CWE DELHI CANTT
HQ CWE DELHI CANTT 110010
REPAIR AND REPLACEMENT AND OVERHAULING OF WATER COOLED CENTRAL AC PLANTS, DX TYPE CENTRAL AC PLANT, REWINDING OF COMPRESSOR MOTORS, REPLACEMENT OF VALUES AND OTHER CONNECTED MISC E/M WORKS AT BHDC UNDER GE (EAST) DELHI CANTT-10
2026_MES_797524_1
CWE/D-72/2026-27
Open Tender
Civil Works
Item Rate
330 days
DELHI CANTT
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
GE EAST DELHI CANTT
₹1.3 L
Yes
5 Nov 2026
5 Nov 2026
4 Dec 2026
5 Nov 2026
3 Dec 2026
26 Nov 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Annual maintenance contract for Air Conditioning plant and other equipment for the following :-
Centrifugal pumps of cap 10 HP - 06
Centrifugal pumps of cap 15 HP - 06
Screw chiller of cap 75 TR - 06
Note 1 :
(i) Checking the functioning of Chiller unit/Air Handling unit/Pumps/Cooling tower/Controls and all such equipment
covered under the contract.
(ii) Free replacing of defective/worn-out parts with new or repaired parts for compressor/thermostat/cut outs based on
our assessment.
(iii) Repairing of equipment as listed in the equipment list at site/service station as the case may be.
(iv) Descaling of condensers/chemical cleaning of evaporator coils/replacement of pre-filters based on our assessment
and working parameters of the plant.
(v) Replenishing refrigerant gas and compressor oil in the system arising out of system defect, excluding sealed
compressor.
(vi) Checking of compressor for its proper working.
(vii) Annual pumping-down and restarting as and when required.
(viii) Checking of Microprocessor control panel, control boards, transducers of packaged chillers/condensing unit for their
correctness and replace if necessary.
(ix) Replacing of parts due to normal wear and tear. | 11 | Per Month | 100 | ₹1,100 |
| 1.03 | (v) In case of any minor fault in the machineries of Central AC plant due to which the plant is put off more than 12 hours the following penalties shall be recovered from the contractor :-
(vi) Rs. 10000/- per day will be recovered from the contractor for non rectification of defect/replacement of any unserviceable spares after 12 hours from lodging of complaint telephonically or verbaly.
(vii) Thereafter Rs. 10000/- will be added every day till rectification of fault/replacement of unserviceable spares as directed. | - | - | - | - |
| 1.04 | (viii) In case of any minor fault in the machineries of Central AC plant due to which the plant is put off more than 12 hours the following penalties shall be recovered from the contractor :-
(ix) Rs. 10000/- per day will be recovered from the contractor for non rectification of defect/replacement of any unserviceable spares after 12 hours from lodging of complaint telephonically or verbaly.
(x) Thereafter Rs. 10000/- will be added every day till rectification of fault/replacement of unserviceable spares as directed. | - | - | - | - |
| 2 | Dismantling compressor of central AC plant for overhauling complete with connected copper pipe line and loading unloading mechanism & pump down the existing refrigerant in separate cylinder, disconnecting of electric motor of compressor, refrigerant line, gauges pipe and carry out the general over hauling of compressor, compressor model:- SMC/4/100, Make:- Accel (R-22) including replacement of springs, aluminium washer packing, screw, lath work, cleaning detergent, cotton waste, changing of compressor oil etc and cleaning the suction filter, oil filter, replacing the defective parts compete system for safe guard the gas with self pumping down system or with total recovery unit system incld. following operation complete all as specified & directed.
(i) Charging of nitrogen Gas in unit & complete system at 300 psi pressure and checking of any dropping of pressure/ leakage up to 72 Hrs after replacement of compressor & rectification of leakage if any.
(ii) Vaccumisation of complete system for minimum 2 days for dropping of vacuum pressure & rectification of leakage if any.
(iii) Charging of complete system with R-22 gas for maintaining the system pressure up to HP - 175 psi & LP - 65 psi....
(iv) Measure the inlet and outdoor temperature of Chiller unit for performance checking and maintaining temp. as per require site.
(v) Testing & commissioning of compressor after completion.
Note:-
(a) Spares of compressor shall be measured and paid separetely under respective item of this schedule (Sr No. 2.01 to 2.19).
(b) Any minor items required for overhauling except described here-in-after shall be supplied by the contractor with out any extra cost to the deptt and the rates for the same shall deemed to be included in the quoted rates. | 4 | Each Job | - | - |
| 2.01 | Supply only PISTON with PIN & Rings- Nos -04 Nos(ACCEL Part No. ASL1018R) complete all as specified and directed. SMC/4/100, | 4 | Each set | - | - |
| 2.02 | Supply only CYLLENDER with suction valve -04 Nos(R-22) (ACCEL Part No. ASL1019A) complete all as specified and directed. SMC/4/100, | 4 | Each set | - | - |
| 2.03 | Supply only OIL pump (ACCEL Part No. ASL1011A) complete all as specified and directed. SMC/4/100, | 4 | Each | - | - |
| 2.04 | Supply only Discharge valve assembly (R-22) (ACCEL Part No. ASL1020 A) complete all as specified and directed. SMC/4/100, | 4 | Each Set | - | - |
| 2.05 | Supply only pressure regulation valve (ACCEL Part No. ASL1022 R) complete all as specified and directed. SMC/4/100, | 4 | Each Set | - | - |
| 2.06 | Supply only Set of gasket (ACCEL Part No. ASL1453) complete all as specified and directed. SMC/4/100, | 4 | Each Set | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.54 MB
TENDERPAGES.pdf
Tender Documents • 2.20 MB
BOQ_894615.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .