Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.4 LAccepted-AOC | L1 | Accepted-AOC AWARDE BY L1 FIRM M/S GANGANAGAR ENTERPRISES | |
| 2 | L2₹27.8 L+₹2.8 L (11.2%)Rejected-Finance 31 TILAK NAGAR SRI GANGANAGAR 335001 RAJ | GANGANAGAR | RAJASTHAN | 335001 | L2 | Rejected-Finance L2 FOR REJECTED | |
| 3 | L3₹28.4 L+₹3.4 L (13.6%)Rejected-Finance | L3 | Rejected-Finance L3 FOR REJECTED | |
| 4 | L4₹28.4 L+₹3.4 L (13.8%)Rejected-Finance RM 01 RIDHISIDHI I SRI GANGANAGAR 335001 RAJ | SRI GANGANAGAR | SRI GANGANAGAR | RAJASTHAN | 335001 | L4 | Rejected-Finance L4 FOR REJECTED | |
| 5 | L5₹30.0 L+₹5.0 L (20.1%)Rejected-Finance | L5 | Rejected-Finance L5 FOR REJECTED |
Tender Value
Refer Docs
EMD Value
₹62,400
Closing Date
10 Apr 2021, 6:00 pmClosed
HQ COMMANDER WORKS ENGINEER SRI GANGANAGAR
HQ CWE POST BOX 48 SRI GANGANAGAR-335001 (Rajasthan)
CA No CWE SGNR 111 of 2020-21 SPECIAL REPAIRS TO LT PANEL AND CONVERSION OF LT OH LINE INTO UNDER GROUND LT CABLE WITH ADHESIVE WORK FOR AT SRI GANGANAGAR MILITARY STATION
2021_MES_428855_1
CA NO. CWE SGNR - 111 OF 2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
SRI GANGANAGAR
CLASS d
CATEGORY B(I)
10 documents required · 10 mandatory
₹500
₹62,400
27 Apr 2021
13 Mar 2021
13 Apr 2021
13 Mar 2021
10 Apr 2021
27 Mar 2021
Amount
Supply & Fixing and testing of LT cable 1100 volts grade XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor suitable for earthed system of size 185 sq mm 3.5/4 core in trenches, on poles and in ducts complete all as specified and directed by Engr in charge. (Excavation, earth work, bricks and sand cushioning shall be measured and paid separately) complete all as specified and directed by Engr-in-Charge.
All per ietm Srl No 01 here but for size 95 sq mm 3½ core complete all as specified and directed by Engr-in-Charge.
All per ietm Srl No 01 here but for size 70 sqmm 3½ core complete all as specified and directed by Engr-in-Charge.
All per ietm Srl No 01 here but for size 50 sq mm 3½ core complete all as specified and directed by Engr-in-Charge.
All per ietm Srl No 01 here but for size 35 sq mm 3½ core complete all as specified and directed by Engr-in-Charge.
All per ietm Srl No 01 here but for size 25 sq mm 4core complete all as specified and directed by Engr-in-Charge.
All per ietm Srl No 01 here but for size 16 sq mm 4 core complete all as specified and directed by Engr-in-Charge.
All per ietm Srl No 01 here but for size 16 sq mm 2 core complete all as specified and directed by Engr-in-Charge.
All per ietm Srl No 01 here but for size 10 sq mm 4 core complete all as specified and directed by Engr-in-Charge.
All per ietm Srl No 01 here but for size 10 sq mm 2 core complete all as specified and directed by Engr-in-Charge.
Supply, fixing and testing of LT flexible FR PVC insulated round sheathed, Aluminium (flexible) cable, 1100 volt conforming to IS-694 suitable for on poles and in ducts, size of sqmm 3 core 2.5, complete all as specified and directed by Engr-in-Charge.
Supplying, installing, commissioning and testing of factory made LT Panel board of size 1.2x1.2x0.6m ,out door CPRI approved of cubical type made out of 3.15 mm thick CRCA sheet confirming to IS-8623 out dooor type totally enclosed double door hinged type front & rear opening weather proof dust vermin proof with canopy slope tope powder coated painting locking arrangement, magnetic catch as directed entry holes and glands of siutable size of incoming/outgoing cable mounted on including MS angle iron stand fabricated out of 50x50x6mm angle iron frame with a clearance of at least 0.45 mtr above gd level and 0.3 mtr below gd level incling reqd PCC for foundation and copping , internal coper control wiriing suitable size for instrument/indicators etc suitable size of copper strip for power cable connection from copper bus bar of high quality electrical grade of rating 1.5 times for incomer including removing all panel connection and complete all as specified and directed by Engr-in-Charge. INCOMING: (a) Micro processor based release MCCB 400A, 36KA, 4 pole , 415 volt 50HZ . -01 No (b) Set of three phase indicating lamps-01 Set. (c) Panel mounted LCD display meter in 96x96 sqmm flush mounted case accuracy class 1.0 to o.5 to measure Voltage,Current,Frequency ,power factor,,Power ,THD ,30 days load survey relays with Rs 485 with suitable size of CTsMake HPL cat part No emifis plus / equiavalent make OUTGOING (a) MCCB 4 pole, 415 volts, 250 Amp with breaking cap 25 KA-02 Nos ,TAB2 Adjustable tharmal & Fixed Magnatic Type (b) MCCB 4 pole, 415 volts, 63 Amp with breaking cap 25 KA-05 Nos ,TAB2 Adjustable tharmal & Fixed Magnatic Type Note :- LT Bus bar 3 phase and neutral made out of copper strip of capacity and rating 1.1 times of incomer breaker -01 set. Note :- LT Bus bar 3 phase and neutral made out of copper strip of capacity and rating 1.1 times of incomer breaker -01 set.
All as per item srl No 12 here but for comprising of complete all as specified and directed by Engineer-in-Charge. INCOMING: (a) Micro processor based release MCCB 400A, 36KA, 4 pole , 415 volt 50HZ . -01 No (b) Set of three phase indicating lamps-01 Set. (c) Panel mounted LCD display meter in 96x96 sqmm flush mounted case accuracy class 1.0 to o.5 to measure Voltage,Current,Frequency ,power factor,,Power ,THD ,30 days load survey relays with Rs 485 with suitable size of CTsMake HPL cat part No emifis plus / equiavalent make OUTGOING (a) MCCB 4 pole, 415 volts, 200 Amp with breaking cap 25 KA-01 Nos ,TAB2 Adjustable tharmal & Fixed Magnatic Type (b) MCCB 4 pole, 415 volts, 63 Amp with breaking cap 25 KA-07 Nos ,TAB2 Adjustable tharmal & Fixed Magnatic Type Note :- LT Bus bar 3 phase and neutral made out of copper strip of capacity and rating 1.1 times of incomer breaker -01 set.
M&L for earthing of electric equipments with galvanized steel earth plate electrode 600x600x6mm thickness not less than 6mm thick, buried directly in ground (earth plato not less than 2.25 metrs deep below normal ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level, connecting to and including galvanized iron strip 32x6mm as earthing lead by means of galvanized iron bolts, nuts, check nuts and washers, check nuts of GI steel all as shown in electric plate no 3 in SSR part-I (2009) connected to earth test point made out of aluminum of size 75x75x10 mm all as specified and indicated complete and including charcoal dust, salt etc and GI protection pipe, medium grade 40 mm and GI watering pipe 20 mm, medium grade with with funnel and wire mesh, 40 mm thick pre cast RCC 1:1 1/2:3 (normal mix) cover reinforced with XPM weight not less than 4 kg/sqm with suitable handle of 6mm dia MS bar and angle iron 40x40x3 mm frame for cover, PCC 1:1 1/2:3 (normal mix) pit, excavation and earth work in any type of soil and connected complete all as specified and directed by Engineer-in-Charge.
All as per item No 12 but comprising of following :- INCOMING (a) Micro processor based release MCCB 250A, 36KA, 4 pole , 415 volt 50HZ . -01 No (b) Set of three phase indicating lamps-01 Set. (c) Panel mounted LCD display meter in 96x96 sqmm flush mounted case accuracy class 1.0 to o.5 to measure Voltage,Current,Frequency ,power factor,,Power ,THD ,30 days load survey relays with with suitable size of CTsMake HPL cat part No emifis plus / equiavalent make OUTGOING (a) MCCB 4 pole, 415 volts, 63 Amp with breaking cap 25 KA-05 Nos ,TAB2 Adjustable tharmal & Fixed Magnatic Type Note :- LT Bus bar 3 phase and neutral made out of copper strip 1 No. capacity and rating 1.1 times of incomer breaker -01 set.
All as per item No 12 but comprising of following :- INCOMING (a) Micro processor based release MCCB 250A, 36KA, 4 pole , 415 volt 50HZ . -01 No (b) Set of three phase indicating lamps-01 Set. (c) Panel mounted LCD display meter in 96x96 sqmm flush mounted case accuracy class 1.0 to o.5 to measure Voltage,Current,Frequency ,power factor,,Power ,THD ,30 days load survey relays with with suitable size of CTsMake HPL cat part No emifis plus / equiavalent make OUTGOING (a) MCCB 4 pole, 415 volts, 63 Amp with breaking cap 25 KA-05 Nos ,TAB2 Adjustable tharmal & Fixed Magnatic Type Note :- LT Bus bar 3 phase and neutral made out of copper strip of capacity and rating 1.1 times of incomer breaker -01 set.
S&F on pole/wall/in panel/with fabrication of stand, sheet metal enclosure, Bus bar chamber consisting 4 pole 300 Amp 415 volts aluminium busbar suitable for connecting cable as a junction including connecting of cables with suitable size aluminium thimles, cable glands including earth work, PCC &connected items for fixing complete all as specified and directed by Engr-in-Charge.
S&F on pole/wall/in panel/with fabrication of stand, sheet metal enclosure, Bus bar chamber consisting 4 pole 200 Amp 415 volts aluminium busbar suitable for connecting cable as a junction including connecting of cables with suitable size aluminium thimles, cable glands including earth work, PCC &connected items for fixing complete all as specified and directed by Engr-in-Charge.
M&L for preparation of old surface of steel tubular pole any size and type of poles and applying two coat aluminium paint over red oxide primer and applying two coats of synthetic enamel paint with black & white or yellow colour strips 30cm each up to 1.5 mtr height from top of PCC foundation block and numbering of poles with synthetic enamel paint white in 80 mm high letters 150 mm above the top strip complete all as spd and directed by Engr in charge.
Dismantling of cross-arms of M.S. channel or angle sections etc and complete all as specified and directed by Engineer-in-Charge.
Dismantling of ACSR conductor of any size and capacity including connected items from over head ines complete all as specified and directed by Engineer-in-Charge.
S & F in replacement street light timer, single phase for 8KW light load comprising of nature switch, contactor and MCB housed in a pole mountable enclosure complete all as specified and directed by Engineer-in-Charge. (Make : Swadeep 02EC 8KW1P/ or equivalent in / Indo Asain/ Bajaj/L&T/C&S.
S & F in replacement street light timer, Three phase for 8 KW light load comprising of nature switch, contactor and MCB housed in a pole mountable enclosure complete all as specified and directed by Engineer-in-Charge.
Supply and fixing pole mounting box of size 300x200x105mm, shockproof, dustproof, wheatherproof, including pole mounting arrangement such as clamp made of MS flat 25x3mm size & nut bolts and washer, four way connector suitable for three phase supply, MCB SP 2.5A B cure, as per IS 10192 including taking down the old unservicable pole mounting box complete all as specified and directed by Engr-in-Charge.
Excavation in trenches, not exc 1.5 m wide and n. exc 1.5 m depth; or n exc 10 Sqm on plan and n exc 1.5 m in depth for foundations of poles, struts, stays etc. or laying underground cable etc. in soft/loose soil, & getting out including taking out old brick or precast cable cover for reuse complete all as specified and directed by Engineer-in-Charge.
M & L cement concrete 1:3:6 type C-1 using 20mm graded stone aggregate for pole pedestal (PCC) including necessary form work etc complete all as specified.
Returning, filling in, excavated soil including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified and directed by Engineer-in-Charge
Removal of excavated surplus soil to a distance n.exc 50m and depositing where directed at level not exceeding 1.5 m above the starting point complete all as specified and directed by Engr-in-Charge.
M & L for sand cushioning with dry coarse sand to under ground cable around the cable after laying the cable complete all as specified and directed by Engineer-in-Charge. Note : Thickness after punning shall be considered for payment.
M & L for brick protection with old size sub class 'B' bricks laid flat , length of bricks across the route of underground cable complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement GI pipe 40 mm bore light grade for protection of cable laid under the road / laid under the floor or in trenches complete all as specified and directred by Engineer-in-Charge.
Supply and fix in replacement GI pipe 80 mm bore light grade for protection of cable laid under the road / laid under the floor or in trenches complete all as specified and directred by Engineer-in-Charge.
M&L for boring holes under road/pavement/hard standing or any other situation by manual means suitable for passing GI pipe 80 mm bore and making good both the ends complete all as specified and directed by Engr-in-Charge. --------------------------------------------------------------------------------------------------- Note : A sum of Rs. 61,250.00 will be deducted on account of credit for dismantled/ demolished / taken down material. Please refer details on Srl Page No. 21 (Schedule of Credit) of Tender document
Singla Electricals
m/s G.S. Enterprises
KHANNA CONSTRUCTIONS
DASHMESH ENTERPRISES
BHARAT NIRMAN INFRASTRUCTURE COMPANY
Kaul Enterprises
UNITED ENGINEERING CORPORATION
VISHAV CONSTRUCTIONS
M/S BUDHRAM BISHNOI
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .