Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹36.3 LAccepted-AOC | ₹36.3 L Quoted ₹41.2 L | L1 | Accepted-AOC LOWEST BIDDER |
| 2 | L2₹47.9 L+₹6.7 L (16.3%)Rejected-Finance SHIV BARI ROAD NEAR KASUMAL HOTEL BIKANER 334003 RAJASTHAN | BIKANER | BIKANER | RAJASTHAN | 334003 | ₹47.9 L+₹6.7 L (16.3%) | L2 | Rejected-Finance Other than Lowest |
| 3 | L3₹50.8 L+₹9.5 L (23.2%)Rejected-Finance | ₹50.8 L+₹9.5 L (23.2%) | L3 | Rejected-Finance Other than Lowest |
| Sl No | Description | Qty | Unit | M/s Rohit Construction Co. L2 | SHREE BHAGWATI ENTERPRISES L1 | Akarsha Enterprises L3 |
|---|---|---|---|---|---|---|
| 1.00 | Caliberation/Servicing/Overhauling & testing and commissioning of factory manufactured, HT 11 KV Phase 3 wire 50 C/S 400 Amps, 18.4 KA single panel switch board, vertical isolation and horizental draw out type vaccum circuit breaker (VCB) confirming to IS-13118, EIC-56 totally enclosed, single busbar floor mounting metal clad indoor extendible fully interlock complete comprising the following :-
(a) CTs primary current injection test .
(b) IR values of CTs
(c) Ratio test of PTs and IR value
(d) Protection relays testing through secondary current injection kit
(e) Voltmeter, ammeter functional tesing
(f) Breaker tesing for tripping time, closing time, contact resistance values and physically healthyness of Vaccum interuptor.
Note :- 1. Wiring of Control Panels of VCBs, wiring of WTI, OTI, CTs, PTs will be including quoted rate.
2. Contractor will be responsible for arranging the expert for checking and rectification/Alteration of control wiring of safety relays. | 26 | Each Job | 5,000 ₹1,30,000 | 3,000 ₹78,000 Lowest | 6,500 ₹1,69,000 |
| 2.00 | Taking down and dismounting defective transformer 33/11 KV of capacity 0.750 MVA to 1.00 MVA from foundation by using crane and transporting to workshop or factory (authrorised for such repair) for repair after disconnecting HV, LV side HT cable or HT aluminium conductor, dismantling the same for repair & renewal of unserviceable parts and reassembling complete, spray painting with two coats of synthetic enamelled grey paint after preparation of old surface writing MES No with white paint of suitable size letter and transporting to back from workshop to site, installation on plate form, testing & commissioning to entire satisfaction complete all as specified and directed by Engr -in- Charge. | 1 | Each Job | 30,000 ₹30,000 | 25,000 ₹25,000 Lowest | 45,000 ₹45,000 |
| 3.00 | Taking down and dismounting defective transformer 33/11 KV of capacity 1.6 MVA to 5.0 MVA from foundation by using crane and transporting to workshop or factory (authrorised for such repair) for repair after disconnecting HV, LV side HT cable or HT aluminium conductor, dismantling the same for repair & renewal of unserviceable parts and reassembling complete, spray painting with two coats of synthetic enamelled grey paint after preparation of old surface writing MES No with white paint of suitable size letter and transporting to back from workshop to site, installation on plate form, testing & commissioning to entire satisfaction complete all as specified and directed by Engineer-in-Charge. | 1 | Each Job | 40,000 ₹40,000 Lowest | 80,000 ₹80,000 | 60,000 ₹60,000 |
| 4.00 | S&F post insulator, porcelain, vitreous, with hardware fitting complete for 33000 volts grade and including taking down old unserviceable post insulator complete all as specified and directed by Engineer-in-Charge. | 8 | Each | 500 ₹4,000 | 450 ₹3,600 Lowest | 1,800 ₹14,400 |
| 5.00 | Supply & Fixing of lightening arrestors 33 KV, 10 KA station type Class including all clamps, nuts, bolts and washers and connection to earth with 32x6mm GI strip complete and including taking down old unserviceable LA complete all as specified and directed by Engineer-in-Charge. | 1 | Set of Three | 12,000 ₹12,000 | 4,500 ₹4,500 Lowest | 10,000 ₹10,000 |
| 6.00 | M&L for switch air break gang operated triple pole mechanically operated, mounted on HT insulators (9 insulators type & 6 insulators for DO with horizontal operated) and MS galvanized steel frame with operating mechanism worked from ground level including operating rod for current rating up to 400 Amps 33000 volts complete with locking arrangement MS clamps, bolts and nuts and washers etc also including drop out expulsion type of fuses with fuse barrels of required capacity to suit load at site including two coats of aluminum paint over a coat of red oxide primer on MS work and including taking down old switch air break gang operated complete all as specified and directed by Engineer-in-Charge. Note :- stack for fixing with poles shall be measure and paid separately) | 1 | Each Set | 50,000 ₹50,000 | 15,500 ₹15,500 Lowest | 23,500 ₹23,500 |
| 7.00 | M&L for switch air break gang operated triple pole mechanically operated, mounted on HT insulators (9 insulators type & 6 insulators for DO with horizontal operated) and MS galvanized steel frame with operating mechanism worked from ground level including operating rod for current rating up to 400 Amps 11000 volts complete with locking arrangement MS clamps, bolts and nuts and washers etc also including drop out expulsion type of fuses with fuse barrels of required capacity to suit load at site including two coats of aluminum paint over a coat of red oxide primer on MS work and including taking down old switch air break gang operated complete all as specified and directed by Engineer-in-Charge. Note :- stack for fixing with poles shall be measure and paid separately | 2 | Each Set | 20,000 ₹40,000 | 15,500 ₹31,000 Lowest | 16,500 ₹33,000 |
| 8.00 | Material and labour for switch air break gang operated triple pole mechanically operated, mounted on HT insulators (9 insulators Vertical type operated) and MS galvanized steel frame with operating mechanism worked from ground level including operating rod for current rating up to 400 Amps 11000 volts complete with locking arrangement MS clamps, bolts and nuts and washers etc also including drop out expulsion type of fuses with fuse barrels of required capacity to suit load at site including two coats of aluminum paint over a coat of red oxide primer on MS work and including taking down old switch air break gang operated complete all as specified and directed by Engineer-in-Charge. Note :- stack for fixing with poles shall be measure and paid separately. | 3 | Each Set | 12,000 ₹36,000 | 11,500 ₹34,500 Lowest | 14,000 ₹42,000 |
| 9.00 | Material and labour for switch air break gang operated triple pole mechanically operated, mounted on HT insulators (9 insulators Vertical type operated) and MS galvanized steel frame with operating mechanism worked from ground level including operating rod for current rating up to 200 Amps 11000 volts complete with locking arrangement MS clamps, bolts and nuts and washers etc also including drop out expulsion type of fuses with fuse barrels of required capacity to suit load at site including two coats of aluminum paint over a coat of red oxide primer on MS work and including taking down old switch air break gang operated complete all as specified and directed by Engineer-in-Charge. Note :- stack for fixing with poles shall be measure and paid separately | 8 | Each Set | 11,000 ₹88,000 | 10,500 ₹84,000 | 1,300 ₹10,400 Lowest |
| 10.00 | S&F annunciator relay box consisting of 4/6 block 18 to 90 volts DC complete in existing VCB of CG make and including taking down old relay box of any size complete all as specified and directed by Engineer-in-Charge. | 3 | Each | 6,000 ₹18,000 | 8,500 ₹25,500 | 3,800 ₹11,400 Lowest |
Tender Value
₹50 L
EMD Value
₹1 L
Closing Date
29 Nov 2025, 6:00 pmClosed
CWE (A) Jaisalmer
HQ CWE ARMY JAISALMER 345001 RAJASTHAN
REPAIR /MAINT OF 33/11 KV SUB STATION AT JAISALMER STATION UNDER GE (A) JAISALMER.
2025_MES_738181_1
84372/C/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
JAISALMER
AS PER NIT
8 documents required · 8 mandatory
₹500
GE ARMY JAISALMER
₹1 L
Yes
30 Dec 2025
3 Nov 2025
1 Dec 2025
3 Nov 2025
29 Nov 2025
24 Nov 2025
3 Nov 2025 - 10 Nov 2025
Amount
Caliberation/Servicing/Overhauling & testing and commissioning of factory manufactured, HT 11 KV Phase 3 wire 50 C/S 400 Amps, 18.4 KA single panel switch board, vertical isolation and horizental draw out type vaccum circuit breaker (VCB) confirming to IS-13118, EIC-56 totally enclosed, single busbar floor mounting metal clad indoor extendible fully interlock complete comprising the following :- (a) CTs primary current injection test . (b) IR values of CTs (c) Ratio test of PTs and IR value (d) Protection relays testing through secondary current injection kit (e) Voltmeter, ammeter functional tesing (f) Breaker tesing for tripping time, closing time, contact resistance values and physically healthyness of Vaccum interuptor. Note :- 1. Wiring of Control Panels of VCBs, wiring of WTI, OTI, CTs, PTs will be including quoted rate. 2. Contractor will be responsible for arranging the expert for checking and rectification/Alteration of control wiring of safety relays.
Taking down and dismounting defective transformer 33/11 KV of capacity 0.750 MVA to 1.00 MVA from foundation by using crane and transporting to workshop or factory (authrorised for such repair) for repair after disconnecting HV, LV side HT cable or HT aluminium conductor, dismantling the same for repair & renewal of unserviceable parts and reassembling complete, spray painting with two coats of synthetic enamelled grey paint after preparation of old surface writing MES No with white paint of suitable size letter and transporting to back from workshop to site, installation on plate form, testing & commissioning to entire satisfaction complete all as specified and directed by Engr -in- Charge.
Taking down and dismounting defective transformer 33/11 KV of capacity 1.6 MVA to 5.0 MVA from foundation by using crane and transporting to workshop or factory (authrorised for such repair) for repair after disconnecting HV, LV side HT cable or HT aluminium conductor, dismantling the same for repair & renewal of unserviceable parts and reassembling complete, spray painting with two coats of synthetic enamelled grey paint after preparation of old surface writing MES No with white paint of suitable size letter and transporting to back from workshop to site, installation on plate form, testing & commissioning to entire satisfaction complete all as specified and directed by Engineer-in-Charge.
S&F post insulator, porcelain, vitreous, with hardware fitting complete for 33000 volts grade and including taking down old unserviceable post insulator complete all as specified and directed by Engineer-in-Charge.
Supply & Fixing of lightening arrestors 33 KV, 10 KA station type Class including all clamps, nuts, bolts and washers and connection to earth with 32x6mm GI strip complete and including taking down old unserviceable LA complete all as specified and directed by Engineer-in-Charge.
M&L for switch air break gang operated triple pole mechanically operated, mounted on HT insulators (9 insulators type & 6 insulators for DO with horizontal operated) and MS galvanized steel frame with operating mechanism worked from ground level including operating rod for current rating up to 400 Amps 33000 volts complete with locking arrangement MS clamps, bolts and nuts and washers etc also including drop out expulsion type of fuses with fuse barrels of required capacity to suit load at site including two coats of aluminum paint over a coat of red oxide primer on MS work and including taking down old switch air break gang operated complete all as specified and directed by Engineer-in-Charge. Note :- stack for fixing with poles shall be measure and paid separately)
M&L for switch air break gang operated triple pole mechanically operated, mounted on HT insulators (9 insulators type & 6 insulators for DO with horizontal operated) and MS galvanized steel frame with operating mechanism worked from ground level including operating rod for current rating up to 400 Amps 11000 volts complete with locking arrangement MS clamps, bolts and nuts and washers etc also including drop out expulsion type of fuses with fuse barrels of required capacity to suit load at site including two coats of aluminum paint over a coat of red oxide primer on MS work and including taking down old switch air break gang operated complete all as specified and directed by Engineer-in-Charge. Note :- stack for fixing with poles shall be measure and paid separately
Material and labour for switch air break gang operated triple pole mechanically operated, mounted on HT insulators (9 insulators Vertical type operated) and MS galvanized steel frame with operating mechanism worked from ground level including operating rod for current rating up to 400 Amps 11000 volts complete with locking arrangement MS clamps, bolts and nuts and washers etc also including drop out expulsion type of fuses with fuse barrels of required capacity to suit load at site including two coats of aluminum paint over a coat of red oxide primer on MS work and including taking down old switch air break gang operated complete all as specified and directed by Engineer-in-Charge. Note :- stack for fixing with poles shall be measure and paid separately.
Material and labour for switch air break gang operated triple pole mechanically operated, mounted on HT insulators (9 insulators Vertical type operated) and MS galvanized steel frame with operating mechanism worked from ground level including operating rod for current rating up to 200 Amps 11000 volts complete with locking arrangement MS clamps, bolts and nuts and washers etc also including drop out expulsion type of fuses with fuse barrels of required capacity to suit load at site including two coats of aluminum paint over a coat of red oxide primer on MS work and including taking down old switch air break gang operated complete all as specified and directed by Engineer-in-Charge. Note :- stack for fixing with poles shall be measure and paid separately
S&F annunciator relay box consisting of 4/6 block 18 to 90 volts DC complete in existing VCB of CG make and including taking down old relay box of any size complete all as specified and directed by Engineer-in-Charge.
S&F master trip relay 24 Volts DC complete in existing VCB of CG make and including taking down old unserviceable relay complete all as specified and directed by Engineer-in-Charge.
S&F master trip relay 110 Volts DC complete in existing VCB of CG make and including taking down old unserviceable relay complete all as specified and directed by Engineer-in-Charge.
S&F earth fault over current relay 24 Volts DC complete in existing VCB of CG make and including taking down old unserviceable relay complete all as specified and directed by Engineer-in-Charge.
S&F auxilary relay 110 Volts DC complete in existing VCB of CG make and including taking down old unserviceable relay complete all as specified and directed by Engineer-in-Charge.
S&F auxilary relay 24 Volts DC complete in existing VCB of CG make and including taking down old unserviceable relay complete all as specified and directed by Engineer-in-Charge.
S&F Voltmeter digital type for ACB/VCB any range complete and including taking down old unserviceable voltmeter complete all as specified and directed by Engineer-in-Charge.
S&F Ameper meter Digial type for ACB/VCB any range complete and including taking down old unserviceable amp meter complete all as specified and directed by Engineer-in-Charge.
S&F indication lamp RYB with holder complete 110 Volts DC complete in existing VCB of CG make and including taking down old unserviceable lamp complete all as specified and directed by Engineer-in-Charge.
S&F HRC fuse 5 Amps complete and including taking down old unserviceable fuse complete all as specified and directed by Engineer-in-Charge.
S&F multi functional meter for 11 KV VCB complete in existing VCB of CG make and including taking down old unserviceable multifunctional meter complete all as specified and directed by Engineer-in-Charge.
S&F over current and earth fault IDMT protection relay (digital relay) type CGI 14 N,75/250 Volts complete necessary connection and testing in existing VCB of CG make and including taking down old unserviceable IDMT protection relay complete all as specified and directed by Engineer-in-Charge.
Supply and fixing universal motor (spring charge for 11 KV VCB) 220 volt AC/DC type PMR5 in existing VCB of CG and including taking down old unserviceable motor complete all as specified and directed by Engineer-in-Charge. Make : - Delco or equivalent make as approved by GE.
S&F of PT fuse suitable for 11 KV in existing VCB of CG make complete and including taking down old unserviceable PT fuse complete all as specified and directed by Engineer-in-Charge.
Dehydration of transformer oil (mounted on poles/platform etc) with the help of filtering and drying plant by mechanical machines of suitable capacity to achieve dielectric strength of 50 KV complete all as specified and directed by Engineer-in-Charge.
Supply, filling & topping up of transformer oil of dielectric strength 50 KV minimum for voltage stablizer, transformer, OCB's and PTS complete all as specified and directed by Engineer-in-Charge.
S&F TNC switch suitable for vacuum circuit breaker 11 KV, 110 Volts, DC complete and including taking down old unserviceable switch complete all as specified and directed by Engineer-in-Charge.
S&F TNC switch suitable for vacuum circuit breaker 11 KV, 24 Volts, DC complete and including taking down old unserviceable switch complete all as specified and directed by Engineer-in-Charge.
S&F tripping coil for VCB suitable for 110/24 Volts DC complete and including taking down old unserviceable tripping coil complete all as specified and directed by Engineer-in-Charge.
S&F closing coil for VCB suitable for 110/24 Volts DC complete and including taking down old unserviceable closing coil complete all as specified and directed by Engineer-in-Charge.
Supply, Jointing and testing out door type cable termination heat shrinkable joint kit suitable for size 95 Sq mm 3 core 11KV (unearthed cable) under ground XLPE cable and including taking down old unserviceable joint complete all as specified and directed by Engineer-in-Charge.
All as per item No. 31.00 here-in-before above but size of 185 Sqmm 3 Core.
Supply, Jointing and testing indoor type cable termination heat shrinkable joint kit suitable for 95 Sq mm 3 core 11 KV (unearthed cable) under ground XLPE cable including taking down old unserviceable complete all as specified and directed by Engineer-in-Charge.
All as per item No. 33.00 here-in-before above but size of 185 Sqmm 3 Core .
Supply jointing and testing straight through heat shrinkable joint kit suitable for 95 Sq mm 3 core 11 KV (unearthed cable) under ground XLPE cable complete and including taking down old unserviceablejoint complete all as specified and directed by Engineer-in-Charge.
All as per item No. 35.00 here-in-before above but size of 185 Sqmm 3 Core .
S&F 33 KV outdoor oil filled live tank single phase current transformer of ratio 150/5-5A class 1.0 & 5P10, Burden 15 VA complete and including taking down old unserviceable CT complete all as specified and directed by Engineer-in-Charge.
S&F 33 KV outdoor oil filled live tank single phase current transformer of ratio 100/5-5A class 0.5 & 5P10, Burden 15 VA complete all as specified and directed by Engineer-in-Charge.
S&F 33 KV outdoor oil filled single phase potential transformer ratio 33KV/√3/110V/√3, class 0.5 & 23P, Burden 100 VA, Voltage ratio 1.2 Continuous, 1.5 times for 30 Sec as per IS-3156:1992 complete and including taking down old unserviceable PT complete all as specified and directed by Engineer-in-Charge.
S&F 11 KV indoor type CTs as per IS-2705 suitable for 400-200/5-5A 15VA/15 VA class 0.5, 5P10 as per IS 2705 complete and including taking down old unserviceable CT complete all as specified and directed by Engineer-in-Charge.
S&F 11 KV indoor type CTs as per IS-2705 suitable for 200-100/5-5A 15VA/15 VA class 0.5, 5P10 complete as per IS 2705 complete and including taking down old unserviceable CT complete all as specified and directed by Engineer-in-Charge.
Supply & fixing synthetic rubberised gaskets 4mm thick for top cover and other joints for transformer capacity 0.750 MV to 5 MV 33/11 KV and including taking down old unserviceable gasket complete all as specified and directed by Engineer-in-Charge.
Supply & Fix porcelain bushing with stem brass rod for 33/11 KV transformer of cap 0.750 MV to 1.0 MV complete and including taking down old unserviceable bushing complete all as specified and directed by Engineer-in-Charge.
Supply & Fix porcelain bushing with stem brass rod for 33/11 KV transformer of cap 1.6 MV to 5 MV complete and including taking down old unserviceable bushing complete all as specified and directed by Engineer-in-Charge.
M&L for taking out old unserviceable core, limb and HV/LV winding of transformer and taking out burnt copper winding wire cleaning carefully and rewinding the same with new superior quality 99.99% pure copper enamelled wire as per existing gauge including insulating material for transformer 0.750 MV to 1.0 MV complete all as specified and directed by Engineer-in-Charge.
M&L for taking out unserviceable core and limb and HV/LV winding of transformer and taking out burnt copper winding wire cleaning carefully and rewinding the same with new superior quality 99.99% pure copper enamelled wire as per existing gauge including insulating material for transformer 1.6 MV to 5.0MV complete all as specified and directed by Engineer-in-Charge.
S&F in repair fuse wire suitable for GOD at MRS and other locations of followings capacity :-
Supply, laying & testing XLPE insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) with stranded aluminum conductor, 11000 volts grade, of size 185 sqmm, 3 core including taking down old unserviceable cable complete all as specified and directed by Engineer-in-Charge.
Supply, laying & testing XLPE insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) with stranded aluminum conductor, 11000 volts grade, of size 120 sqmm, 3 core and including taking down old unserviceable cable complete all as specified and directed by Engineer-in-Charge.
Supply, laying & testing XLPE insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) with stranded aluminum conductor, 11000 volts grade, of size 95 sqmm, 3 core including taking down old unserviceable cable complete all as specified and directed by Engineer-in-Charge.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, laying of cable/pipe etc not exceeding 10 sqm on plan and getting out in Soft/disintegrated rock complete all as specified and directed by Engineer-in-Charge.
Excavating in trenches, not exceeding 1.5m wide and exceeding 1.5m but not exceeding 3.00m depth for foundation etc or for shaft, wells, cesspits, manholes, pier holes etc not exceeding 10 sqm on plan and n exc 1.5 m in depth and getting out in soft/ disintegrated rock complete all as specified and directed by Engineer-in-Charge.
Returning, filling in, including, spreading, levelling, watering and well ramming excavated Soft/Disintegrated rock in layers complete all as specified and directed by Engineer-in-Charge.
Removing excavated Soft/Disintegrated rock to distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed by Engineer-in-Charge.
M&L for sand cushioning to underground PVC/XLPE cable with tibba sand and punning to provide required cover complete all as specified and directed by Engineer-in-Charge. Note :- For the purpose of payment only punned thickness will be measured
Supplying and laying Jodhpur stone quarry faced stone slab cover 25 to 30 cm in width, 50 to 60 cm long and 40 to 50 mm thick, laid dry and abutting each other with gap between adjacent slab not exceeding 10 mm over under ground cables for protection complete all as specified and directed by Engineer-in-Charge.
M&L for cutting the existing bituminous road / hard standing to size not exceeding 45cm wide and depth not less than 45cm for passing of UG cable through GI pipe and making good the disturbed surface filled with excavated material and top 200mm depth with plain cement concrete 1:3:6, type C1 using 20mm graded aggregate complete all as specified and directed by Engineer-in-Charge.
S&F GI pipe light grade of dia 80 mm laying in road and along with poles for cable protection complete and including taking down old unserviceable pipe of 80mm dia complete all as specified and directed by Engineer-in-Charge.
M&L for cement concrete (1:3:6) type C-2 using 40mm grade stone aggregate for foundation of stay assembly struts or pole etc complete all as specified and directed by Engineer-in-Charge.
M&L for cement concrete 1:2:4 type B-1 using 20mm grade stone aggregate for coping around poles including necessary form work finishing even and smoth with out using extra cement complete all as specified and directed by Engineer-in-Charge.
M&L for cement concrete 1:4:8 type D-2 using 40mm grade stone aggregate in foundation of PCC pole/struts as specified including necessary form work finishing even and smoth with out using extra cement complete all as specified and directed by Engineer-in-Charge.
Removing grass and bushes including its roots growing at Substation yard and keep the sub station yard neat and clean complete all as specified and directed by Engineer-in-Charge.
Material and labour for substation yard spreading levelling with 40 mm graded coarse aggregate / gravells laid approximately 75 mm thick layers near VCB/Transformer /2/4 pole structure and plateform etc complete all as specified and directed by Engineer-in-Charge.
Material and labour for substation yard spreading levelling with 20 mm graded coarse aggregate / gravells laid approximately 75 mm thick layers near VCB/Transformer /2/4 pole structure and plateform etc complete all as specified and directed by Engineer-in-Charge.
Cuttting / trimming of tree branches in close proximity to over head lines to maintain a clearance of 1.5 meters from the over head line to nearby trees complete all as specified and directed by Engineer-in-Charge. Note :- Only effected area of over head conductor shall be measured.
S&F vacuum Interrupter bottle type with brash, connecting parts suitable for 11 KV VCB Panel as per site requirement complete and including taking down old unserviceable vacuum interrupter bottle type with brash complete all as specified and directed by Engineer-in-Charge.
M&L for aluminium conductor steel reinforced (ACSR) for jumpering and including taking down unserviceable conductor complete all as specified and directed by Engineer-in-Charge.
M&L for cross arms bracings supports, clamps and back plates fabricated from structural steel sections incl nuts bolts washers welding, bending cold or hot, drilling holes for bolts in any shpae or size as indicated or directed and inclusive of one primer coat of red oxide zinc chrome primer and two coats of aluminium paint incl preparation of surfaces including dismantling and taking down old unserviceable cross arms complete all as specified and directed by Engineer-in-Charge.
M&L for painting tranformer complete by removing existing oil paint by scrapping and applying two coats of approved colour synthetic enamel paint (1st grade quality) over a coat of primer after preparation of surfaces including writing SM / MES numbers and date of oil tested etc. for the following capacity complete all as specified and directed by Engineer-in-Charge.:-
Transformer of capacity 750 KVA to 1000 KVA, 33 KV/11 KV.
Transformer of capacity 1600 KVA to 2000 KVA, 33 KV/11KV.
Transformer of capacity 5000 KVA, 33 KV/11KV.
S&F PVC insulated armoured copper control cable 1100 voltage grade of following size including taking down old cable complete all as specified and directed by Engr-in- Charge:-
2.5 Sqmm 4 Core
2.5 Sqmm 6 Core
2.5 Sqmm 12 Core
M&L steel tubular swaged poles and complete with cast iron / M.S base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55 (11 mtrs long) including painting with two coats of aluminium paint over a coat of red oxide metal primer complete all as specified and directed by Engr-in-Charge. The pole shall conform to IS 2713:1980 and each component pipe shall be ISI marked and conform to IS 1161 and including taking down old unserviceable pole complete all as specified and directed by Engineer-in-Charge.
S&F mild steel Chequered Plate, Square cut to required size for cable duct cover , inclusive of one primer coat of red oxide zinc chrome primer and two coats of black paint complete and including taking down old unserviceable plate complete all as specified and directed by Engineer-in-Charge.
M&L for Isolating 33 KV Bus System, temporery earth connection of BUS system removing old paint from surface of cross arms, channels, 2/4 pole structure by scraping, rubbing and making good surcace for painting and including two coats of synthetic aluminium paint on rusted pealed out surface after cleanng complete all as specified and directed by Engineer-in-Charge. Loc : 33/11 KV Yard-02 Nos
Providing the cable fault locating Machine with necessary T&P at site for locating exact pin point of fault along with the length of armourd 11 KV XLPE insulated HT cable complete all as specified and directed by Engineer-in-Charge.
S&F in repair copper rod for bushing suitable for 11 KV CT of ratio 100/5-5A class 0.5 & 5P10 and as per site requirement complete all as specified and directed by Engineer-in-Charge.
S&F Polyfloor insulating rubber mat suitable for 11 KV Sub Station of Size 2mtrx1mtrx3mm thick ISI mark complete all as specified and directed by Engineer-in-Charge.
M/s Rohit Construction Co. (BID ID -3484403)
Akarsha Enterprises (BID ID -3482220)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.43 MB
BOQ_826561.xls
BOQ • 0.29 MB
TENDER_84372.pdf
Tender Documents • 3.50 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .