Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.6 LAccepted-AOC HOUSE NO 2 4 136 LINGREDDY MANSION BLOCK NO IV OPP HANUMAN TEMPLE TADBUND SECUNDERABAD 500009 | SECUNDERABAD | HYDERABAD | TELANGANA | 500009 | L1 | Accepted-AOC Accepted being L1 | |
| 2 | L2₹40.2 L+₹33,059.20 (0.83%)Rejected-Finance | L2 | Rejected-Finance Not being L1 | |
| 3 | L3₹40.4 L+₹50,902.20 (1.28%)Rejected-Finance | L3 | Rejected-Finance Not being L1 | |
| 4 | L4₹40.7 L+₹83,003.20 (2.08%)Rejected-Finance 39 40 DASHMESH MARKET CIVIL GURUDWARA LINE PORT BLAIR 744 101 | PORT BLAIR | SOUTH ANDAMANS | ANDAMAN AND NICOBAR ISLANDS | 744101 | L4 | Rejected-Finance Not being L1 | |
| 5 | L5₹42.7 L+₹2.8 L (6.94%)Rejected-Finance | L5 | Rejected-Finance Not being L1 |
Tender Value
₹40.5 L
EMD Value
₹81,000
Closing Date
1 Oct 2020, 6:00 pmClosed
Garrison Engineer Utility
Garrison Engineer Utility Mudfort Secunderabad
PROVN OF 03 X HIGH MAST LIGHTS (12 M) AT SAFILGUDA (JCOS AND OR MD ACCN) OF 654 EME BN, PROVN OF ADDITIONAL STREET LIGHT AND UPGRADATION OF ELECTRIC SUPPLY AT 60 COY ASC (SUP) TYPE-G, SPECIAL REPAIR/REPLACEMENT OF 80 KVA UPS BATTERIES OF OT OF MH SE
2020_MES_378770_1
GE (U)/SEC/TOKEN/06 OF 2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE Utility Secunderabad
as per NIT
6 documents required · 6 mandatory
₹500
GE Utility Secunderabad
₹81,000
Yes
8 Jan 2021
18 Sept 2020
5 Oct 2020
18 Sept 2020
1 Oct 2020
18 Sept 2020
Amount
Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth, for foundation of PCC/Steel pole, laying of cable in trenches or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and getting out in hard / dense soil complete all as specified and directed.
All as per Item No 1 above but Exc 1.5 M and not Exc 3 m
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm in soils complete all as specified and directed.
Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed.
M&L filling sand in trenches for sand cushioning of laying of cables to the full width of excavated trench 8 cm thick before laying the cable and 15 cm above the cable, gently punned down, stretching and testing of cable on transformer yard etc complete all as specified and directed. Note :- Thickness of sand cushion after punning down (i.e 18 cm) shall be measured for payment.
Supply and Laying bricks, common burnt clay building bricks, sub class 'B' of old size 230 x 115 x 75 mm laid across in trenches for cable protection complete all as specified and directed.
Supply & lay galvanised Iron tubing 50mm bore, light grade in protection of cable at road crossing/hard standing/pole protection fixed with MS clamps of size 40 X 4 mm, nut bolts and washer as per site requirement including taking down old unserviceable pipes complete all as specified and directed.
All as per Item No 7 above but 40 mm bore of pipe
Supply, errect, test and commissioning of High Mast system consisting of single/double section mast shaft, made out of hot dip galvanised steel structure 12 Mtrs long including head frame, three wire suspension , steel wire rope 6mm dia (7/10 construction) double drum winch, galvanised lantern carriage arrangement suitable for and including 6 Nos 1X200W LED lights, 01 number LED type aviation obstruction light including lamp, lightning final etc, with integral power tool installed inside base compartment for operation including accessories such as suitable for wind velocity as per IS 875 Part 3, including/confirming to the following :( make of mast: philips/bajaj/surya/crompton /HAVELLS)
Make of LEDs : (i) The light luminaries shall be 1X200 watt LED lamp - 06 nos , non-integral asymmetric type flood light with die cast aluminium housing with IP 65 protection flood light fittings. ( MAKE : HAVELLS Model No JETAVALOURFL200WLED757PINTNBLTG/ PHILIPS MODEL NUMBER: BVP483 LED235 CW SWB PSU GR/ BAJAJ MODEL NUMBER :GLEAMF 240WHSYPC / WIPRO MODEL NUMBER : LF20-272-060-57-G2/ SURYA MODEL NO SLEFL200WIP66 LUMOS11/ LUKER- LFL HL 200 (ii) TThe Aviation obstruction light LED type SIMILER TO XGP400 IXLED-K2/RD 240 VOLT OF MAKE PHILIPS / BGAV 302 LED OF BAJAJ/ SLE AL 54 LDR -SEN IP 65 OF SURYA / GLN 704 OF CG/ EQUIVALENT FROM PHILIPS/HAVELLS. Make of high mast:- Philips / Bajaj / Havells / Wipro/Crompton/ Surya. Notes:- (i) LED used should be the make of Cree/Osrm/Lumilieds /Nischia. (ii) Contractor has to produce LM-79 /LM-80 certificate along with purchase vouchers and Guarantee certificate from Manufacturer. (iii) Surge protection of the drive shall not be less than 10 KV. (iv) Cable if required for connection will be measured and paid separately under respective item
(a) Foundation bolts manufactured from special steel along with nuts, washers, anchor plates and templates complete all as specified and directed. (b) Design and casting of suitable shallow foundation with M-25 design mix concrete for high mast as per manufacturers norms considering the safe soil bearing capacity of soil as 10T/Sqm at 1.2 meters depth, however the soil bearing capacity be checked/confirmed by the Engineer-in-charge as per site condition and got approved by the GE before commencement of work.
(c) Advance Maintenance Free G.I. SAFE EARTHING Electrode with PIPE of not less than 50 mm outer dia( THICKNESS NOT LESS THAN -2.5MM) and two meter length, The electrode should be of galvinised (80 -100 micron) along with earth lead as Galvanised steel strip of size 32 X6 mm 7.5 m . The GI Electrode shall be pre-filled with Cristaline Conductive Material (CCM) . The GI electrode shall be surrounded with 25 kg BackFill compound to provide maximum contact between the electrode and Back Fill Compound. Backfill compound should be eco-frendly and having RoHs certification . GI Electrode Shall be tested from CPRI.The earting pit should be cover with pcc(1:2:4 , B1) cover ,of 300x300 mm complete all as specified and directed make ASHLOK / INDELEC/JMV /TERCEL/TRUE POWER - 2 nos .
(d) LT FEEDER PILLAR BOX BOTH SIDE OPENABLE with projected Globe roof for rain water protection,manufactured by a CPRI approved Manu-facturer Dust and Vermin Proof , suitable for 440 Volt 3 Phase 4 Wire System made out of 3.00 mm thick CRCA Sheet of size .75MX.75MX.40M and built upon Rigid Frame Work having Front and Rear hinged double shutter Doors with Neoprene Rubber Gasket, Epoxy Powder Coated including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embeded with 50X6mm Mild Steel Angle Iron Frame and 600mm above the Normal Ground Level comp -lete with PCC Foundation in Cement Concrete 1:2:4 (20mm Graded Stone Aggregate) and Test-ing after Installation complete all as specified and comprising of the following :– (for controlling of hogh mast light)
Note : (i) The contractor shall procure the high mash with all fittings and accessories directly from manufactorers. (ii) The installation fittings and accessories shall be gote done under the supervision of manufacturer and as per manufacturers instructions and approved by GE. iii)PV and Test certificate for each and every item related to High mast system to be produced. iv) necessary approval must be taken regarding details technical specificatio and foundation drawing of high mast light before placing order to the company. v) Testing for Design mix to be got done from approved labarotory , cost for the same deemed include in the quoted rate.
Supply, install,Testing and Commissioning of 80 KVA (384 DC) UPS with 3 Phase Input and 3 Phase Output with inbuilt isolation Transformer with 64 Nos 12 Volt 150 AH Sealed Maintanance free Batteries to provide 60 Minutes backup ( 2 Bank of 32 battery each connected in parallel) including battery rack and complete interconnecting copper cables with and including lugs complete all as required for proper functioning of UPS. the Technical details of UPS are as under : (a) Input Parameters (i) Capacity in KVA - 80 KVA (ii)Nomininal Voltage - 415V AC (3Ph +N)+/-15% (iii) Frequency - 50Hz +/-6% (iv) Rectifier Bridge - SCR based (6 Pulse full controlled) (v) Power Factor - ˃ 0.8 (vi) THDi - ˂ 5% (at full load and v THD ˂1%) (vii)DC Voltage Ripple - ˂3% without Battery, ˂1% with Battery (viii)DC Current Ripple - Max 5% (xi) Power Walk in - Up to 60 sec, settable
(b) Output Parameters (i) Nominal rating in KVA - 80 KVA (ii) Nominal Power in KVA- 64 KW (iii)Inverter Bridge-Space Vector Modulation & IGBT Technology (iv) Output Wave Form - Sine Wave (v) Controller-32bit DSP based (vi) Voltage-400V/415V AC (380V Optional) (vii) Voltage Stability-Steady State +/-1% (viii) Dynamic Response-<1.5% (xi) Recovery time - 98% recovery within 20ms (x) Frequency - 50Hz +/-0.1Hz (xi) Output Voltage THD for 100% Linear load-<1.5% (xii) Output Voltage THD for 100% non-Linear load - <5% ((xiii) Power Factor handling Capacity-0.6 to unity within KVA & KW rating (xiv) Overload capacity from inverter at nominal voltage - 110% for 60 min 125% for 10 min 150% for 60 sec (xv) Duty - Continuous (xvi) Crest Factor- 3:01 (xvii) Parellel - Up to 6 units (xviii) Wound Components- Inbuilt Output Isolation Transformer Overall Efficiency - 80 KVA (i) At 25% load - Up to 90 % (ii) At 50% load - Up to 92 % (iii) At 75% load - Up to 92 % (iv) At 100% load - Up to 92 % (v) Frequency on Eco Mode - Up to 99%
(C) Battery Parameters (i) Nominal rating in KVA - 80 KVA (ii)Nominal power in KVA - 64KW (iii) Nominal DC bus voltage - 384VDC iv) Battery Type - 12V SMF VRLA (v) Float Voltage - 2.27V/Cell (vi) Boost Voltage - 2.35V/cell (vii) Minimum Discharge Voltage - 1.75V/cell (d) Bypass Parameters (i) Nominal rating in KVA - 80 KVA (ii)Nominal power in KVA - 64KW iii) Input Connection - Common with mains input (iv) Bypas Voltage & Variation - 400V/ 415V AC (3 ph + N ), +/-15% (380V Optional) (v) Frequency Sync range - 50 Hz +/-2.5Hz (vi) Transfer Time - Sync Mode : No Break, Async Mode :˂5ms (vii) Retransfer Time - Sync Mode : No Break, Async Mode :Inhibited (viii) Primary Components - Static Switch (SCR-SCR module) (xi) Manual Bypass- Inbuilt
(.e) Environmental & Mechanical Parameters (i) Nominal rating in KVA - 80 KVA (ii)Nominal power in KVA - 64KW (iii) Operating temparature _ UPS : 0 to40 Deg C (iv) Storage Temperature - UPS : 0 to 70 Deg C (v) Relative Humidity - Up to 95% RH Non Condensing (vi) Maximum Operating Altitude - 1000m above MSL (vii) Acoustic Noise - ˂65dBA @ 1m (viii) Cooling - Forced Air cooling (f) Display Characteristics (i) Nominal rating in KVA - 80 KVA (ii)Nominal power in KVA - 64KW (iii) LCD Display - Input voltage, Output voltage, Input current, Output current, Battery voltage, Output KVA, Battery current, Output KW, Bypass voltage, Output PF, Bypass frequency, Output frequency, Temperature, Output Load in %, Date & time. (iv) LED indication - Rectifier ON / OFF, Load ON, Inverter ON / OFF, Float Charge, Bypass available, Boost Charge, Manual bypass ON, Battery low, SWI (Inverter Switch ON), Battery Charging/ Discharging, SW b (Bypass Switch on) (v) Alarm - For Fault Condition (vi) Protection - Input UV/OV, Battery current limit, Rectifier OV, Output UV/OV, Battery low, Output overload, Over temperature, Output short circuit, Battery OV.
(g) Physical Characteristics i) Nominal rating in KVA - 80 KVA (ii)Nominal power in KVA - 64KW (iii) Ingress Protection - IP 20 (iv) Cable Entry - Bottom Front (v) Cabinet Steel Thickness - Frame 2mm, Front door 2mm, Covers1.2mm (vi) Installation - Free Standing, Floor Mounting Make : Fuji Electric Consul Neowatt . Model Falcon Series / equivalent from Sukam/microtec/Power One for UPS and Exide/Amaron for SMF battery
Supply ,Install Testing &Commissioning of wall mounted Indoor type totally enclosed LT panel Board CPRI APPROVED , IP 55 compartmentalised design, dust and varmin proof of suitable size suitable for 440 Volt 3 phase 4 wire system made out of 2.0mm thick CRCA sheet and built upon regid frame work having front hinged doors with neoprene rubber gasket including danger plate, earthing strip point and, ventilation louvers at the rear side, bottom detachable gland plate complete with suitable size of Zinc/Cromium plated and nuts, bolts ;and washers etc. The pannel shall be Epoxy Powdwer Coated and the control circuit diagram shall be with colour code solid conductor copper 1.5 sqmm cable for easy identification including incomming/outgoing cable holes at the bottom and TOP. The Panel shall be emmbeded with 40 x 4 mm MS Angle Iron frame a complete all as specified and directed by Engr in charge.
Supply & Erecting Steel Tubular Swaged Pole Type 410-SP-31 (9.0 METRE long) including Cast Iron Base Plate, Finial Taper Plug, Cap, Mild Steel Bolts, Nuts, Screws including applying Two Coats of Black Bituminous Paint Internally and Externally upto Planting Depth and applying with Two Coats of Aluminium Painting over a Coat of Aluminium Primer (Externally from Top of Coping),3 Nos 30 cm wide circular band with black and yellow paint starting starting from plinth lavle at a gap of 30 cm in between two bands including Writing MES Pole No. with Synthetic Enamel Paint (First Grade/quality), complete all as specified and as directed. Note :- I) Pole to supplied with two nos hole of suitable dia and suitable position for passing of street light connecting wire from JB to street light ii) Excavation and PCC will be measured and paid separately.
Supply, lay, test and commissioning of XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable in trenches/fixed to walls/poles etc and connecting/terminating by using lugs of size with aluminium conductor of 4 Core 10 Sqmm le all as directed. MAke : Havells/Finolex/kei/pOLYCAB Note :- Earth work excavation, sand cushioning and brick protection shall be measured and paid separately.
All as per item no:13 above but 4 Core 16 Sqmm
All as per item no:13 above but 3.5 Core 25 Sqmm
All as per item no:13 above but 3.5 Core 35 Sqmm
All as per item no:13 above but 3.5 Core 50 Sqmm
All as per item no:13 above but 3.5 Core 70 Sqmm
All as per item no:13above but 3.5 Core 95 Sqmm
S & F hot press moulded SMC junction / terminal box of size with internal diamensions of 200 x 140 x 95 mm with hinged door, incl provision of 4 way connector 415 Volts made out of polycarbonate or bakelite and 1 No MCB of 6 Amps with DIN bar, drilling holes for cable connections, connecting incoming and or out going cables by providing suitable of size of cable lugs/glands, fixied on pole by means of 2 SETS OF clamps made out of MS flat iron of size 25 mm x 3 mm including dismantling of old unserviceable all as specified and as directed.Make: Hensel/Syntex/C&S/nyptune
Supply and Fixing of cable jointing kit for 1.1 KV grade cable for outdoor termination heat shrinkable type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 sqmm to 95 sqmm complete including all as specifide and directed.
M & L cutting of road, hard standing made of concrete or premix carpet, WBM, soiling and morrum filling including excavation for laying of cable and pipe all as directed and making good the road/hard standing by using all old/new materials (75%)and with PCC (1:2:4)(25%) etc, required to match with the existing surface complete all as specified and directed.
S&F galvasised steel strip 32X6 mm with saddles and fixing screws on poreceling insulator/ spacer fixed at every 1 mtr length as lightening conductor on roof/wall of explosive building and joining the same with existing earth test point all as directed by Engr-in-Charge.
Advance Maintenance Free G.I. SAFE EARTHING Electrode with PIPE of not less than 50 mm outer dia( THICKNESS NOT LESS THAN -2.5MM) and two meter length, The electrode should be of galvinised (80 -100 micron) along with earth lead as Galvanised steel strip of size 32 X6 mm 7.5 m . The GI Electrode shall be pre-filled with Cristaline Conductive Material (CCM) . The GI electrode shall be surrounded with 25 kg BackFill compound to provide maximum contact between the electrode and Back Fill Compound. Backfill compound should be eco-frendly and having RoHs certification . GI Electrode Shall be tested from CPRI.The earting pit should be cover with pcc(1:2:4 , B1) cover ,of 300 x 300 mm complete all as specified and directed make ASHLOK / INDELEC/JMV /TERCEL/true power .
M&L for stright Through Joint heat shriankable type suitable for 1100 volt 50 to 95 Sqmm 3.5 core complete all as specified and directed
M&L for stright Through Joint heat shriankable type suitable for 1100 volt 16 - 35 Sqmm 3.5 core complete all as specified and directed
Supply, Installation, test and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX made out of 3.00mm thick CRCA Sheet with projected Globe roof (min 100 mm all around )for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embeded with 50X50X6mm Mild Steel Angle Iron Frame and 500 mm above the Normal Ground Level complete with internal connection with suitable size of cable ,cable lugs,and cable glands PCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Test-ing after Installation complete all as specified and comprising of the following :–
Note:i) All Internal connection between MCCB and Changeover and Bus bar shall be connected by aluminium strip of suitable size and capacity. (II) All MCCB to be connected with both side Spreader Link. The rate shall deemed to be include in the item rate iii) All existing incoming and out going cables are to be connected to the above panel with proper lugs, glands nuts, bolts etc the cost of work is deemed to be included in the above item.. (iV) The cost shall also be include the breaking of floors/walls etc including digging of trenches for removing of cables of loops and connecting to the new panel boards and making good the disturbed surfaces to match with the existing surfaces (V) The panel shall be Fabricated from a reputed firm(CPRI Approved) .
M&L for road crossing/drain crossing by adopting trench less tunneling work through specified pipe jacking method by erecting the equipment to true to the allignment and gradient by haidrolic pipe jacking technique complete including tunneling, excavation in any type of soils including hard rock, MS casing pipe 65 mm dia in any length including jointing materials to carry LT UG cables of size upto 120 Sqmm and necessary conveyance charges of machinery and other required materials in co-ordination with the concerned authorites complete all as specified and as directed.
Cement Concrete 1:3:6 TYPE C2 (40mm Graded Stone Aggregate) as Lean Concrete in Foundation of Poles, Stay Assembly, etc., including Formwork AND FOR FOUNDATION OF GI PIPE , BOLLARD LIGHT (as/if required), complete all as specified and as directed.
Cement Concrete 1:3:6 Type C1 (20mm Graded Stone Aggregate) as in Coping of Poles,side walls of cable ducts etc. including Formwork (as/if required), complete all as specified and as directed.
Supply and fixing bracket/clamps made of MS flat strips, angle iron suitable size and shape duly fabricated to be fixed with GI bolts/nuts and washer for fixing of GI bracket, PVC conduit, pole junction box or flood lights all as directed and specified
Dis connection existing LT UG cable of any size from pole/Oh line and connect the same to federpiller box by using cable glands , lugs etc as required complete all as directed
M&L for twin core 1100 volt grade aluminium service wire cross sectional area 4.0 Sqmm for connection of light complete all as specified and directed
M&L for twin core 1100 volt grade aluminium service wire cross sectional area 6.0 Sqmm for connection of light complete all as specified and directed
Fabrication and installation of GI pipe bracket made of midium Grade tubing of size 40 mm dia, duly bended by hot forgoing after filling of sand, length 1.20 mtr including providing two pair of MS flat strip clamps 40 mm x 4 mm with GI bolts nuts and washer complete all as specified and directed
Material and Labour for drawing one runs of PVC insulated unsheathed three core multi stranded copper conductor HV round cable FRLS cable of size 1.50 sq mm from cable junction box tostreet lightthrough inside the pole and bracket and exposed portion of the cable to be protected with flexible conduit complete all as specified and directed
Supply, fixing, connecting and testing energy saving, environmental friendly long life Varsatile pressure die cast aluminium alloy for housing (heat sink) with IP66 protection road way light fitting with high power LED as light source of capacity 60 watts with warranty option of 5 years with suitable driver and cable gland for maintaining ingress protection with Epoxy powder coated siemens grey finish after phosphochromate treatment, Tempered protective toughened glass,thermal shock and impact resistant fixed to the housing with SS screws , High efficiency long life LED chip in modules with lumen efficacy of >140 lm/W with PC lens and system lumen 6000. Powered by Built-in electronic LED driver with APFC (SMPS based constant current supply), lower THD, Open Circuit protection, Phase to Phase protection, Over Voltage protection, Surge Voltage protection. CCT 5700, CRI>70, THD<10%, PF>.95, IP66, IK07.Life class of 50,000 hrs @ L70, Operating Temperature:-10 TO +50 DEG.C; Input Supply Voltage Range:140-270 V, Frequency : 50-60 HZ, Driver
safety requirement standards :IS 15885-2-13, Test report to be submitted for Driver performance requirements as per IS 16104, for Photo bilogical safety norms as per : IS 16108, Certification as per LM 79 for Luminaire , LM 80 for LED Source, with all standard accessories etc, including disconnecting and taking down old existing light fittings any type/capacity from any height/position complete all as specified and as directed. Make: Bajaj Cat No.BRTFG 90W LED V3 or Havells Cat No. ENDURAPEARLPLUSSL60WLED757SASYTOPC or Wipro cat No. LR02-671-XXX-57- G2 or LUKER Cat No :- LST 60 safety requirement standards :IS 15885-2-13, Test report to be submitted for Driver performance requirements as per IS 16104, for Photo bilogical safety norms as per : IS 16108, Certification as per LM 79 for Luminaire , LM 80 for LED Source, with all standard accessories etc, including disconnecting and taking down old existing light fittings any type/capacity from any height/position complete all as specified and as directed. Make: Bajaj Cat No.BRTFG 60W LED V3 or Havells Cat No. ENDURAPEARLPLUSSL60WLED757SASYTOPC or Wipro cat No. LR02-671-XXX-57-G
sandhya enterprises
SANJEEV CONSTRUCTIONS
STANDARD AGENCIES
diesel power services (a.p)
L and S ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .