Loading…
Loading…
Tender Value
₹56.3 Cr
EMD Value
₹1.1 Cr
Closing Date
3 Jul 2026, 2:00 pm
Sumit Nandal
Municipal Corporation Panipat
Design, Construction, ErectionTestingCommissioning, OandM for 15 years after DLP for Transfer of 60MLD Treated Waste Water from 25MLD and 35MLD STPs Siwah to existing HSVP tanks in Sector29 MC Panipat
2026_HRY_526500_1
202643E41094 C36E 4ECE 8C1B 294C9A202E86286ULB
Open Tender
Civil Works
700 days
Panipat
2 documents required · 2 mandatory
₹50,000
₹1.1 Cr
Yes
MC Panipat, Devi Lal Complex
3 Jun 2026
3 Jun 2026
3 Jul 2026
3 Jun 2026
3 Jul 2026
3 Jun 2026
15 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | Item Code |
|---|---|---|---|---|---|---|
| 1 | 11 kV SWITCHYARD / TWO POLE (DP) STRUCTURE:
Supply, Installation, Testing and Commissioning of 11 kV, 3 Phase, 50 Hz, Two Pole Structure made of 6` X 3` `I` section girder having min. 9mtr. length, 4` X 2` M.S. channels, angles, clamps, nuts, bolts, stay wires including earthing system etc. suitable for erection of following / indicated accessories duly connected with ACSR conductor as per approved drawings and in compliance with requirements of IS/IEC / Power Supply Co.:
(a) 11kV 200A DO (drop out) fuses with S.R.B.P. tubes carries (03 nos.)
(b) 11kV 400A G.O.D. switch complete with insulators, operating handle with galvanized pipe, square bar etc. (01 set)
(c) 11kV lightning arrestors with clamps (03 nos.)
(d) 11kV shackle (Disc/Pin/Post) as required insulators (06 nos.)
(e) ACSR Dog Conductor (mini. 30Mt.)
(f) 11 kV fiber operating rod
(g) 20 mm dia. GI stay sets (2 sets), required foundation etc.
and to be painted with two coat of red oxide and final two coat of Aluminium paint at site as per IS, Specification and Drg. | 1 | Each Set | - | - | ITEM1 |
| 2 | H.T. INDOOR SWITCH GEAR PANEL
SITC of 11 kV, 500 MVA, 630A, Indoor, Extensible type, Horizontal draw out, Motorised spring charging mechanism, 3 breaker Vacuum Circuit Breaker Panel (1 No. Incomer plus 2 Nos.outgoing), with EC grade copper busbars along with required Resin cast CT Dual primary and secondary, Cl: 0.5/5P10, 15VA, Digital MFM with RS 485 with 3 Line Display, Class-0.5s and PT (dual secondary) Cl:0.5/3P, min 200VA or higher for metering and protection, 110V DC power pack for incoming and outgoing feeder, Annunciator, Hooter, Indicating lamps, Numerical Protection relay
(Current and Voltage Based) with RS 485 with combined protection for 3O/C plus 1E/F, S/C, Under and Over Voltage, Transformer Protection Aux. relay etc. High speed tripping relay, Trip ckt supervision relay, Fuse failure relay, Digital Power factor meter, Ammeter, Voltmeter (Only I/C), A/M switch suitable for PLC/SCADA etc. complete in all respects as per IS, Specification. | 1 | Each Set | - | - | ITEM2 |
| 3 | SITC of H.V. CABLES
11 kV (E), 3C x 240 sq.mm., Aluminium, extruded innersheath, Armoured, XLPE , H.V Cable as per IS 7098 (part 2) and Tech. Specification.
(PSC DP Structure to Client DP Structure, Client DP Structure to HT Panel, HT Panel to Transformer 1 and 2) | 100 | Per Metre | - | - | ITEM3 |
| 4 | Supply and levelling of Switch yard and transformer yard using gravel, fine sand and other required filing material, enmarked for the Switchyard and Transformer yard including removing of trees or boulders etc. if any. The general level of the yard shall be at a convenient level for movement of man and material and it should match with FGL and as per Specification and Drg. | 110 | Sqm | - | - | ITEM4 |
| 5 | Supply and Installation of GI Chain link fencing frames with L angle/Channel post around Transformer yard etc. as per Specification and Drg. | 55 | Rmt. | - | - | ITEM5 |
| 6 | SITC of H.V. CABLES
SITC of 3.0 mtr wide gate with GI chain link as per Specification and Drg. | 3 | Nos. | - | - | ITEM6 |
| 7 | STAND ALONE VFD CUBICLE PANEL FOR 75kW SUBM. NC PUMP :-
SITC of Standalone VFD Panel (LT MCC panel, 50kA) for Min. 75kW Motor, compartmentalized, Floor Mounted / stand mounted as per site condition / requirement, operating height maximum 1800/1900 mm, Extensible on both ends, suitable for Manual and Auto operation. Auto operation and moitoring through PLC/SCADA: Manual from panel when in remote mode complete in all respects as per Tender SLD / Specification / IS and including following as minimum:
Panel comprising of Min. 200A TPN Microprocessor MCCB LSIG as incomer,VFD with inbuilt RS 485 for 75 kW Motor or higher as per pump manufacturer reco. with VFD rating minimum (148A @ 50°C) with suitable derating with detachable type door mounted display key pad, 200A, AC3 duty Line contactor, Semi conductor fuse, Input Choke having Max. 2% voltage drop shall be provided, rating as recommended by VFD manufacturer and Output choke as recommended by VFD OEM for harmonic mitigation, VFD with 3C3 Confromal coating, MFM Cl. 0.5 with RS-485, Resin Cast CT Cl: 0.5, SPP, Space heater, A/M, L/R switch, R,Y,B, On, Off, Trip, Speed Up and Speed down Indicating lamps, Start, Stop, Speed Up and down Push buttons.
Heavy duty 6` Metalic Housing and Metal Impeller / Blade / Vanes of Minimum 2nos. or higher as required at the top of the panel with canopy/hood etc. Voltage and current harmonics shall be as per recommendations of the IEEE-519 2014 or latest revision.
STAND ALONE PANEL MINIMUM SIZE: 1.2M (W) X 1.5M (H) X 1.0M (D) | 6 | Each Set | - | - | ITEM7 |
| 8 | SITC of 135 KVAR at 415V, APFC Panel Filter Panel with 7% Detuned reactors,compartmentalised, Floor mounted, extensible type on both sides with Horizontal bus bar arrangement as per site requirement and complete in all respects as per SLD / Specification / IS and including following as minimum:
(1) INCOMER:
1.1 320A, TPN, 50 KA TM MCCB with Digital Voltmeter with VSS, Digital Ammeter with ASS, Resin Cast CT- Cl : 1.0,10VA, A/M, L/R switch, Indicating lamps, Push buttons etc.
1.2 Microprocessor based APFC Relay,144sq.mm, 12 STEP with RS 485 with minimum operating current 10mA.
2. OUTGOING CAPACITOR FEEDER:
Capacitor feeder of following rating comprising of TPN MCCB/MCB with ON and TRIP Indication, Capacitor duty contactor,Heavy duty MPP / gas filled capacitor unit, A/M Switch, ON Delay timer,ON / OFF Push button, ON, TRIP, Auto and Manual Indication lamp etc. as per Tender SLDand Specification
2.1 25 KVAR FEEDER: 4 NOS
2.2 20 KVAR FEEDER: 1 NO
2.3 5 KVAR FEEDER: 2 NOS
2.4 2 KVAR FEEDER: 2 NOS
2.5 1 KVAR FEEDER: 1 NO
2.6.Two nos. Vacant feeder suitable for 1-25KVAr and 1-20KVAr to be provided.
NOTE: 1. cooling/exhaust fan : Heavy duty 8` Metalic Housing and Metal Impeller / Blade / Vanes of Minimum2nos. or higher as required at the top of the panel with canopy/hood.
2. For Capacitors of rating = 5 KVAr only, All types viz. APP/MPP/Gas Filled are acceptable. | 2 | Each Set | - | - | ITEM8 |
| 9 | `SITC of 400V, 3Ph 4 wire, closed loop compensation, min. 150A Active harmonics filter (AHF) with MCCB and fast acting semi conductor fuse protection, CT of Class 1 or better with 15 VA, Touch screen display, Alarms for fault conditions, floor mounted, expandable as per site requirement and complete in all respects as per Specification / IS/IEC to maintain harmonic levels as per latest IEEE 519 standards.
Note:- Above mentioned ratings are min rating for AHF panel and contractor to provide higher rating AHF panel if required as per actual calculation of the vendor/ OEM. | 2 | Nos. | - | - | ITEM9 |
| 10 | `SITC of Lighting Distribution Board (LDB) as under:
SITC of 3 Phase 4 Wire 4P, double door Prewired LDB each for Indoor Lighting and Outdoor Lighting Suitable to house :
Incoming: 32A FP, ELMCB (30mA)
Outgoing: 20A SP MCB (9 nos.) and 16A SP MCB (9 nos.) | 2 | Nos. | - | - | ITEM10 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.83 MB
BOQ_605476.xls
BOQ • 0.40 MB
Download all tender documents and submit your bid