Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.8 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹13.2 L+₹43,300 (3.38%)Rejected-Finance CB 288 RING ROAD NARAINA NEW DELHI NEW DELHI 28 | NEW DELHI | DELHI | 110028 | L2 | Rejected-Finance Higher quoted amount | |
| 3 | L3₹15.2 L+₹2.4 L (18.7%)Rejected-Finance VILL POST GOASI DIST PURNEA BIHAR 854301 | PURNEA | PURNEA | BIHAR | 854301 | L3 | Rejected-Finance Higher quoted amount | |
| 4 | L4₹15.2 L+₹2.4 L (19.0%)Rejected-Finance | L4 | Rejected-Finance Higher quoted amount | |
| 5 | L5₹15.6 L+₹2.8 L (22.2%)Rejected-Finance | L5 | Rejected-Finance Higher quoted amount |
Tender Value
₹15.8 L
EMD Value
₹31,600
Closing Date
9 Jan 2023, 6:00 pmClosed
GE (AF) PURNEA
GE AF PURNEA, P.O - CHUNAPUR AIR FIELD, DIST- PURNEA BIHAR, PIN CODE 854303
PROVN OF SERVO VOLTAGE STABILIZER AND ISOLATION TRANSFORMER FOR NFS PKG 1 2 AT AIR FORCE STATION PURNEA UNDER GE (AF) PURNEA
2022_MES_568851_1
8004/E8
Open Tender
Electrical and Maintenance Works
Item Rate
90 days
PURNEA
CLASS E CATEGORY b(i)
6 documents required · 6 mandatory
₹500
Yes
GE (AF) PURNEA
₹31,600
Yes
21 Jan 2023
13 Dec 2022
11 Jan 2023
13 Dec 2022
9 Jan 2023
27 Dec 2022
Amount
Supply, installation, testing and commissioning of 100 KVA servo controlled Voltage stabilizer factory assembled floor mounted, complete (As per BIS 9815) with safety control and metering equipment mounted on common base frame comprising of following complete all as specified and as directed with the following accessories: (a) Servo controlled technology (b) Type -Three Phase, indoor, unbalanced supply, unbalance load (c) Oil cooling type (d) Testing - As per IS : 9815 (part I) (Reaffirmed-2019) and IS: 2026 (e) Input voltage - 300 V - 480 V Ph to Ph (f) Output Voltage - 415+/- 1 % (g) Frequency - 50 Hz +/- 5 % (h) metering - Digital Microprocessor based (i) Efficiency - Not less than 95 % (j) Responsible time - less than 10 mili second (k) Insulation Resistance (IR)- More than 10 Mega ohms at 500 V DC (l) Protections Provided - Over load, short circuit Protection, High/low voltage cut off, by pass arrangement, single phase preventer. (m) 1st filling of transformer oil to be included by manufacturer. (n) Copper winding for buck - boost transformer (o) Speed of correction not be less than 6v/s between phase & neutral. (p) Lossess-The no load current shall not be more than 5% of rated output current. (Makes:- M/s Instruments & Equipment Co./ M/s Voltamp / M/s APLAB / M/s Andrew Yule / M/s Brentford / M/s AE / M/s Vinek (Brand Name:-Volina). Note-(i) RATES FOR INCOMING AND OUT GOING CABLES TEMINATIONS ARE DEEMED TO BE INCLUDED IN THE QUOTED UNIT RATE . (ii) Cost of PRE-DESPATCH INSPECTION OF 100KVA SERVO VOLTAGE STABILIZER shall be deemed to be included in the quoted rate.
Supply, installation, testing and commissioning of 100 KVA Isolation transformer, 3-Phase, Oil - cooled, copper-wound including first filling of oil of requisite dielectric strength as per IS : 335, unbalance type, Primary -415 V, 3 -wire, 50Hz Delta, Secondary 415 V, 4-wire to be connected in star arrangement, designed for input voltage of 415 Volt, output voltage 415 volt, Input frequency 50 Hz+-3%, dielectric strength 2.5 KV for 60 seconds. Insulation to be more than 1000 Mega Ohms, Impedence Voltage - 3-4% complete all as specified and as directed. (Makes:- M/s Instruments & Equipment Co./ M/s Voltamp / M/s APLAB / M/s Andrew Yule / M/s Brentford / M/s AE / M/s Vinek (Brand Name:-Volina). Note-(i) RATES FOR INCOMING AND OUT GOING CABLES TEMINATIONS ARE DEEMED TO BE INCLUDED IN THE QUOTED UNIT RATE . (ii) Cost of PRE-DESPATCH INSPECTION OF 100 KVA ISOLATION TRANSFORMER shall be deemed to be included in the quoted rate.
M &L for earthing complete with copper earth plate electrode (600 x 600)mm x 3 mm thick buried direct in ground (earth pit not less than 2.25 m deep below ground level ) with top edge of the plate not less than 1.5 m below ground level connected to copper strip (25 X 3) mm by means of bolts, nuts, check buts and washers of galvanized rion and steel all as shown in electrical plate No -3 connected to earth test point including necessary excavation in any type of soil and earth work, RCC chamber cover, wire mesh, funnel , test point, GI protection pipes of 32mm dia medium grade, watering pipe of GI 20mm dia medium grade, necessary salt and charcoal etc complete and testing on completion vomplete all as specified and as directed.
S&F three Pole & neutral AC, 50 Hz, ON LOAD Change over switch 415V in sheet metal enclosures of capacity 125 Amps complete all as specified and as directed. Make:- L&T/LEGRAND/ABB/SIEMENS/GE/C&S ELECTRIC LTD/ SCHNIEDER/ HAVELLS INDIA LTD
Electro Tech Systems
shashi bhushan gupta
ALAM ENTERPRISES
BHARADWAJ BROTHERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .