PVC insulated and PVC sheathed complete all as specified and directed.
Supplying and fixing in repair flat twin core ,6 sqmm nominal cross sectional area multistranded aluminium conductor FRLS cable, PVC insulated and sheathed 1100 Volts grade complete all as specified and directed.
M&L for old painted steel surface or iron surfaces of LT FPB of various size by scraping with steel wire brush/scrapper emery paper etc and applying one coat of synthatic enameled siemens grey/existing colour (painting shall be done by spray machine ) including hinge welding and fiting of new two number door for front and backside for thickness upto 3.15mm & size as per existing panel of the LT FBP door matching with the LT FBP including panel repair complete all as specified and directed.
MCCBs four pole 16 KA, fixed type incl taking out unserviceable MCCB's and connecting,of capacity upto 100 AMPS complete all as specified and directed.
MCCBs four pole 16 KA, fixed type incl taking out unserviceable MCCB's and connecting,of capacity 125 AMPS complete all as specified and directed.
MCCBs four pole 16 KA, fixed type incl taking out unserviceable MCCB's and connecting,of capacity 160 AMPS complete all as specified and directed.
MCCBs four pole 25 KA, fixed type incl taking out unserviceable MCCB's and connecting,of capacity 200 AMPS complete all as specified and directed.
MCCBs four pole 25 KA, fixed type incl taking out unserviceable MCCB's and connecting,of capacity 250 AMPS complete all as specified and directed.
MCCBs four pole 36 KA, fixed type incl taking out unserviceable MCCB's and connecting,of capacity 400 AMPS complete all as specified and directed.
Digital type Volt meter , 3 ph , class 1 including taking down unserviceable voltmeter, complete all as specified and directed.
Digital type Ammeter 3 ph , 5 Amps , class 1 including taking down unserviceable ammeter, complete all as specified and directed.
Indicator lamps (LED Type) including taking down unserviceable indicator lampsall, complete all as specified and directed.
S & F in rep MCB’s single pole with neutral, 6 to 32 Amps, 250 volts with 'B curve, fixed in existing PVC box including connecting complete all as specified and directed.
Dismantling the existing unserviceable ( damaged/broken) LT street light swaged poles / RCC poles or unserviceable tilted steel pole of any size, from ground after necessary excavation etc. and removing the unserviceable poles including making good disturbed ground and deposite in MES store yard complete all as specified and directed.
M&L for plain cement concrete 1:3:6 type C-2 using 40 mm graded stone aggregates, as in copping of poles complete all as specified and directed.
Disconnecting the existing cable from Panel / Pole, preparing the end for jointing including all earth work, Supply and fixing Cable end termination including sleeves heat shrinkable joint suitable for LT XLPE cable of size 3.5 core size 70 to 120 sqmm. complete all as specified and directed.
All as item No 28 above but size 120 to 240 sqmm.
Supplying, transporting, erecting and fixing Steel tubular swaged poles type 410 SP-31 ( 9.0 metres long) complete with cast iron base plate, finial, taper plug, bolts, nuts and screws as specified, including necessary excavation and earth work , PCC 1:4:8 type D2 in foundations below pole, PCC 1:3:6 type C2 around poles and PCC 1:3:6 type C1 as in plinth block , disposal of surplus soil to a distance not exceeding 50 m and depositing where directed, painting steel tubular poles exposed surafces with Aluminium paint two coats over one coat of red oxide primer and providing 300 mm wide bands (3 bands/ straps with synthetic enamel paint and 2 bands with Black bituminous paint ) from plinth block and numbering of poles , painting embedded portion of poles with one coat of bituminous paint complete all as specified and directed.
S&F MS Junction Box made of 1.6 mm thick MS sheet of size 250 x 200 x 150 mm complete with front openable hinged cover and locking arrangements with 4 Nos aluminium bus bar 100 Amps, mounted on porcelain insulator including MCB SP 10Amp , 10 KA-1No, fixed on box in Din rail complete with electrical connection fixed to pole with suitable size FI clamp nut bolts and washer including duly painted with powder coated paint complete including required size and length of copper conductor cable and making connections complete all as specified and directed.
Restreching only existing LT OH/ HT OH lines consisting following lines of ACSR and GI wire , any size and tightening with aluminium binding wire 2/4/5/6 Lines of ACSR and 1 line of GI wire complete all as specified and directed. Note :- (i) Linear length centre to centre of the poles shall only be measured (ii) Cleaning / pruning of tree branches falling around the conductor shall also deemed to be included in the quoted rates
S & F Offload change over switch, 200 Amps, 415 volts, 4 pole in sheet metal enclosure conforming to IS:13947 (Part-3); IEC:60947-3 with locking facility including all connecting/ jointing materials and dismantling of existing change over switch, complete all as specified and directed. Make havells or equivalent as per spacified and directed
S & F On load change over switch, 63 Amps, 415 volts, 4 pole side handle type in sheet metal enclosure conforming to IS:13947 (Part-3); IEC:60947-3 with locking facility including all connecting/ jointing materials and dismantling of existing change over switch, complete all as specified and directed.
S & F Off load change over switch (side operated handle) 400 Amps, 415 volts 4 pole in sheet metal enclosure with interlock door and pad lock facility including dismantling of existing change over switch, complete all as specified and directed.
Supply and fixing new generation ,energy saving ,environment friendly LED GATE LIGHT fitting,fully cast aluminium body finish with polyeurethene paint with acryilic window cover with B22 brass holder suitable for 15 to20 watt led bulb as light sopurce including making connections complete all as specified and directed. Make- MEPRO cat part no. PTL-0002 OR EQUIVALATS MAKE as spacified and directed by engineer in charge
Supply and fixing new generation ,energy saving ,environment friendly POST TOP LANTERN fitting, aluminium spun lamdscape luminaires with high power LED 25 watt as light sopurce including making connections complete all as specified and directed. Make- havells cat part no. RUBYPT25WLED830SSYMTOPC or equivelent make.
S&F MCCBs four pole 36 KA, fixed type incl taking out unserviceable MCCB's and connecting,of capacity 630 AMPS complete all as specified and directed.
M&L Earthing complete with galvanised mild steel earth plate electrode 600x600x6.0mm thick, burried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI strip 32 x 6 mm as earth strip electrode bolted or rivetted to earth plate at one end and connected to equipments at another end, GI earth strip encased in and including 40 mm dia GI 'light grade' pipe from upper end of earth plate upto equipments,20 dia bore GI pipe 'light grade' as water pipe from earth chamber to upper edge of earth plate, Test point , GI funnel with wire mesh fixed on water pipe and PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1, duly reinforced with MS TMT bars 8mm dia @ 100 c/c both ways with 10mm dia MS round bar as in lifting handles, excavation, earth work including laying the GI pipe concealed in floor/wall all as described in electric plate of SSR Part I complete all as specified and directed by Engineer-in- Charge and testing on completion. Note :- If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department.
M&L Earthing complete with Copper earth Plate electrode 60x60cmx3.15mm thick, burried directly in ground ( earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, Including connected to copper strip 20x3mm lead (upto 7.5 Mtr) by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate connected to earthing test point all as specified or indicated including testing on completion.ith salt to a packed thickness of 15 cm all around the plate, and including 40 mm dia GI 'light grade' pipe from upper end of earth plate upto equipments,20 dia bore GI pipe 'light grade' as water pipe from earth chamber to upper edge of earth plate, Test point , GI funnel with wire mesh fixed on water pipe and PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1, duly reinforced with MS TMT bars 8mm dia @ 100 c/c both ways with 10mm dia MS round bar as in lifting handles, excavation, earth work including laying the GI pipe concealed in floor/wall all as described in electric plate of SSR Part I complete all as specified and directed by Engineer-in- Charge and testing on completion. Note :- If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department.
Dismantling and removing existing unsv street light/ flood light MH/HPSV fittings of any type and any capacity from street light poles any hieght and high mast light pole after disconnecteing of electrical connection complete all as specified and directed.
Supply and Fixing in replacement, connecting and testing energy saving LED street light fittings 35 Watt with thermal management, potted driver, pressure die cast housing LM 6 alloy/anti dust exposed lens, in built tilt angle arrangement and environment friendly long life with IP66 protection on existing street light poles and bracket complete all as specified and directed.
Supply and Fixing in replacement, connecting and testing energy saving LED street light fittings 45 Watt with thermal management, potted driver, pressure die cast housing LM 6 alloy/anti dust exposed lens, in built tilt angle arrangement and environment friendly long life with IP66 protection on existing street light poles and bracket complete all as specified and directed.
Supply and Fixing in replacement, connecting and testing energy saving LED street light fittings of 60 Watt with thermal management, potted driver, pressure die cast housing LM 6 alloy/anti dust exposed lens, in built tilt angle arrangement and environment friendly long life with IP66 protection on existing street light poles and bracket complete all as specified and directed.
Supply and Fixing in replacement, connecting and testing energy saving LED street light fittings of 100 Watt with thermal management, potted driver, pressure die cast housing LM 6 alloy/anti dust exposed lens, in built tilt angle arrangement and environment friendly long life with IP66 protection on existing street light poles and bracket complete all as specified and directed.
Supply and Fixing in replacement, connecting and testing energy saving LED street light fittings of 90 Watt with thermal management, potted driver, pressure die cast housing LM 6 alloy/anti dust exposed lens, in built tilt angle arrangement and environment friendly long life with IP66 protection on existing street light poles and bracket complete all as specified and directed.
Spply and Fixing in replacement GI bracket for street light fittings fabricated with GI tubing 40mm dia 'light grade' 1.5m long and bending to angle of 120 degree including mild steel clamp of suitable size with two coat aluminium paint suitable for fixing on PCC/steel poles complete all as specified and directed.
Supply and Fixing in replacement, connecting and testing energy efficient LED flood light fittings of 120 Watt pressure die cast aluminium housing and IP66 protection including XLPE armoured cable 2 core 4 Sqmm up to 5 mtr from fitting to panel box with emitter complete all as specified and directed.
Supply and Fixing in replacement, connecting and testing energy efficient LED flood light fittings of 150 Watt pressure die cast aluminium housing and IP66 protection including XLPE armoured cable 2 core 4 Sqmm up to 5 mtr from fitting to panel box with emitter complete all as specified and directed.
Lowering the high mast light from height of 16 to 25 mtr and repairs to the extent by removing connections from the system, checking of unserviceable spare parts and serviceable parts ,replacement of unserviceable parts with new spares and testing complete, tightening the loose connection and made item functional, reassembling the fitting and re-fixing/ re-hanging the same after repair in existing location and tesing complete all as specified and directed. Note : (a) Spares required for repair shall be measured and paid separately as supply only items here-in-after (b) The contractor shall provide all type and safety equipment & other tools required at site to electrician for maintenance of light (c) In case any accident/injury of any person deputed by contractor shall be held responsible for setting all claims/compensation. (d) all other item also included in the works which not catered in items
Supply only gear box as per existing size, capacity and make CROMPTON GREEVES complete all as specified and directed.
Supply only motor as per existing size,capacity and make CROMPTON GREEVES complete all as specified and directed.
Supply only controll switch as per existing size, capacity and make CROMPTON GREEVES complete all as specified and directed.
Supply and fixing in replacement, connecting and testing energy efficient LED flood light fittings of 200 Watt pressure die cast aluminium housing and IP66 protection with complete all as specified and directed.
Dismantling and Supply and errection in of 07 mtr continuously tapered hot dip galvanised Octagonal cross sectional pole with single dipping method having bottom 130 mm A/F and top 70 mm A/F 3 mm thick confirming to ASTM A 572 Gr with yield 450 mpa cut and folded to form an octagonal section and welded in accordance with AWS for wind loading as per IS 875 part 3 1987.Poles shall be provided with base plate of size 225x225x12 mm which shall be free from any lamination or incursion with no cutting or welding on the pole after hot dip galvanising with single arm 1000 mm long bracket tilted to 150 degree from horizontal toward vertices suitable for mounting on the octagonal pole, of company recommendation complete all as specified and directed.
Excavating in post holes (or similar holes) each n exc 0.5 cu. m, getting out in soft/loose soil, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm complete all as specified and directed.
M&L for PCC 1:3:6 type C-2 using 40 mm graded stone as in foundation /sub base of floor, filling and mass concrete complete all as specified and directed.
M&L for formwork to sides of concrete foundation, footings for fair finished surfaces etc complete all as specified and directed.
M&L for RCC (Nominal mix) Type B1 1:2:4 (using 20mm graded aggregates) as in Foundations, including rafts, footings, foundation beams; plinth beams; bases for columns, etc; basement slabs, under-reamed piles and mass concrete complete all as specified and directed.
S&F Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/ cladding to wall, fixed with self tapping screws complete all as specified and directed.
M & L for Steel work in tubular trusses including special shaped washer etc. complete using ERW or induction butt welded tubes complete all as specified and directed.
M&L for two coats of synthetic enamel paint over red oxide primer coating incl preparation of newly steel surfaces etc complete all as specified and directed.
DEV INFRATECH
M/S AMARJIT SINGH
Industrial Traders
M K Engineers and Contractors
U K Enterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .