Office of Engineering Services, Room No. 002, Pushp Building Ground Floor, ACTREC, Kharghar, Navi Mumbai 410210
SITC of FCU for different lab at CRI, ACTREC
2026_TMC_925706_1
HT/ET-45/SITC of FCU/2026
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
120 days
ACTREC, Kharghar
As per Tender Terms And conditions
5 documents required · 5 mandatory
₹0
₹11,298
ACTREC, Kharghar
16 Oct 2026
10 Sept 2026
19 Oct 2026
10 Sept 2026
16 Oct 2026
10 Sept 2026
10 Sept 2026 - 16 Sept 2026
17 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Chilled water Fan Coil Unit | - | - | - | - |
| 2 | Supply, Installation, Testing and Commissioning of chilled water Fan Coil Unit. The Fan Coil Unit shall be a factory-assembled, tested, and ready-to-install unit suitable for wall mounting at high level. Units shall comply with relavant standards for performance and safety. Cooling Coil: Multi-row copper tubes with hydrophilic aluminum fins, high-efficiency, seamless construction. Casing: High quality, powder-coated galvanized steel or ABS plastic body with corrosion protection. Drain pan: ABS/stainless steel with 7mm PE insulation to prevent condensation. Fan type: Dynamically balanced centrifugal or tangential fan, low-noise design. Motor: Single-phase, multi-speed motor with internal thermal overload protection. Coil shall be designed for standard working press of 1.6 MPa(16bar) and the test pressure is 3.3MPa(33bar). Filters: Type: Washable synthetic fiber or nylon mesh filter. Thermostat: Microprocessor-based wireless remote controller with LCD display; mode selection (cool/fan/dry/auto), fan speed, temperature setting. Accessories : Pre-asembeled valve station including Motorized 2-way valve with actuator(simens make). Strainer, ball valve with tray. .It shall also have RS485 Modbus communication function for BMS control .Supply & laying of control wiring & power cabling from FCU to local control panel / thermostat and motorized valve actuator, with conduits and accessories. Unit should be Eurovent certified. | - | - | - | - |
| 3 | Decorative Hiwall- 1.5 TR nominal capacity with 600 cfm air quanity | 9 | Nos | - | - |
| 4 | Chilled water piping PPR-CT (FCU units) | - | - | - | - |
| 5 | SITC of PP-RCT (PPR-CT) piping for chilled water circulation. The PP-RCT piping shall conform to ISO 15874 and DIN 8077/8078 standards and shall be manufactured from pressure-rated PP-RCT material of minimum PN 20 rating. Pipes and fittings shall be sourced from the same manufacturer and joined by thermal socket fusion using approved fusion tools; threaded joints shall be permitted only at equipment, valve, and accessory connections using suitable transition fittings with brass inserts. Adequate supports, anchors, guides, and expansion provisions shall be provided in accordance with the manufacturer's recommendations. All chilled water piping shall be insulated with closed-cell elastomeric insulation of minimum 19 mm thickness for pipes hydrostatically tested at 1.5 times the working pressure and maintained for a minimum of two hours without any leakage or pressure loss before insulation and commissioning. 25mm or as per requirement of Hiwall units | 60 | RMT | - | - |
| 6 | SITC PVC drain pipe having pressure holding of 6kg/cm2 Drain piping complete with all accessories with 9mm Nitrile Rubber Insulation. | - | - | - | - |
| 7 | 25 mm Dia. | 30 | RMT | - | - |
| 8 | SITC of power cable for Hiwall units from indoor armoured to main MCB as per the requirment and as per instructed and as directed by OIC-ES | 30 | RMT | - | - |
| 9 | Providing of Core cut in existing RRC wall/Slab up to 15'' thickness is instructed by EIC. | 9 | Nos | - | - |
| 10 | Dismantling and safe removal of existing 2 TR Hi-Wall Split unit including outdoor, piping, insulation, drain piping, control wiring, supports and accessories, complete with shifting of dismantled material to designated location and making good of dismantled area as per site conditions and instructions of Engineer-in-Charge. | 9 | Nos | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.79 MB
TD.pdf
Tender Documents • 1.94 MB
BOQ_972798.xls
BOQ • 0.25 MB
AnnexureForm.xls
Additional Documents • 0.12 MB
ET45EXT.pdf
PDF • 0.40 MB
Corrigendum.pdf
PDF • 0.41 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .