| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.0 LAccepted-AOC | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹33.9 L+₹2.3 L (7.33%)Rejected-AOC | L2 | Rejected-AOC Rejected | |
| 3 | L3₹39.4 L+₹7.8 L (24.8%)Rejected-AOC | L3 | Rejected-AOC Rejected | |
| 4 | L4₹40.6 L+₹9.1 L (28.7%)Rejected-AOC DHARAM SALA SINGHAN CHADOORA DISTT BUDGAM J K | CHADOORA | BUDGAM | JAMMU AND KASHMIR | L4 | Rejected-AOC Rejected |
Tender Value
₹39 L
EMD Value
₹78,000
Closing Date
23 Mar 2022, 6:00 pmClosed
GE AF SRINAGAR
GE AF SRINAGAR AF STATION SRINAGAR 190007
REPAIR / REPLACEMENT OF LOW VOLTAGE PANEL / KIOSK BOX LT SWITCH GEAR, CABLE AND OTHER CONNECTED WORKS IN DOMESTIC AREA AT AIR FORCE STATION SRINAGAR
2022_MES_507482_1
GE(AF)SGR- 14 OF 2022-23
Open Tender
Civil Works
Item Rate
180 days
GE AF SRINAGAR
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE AF Srinagar
₹78,000
Yes
10 May 2022
11 Feb 2022
24 Mar 2022
11 Feb 2022
23 Mar 2022
25 Feb 2022
Amount
Note:- For All Items of This BOQ:- Work has to be executed for External Electrification work, Electric shut will require to execute certain items of this Schedule, Contractor is require to intimate Engineer-in-Charge at least 7 days in advance whenever shut down is require, Engineer-in-Charge will intimate to contractor four days in advance from the date of shut down provided by them. Contractor will manage manpower / tools / plant etc accordingly. No compensation etc will be paid by department in case shut down not provided by the department due to any reason. In case of any dispute Decision of Accepting officer shall be final binding & conclusive
Excavating in trenches in any type of soil not exc. 1.5 mtr wide and not exc. 1.5 mtr in depth for foundation poles, stays, laying of cables etc for shaft, wells, cesspits, manholes, peir holes, etc or not exc. 10 Sqm on plan and getting out, complete all as specified and directed by Engr-in-Charge.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exc. 25 cm thick, using excavated soil complete all as specified and directed by Engr-in-Charge.
Removing excavated soil to a distance not exc. 50 metre and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and directed by Engr-in-Charge.
Taking out carefully unserviceable LT under ground cable of size 10 Sqmm 2 core from trenches / Pipes including taking out bricks cover, complete all as specified and as directed by Engineer-in-Charge. Note:- Serviceable Bricks obtained shall be cleaned and stacked properly for reuse
All as per Item No 04 above but cable of size 16 Sqmm, 2 core.
All as per Item No 04 above but cable of size 16 Sqmm, 4 core.
All as per Item No 04 above but cable of size 25 Sqmm, 3.5 core.
All as per Item No 04 above but cable of size 35 Sqmm, 3.5 core.
All as per Item No 04 above but cable of size 50 Sqmm, 3.5 core.
All as per Item No 04 above but cable of size 70 Sqmm, 3.5 core.
All as per Item No 04 above but cable of size 95 Sqmm, 3.5 core.
All as per Item No 04 above but cable of size 120 Sqmm, 3.5 core.
All as per Item No 04 above but cable of size 150 Sqmm, 3.5 core.
Supply & lay XLPE insulated, PVC inner sheathed, armoured with galvanised steel strip or wire, heavy duty, LT underground cable ISI marked with aluminium conductor 1100 volt grade of size 10 Sqmm, 2 core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing etc complete all as specified & directed. Note:- Earthwork, sand cushion, cable cover if required will be measured and paid separately under respective items of this Schedule.
All as per Item No 14 above but cable of size 16 Sqmm, 2 core.
All as per Item No 14 above but cable of size 16 Sqmm, 4 core.
All as per Item No 14 above but cable of size 25 Sqmm, 3.5 core.
All as per Item No 14 above but cable of size 35 Sqmm, 3.5 core.
All as per Item No 14 above but cable of size 50 Sqmm, 3.5 core.
All as per Item No 14 above but cable of size 70 Sqmm, 3.5 core.
All as per Item No 14 above but cable of size 95 Sqmm, 3.5 core.
All as per Item No 14 above but cable of size 120 Sqmm, 3.5 core.
All as per Item No 14 above but cable of size 150 Sqmm, 3.5 core.
Laying only XLPE insulated, PVC inner sheathed, armoured, LT underground cable of size 10 Sqmm to 16 Sqmm of any core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing etc complete all as specified & directed. Note:- (i) Earthwork, sand cushion, cable cover if required will be measured and paid separately under respective items of this Schedule. (ii) LT cable will Be issued under Sch B free for laying.
All as per Item No 24 above but cable of size 25 Sqmm to 35 Sqmm, 3.5 core.
All as per Item No 24 above but cable of size 50 Sqmm to 70 Sqmm, 3.5 core.
All as per Item No 24 above but cable of size 95 Sqmm 3.5 core.
All as per Item No 24 above but cable of size 120 Sqmm to 150, 3.5 core.
Supply and Laying of bricks well burnt sub class B (old size) laid flat for cable protection width equal to the length of bricks complete all as specified and directed by Engineer-in-Charge.
Laying Only of bricks retrieved from items No. 04 to 13 here-in-before, laid flat for cable protection width equal to the length of bricks complete all as specified and directed by Engineer-in-Charge.
M&L for providing dry river sand as in sand cushioning below and above cable thickness as specified in SSR to under ground cable including punning down of sand in layer all as specified and directed by Engg-in-Charge. Note: for measurement purpose punned thickness of sand will be consider.
M&L for cutting of existing road surfaces up 100 mm deep & 300 mm wide and making good disturbed portion with 100 mm thick plain cement concrete 1:2:4 type B-1 (using 40mm graded crushed stone aggregate) complete all as specified and directed by Engineer-in-Charge.
S&F in repair 50 mm dia bore mild steel galvanized iron tubes, 'light grade' with all fitting and laid in trenches or fixed to pole or laid in floors for protection of cable complete all as directed.
S&F in repair 80 mm dia bore mild steel galvanized iron tubes, 'light grade' with all fitting and laid in trenches or fixed to pole or laid in floors for protection of cable complete all as directed.
Blank
Taking down unserviceable LED light fitting of capacity 30 / 45 Watt from Pole / wall or any other location, any height, any situation, and replacement of electronic driver with new driver of same capacity, tightening the loose connection and made item functional, re-fixing / re-hanging the fitting in existing location or other location (as directed) and testing complete all as specified and directed by Engineer-in-Charge. Note:- Necessary T & P like ladder / Boom Vehicle, tools etc as required for taking down & fixing of light shall be provided by contractor without any extra cost of department.
All as per item No 36 above but replacement of electronic driver sutable for LED light fitting of 50 / 60 Watt.
All as per item No 36 above but replacement of electronic driver sutable for LED light fitting of 100 Watt.
All as per item No 36 above but replacement of electronic driver sutable for LED light fitting of 150 Watt.
S&F in repairs LED street Light fitting 60 Watt, system efficiency not less than 110 lumen / watt, IP66 protection, consisting of high / low voltage cut off, maintenance free isolated Electronic driver circuits, Low THD, PMMA grade high quality Transmittance lens, Epoxy powder coated Die Cast Aluminium housing with weather proof gasket for lamp & driver compartment, fitted in cast aluminium housing with SS screws fixed on existing bracket & connecting, complete.
Supply and fix in repair LED, post top lantern, 40 Watt, 230 volts AC, out door type, with decorative post 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp fixed over existing pole complete Make;- Crompton Cat No LPTO-40-CDL or equvallent cat No of make mention in Appx A.
M&L for preparation of old painted steel surface of LT feeder pillar Box, 440 Volts, 3 phase of any size / location and applying two coats of synthetic enamel paint complete all as specified and directed Engineer-in-Charge.
M&L for Sub main wiring for connecting street light fitting from junction box with two single core, PVC insulated, (ISI marked) , unsheathed, 1100 volts grade, 2.5 Sqmm multistranded copper conductor cable drawn into and including suitable size PVC conduit 20 mm dia ISI marked medium grade with all accessories and including one single core, 2.5 Sqmm PVC insulated multistranded unsheathed 1100 volts grade copper conductor cable as earth wire including taking down old pipe & cable complete all as directed & specified. Note: 2 Runs of main cable and one run earth wire with conduit will be measured as one RM for payment.
Supply, installation testing & commissioning street light control box, factory made, weather and vermin proof having size 200 x 250 x 80 mm made out of 2.00 mm thick CRCA sheet, comprising of MCB SP 10A, C curve 10 KA breaking capacity 01 No's, 16 Amp 230 volt rated aluminium bus bar with mounting rail fixed on porcelein insulator, making holes on strips for connecting cables and fixing of bus bar chamber on street light pole with and including MS clamp of size 25 x 5 mm including nut, bolts washers duly painted with 2 coats of enamel paint over a coat of red oxide primer including taking down old box , all as specified and directed.
Material and labour for renewal of earthing complete with galvanized iron earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m deep below normal ground connected to galvanized steel strip of size 32 x 6 mm by means of bolts nuts check nuts and washer of galvanized steel, watering pipe of 20 mm bore, galvanised iron, medium grade, and 40 mm bore galvanised iron light grade for earth wire protection including all excavation earth work in any type of soil, PCC pit in PCC 1:2:4 type B-1 and RCC 1:2:4, type B1 for precast chamber cover 50 mm thick, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 Kg / sqm), with charcoal, salt, funnel complete all as shown in the electrical plate No 3 of SSR part –I and testing on completion.
Note:- Quoted rates shall be deemed to include for earth wire with protection pipe up to 7.5 M length.
Material and labour for renewal of earthing complete with Copper earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m deep below normal ground connected to copper strip of size 20 x 3 mm by means of bolts nuts check nuts and washer of galvanized steel, watering pipe of 20 mm bore, galvanised iron, medium grade, and 32 mm bore galvanised iron light grade for earth wire protection including all excavation earth work in any type of soil, PCC pit in PCC 1:2:4 type B-1 and RCC 1:2:4, type B1 for precast chamber cover 50 mm thick, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 Kg / sqm), with charcoal, salt, funnel complete all as shown in the electrical plate No 3 of SSR part –I and testing on completion.
Note:- Quoted rates shall be deemed to include for earth wire with protection pipe up to 7.5 M length.
S&F in repair timer distribution board with analog time switches complete of rating 65 Amps 3 pole 230 Volts 415 volt including taking down existing complete all as specified and directed by Engr in charge. Make :- Indoasian Cat part No. TL065ABO or equivalent cat No of Make C&S / HPL / Havells
M&L for preparation of old painted surface of steel tubular poles height approximately 7 to 7.5 meter above GL including cross arms and bracings and applying two coat aluminium paint and rewriting pole number with synthetic enamel paint complete all as specified and directed.
S&F in replacement Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint on 4/6 pole 11 KV HT structure
M&L for Aluminium conductor, steel reinforced (ACSR) Code name : Weasel conductor for HT feeders on steel tubular / PCC poles, stretching without kinks and bends including binding wire including taking down old conductor of any type shape and size, complete all as specified.
Deployment of manpower / tools etc for Restretching / re fixing the existing LT OH / Lines ACSR conductor of any type and size including disconnecting binding wire on insulator, rebinding properly to avoid tension / fitting bending of poles, complete all as specified and directed by Engrr-in-Charge. Note:- Each line of conductor will be measured & paid separately.
Supply & filling Power Transformer Oil for toping up the level of oil having dielectric strength 50 KV at 4 mm gap confirming to IS-335 complete all as specified and directed by Engineer-in-Charge.
Note:- Transformer oil shall be supplied in sealed Containers. Make :- M&I MATERIAL (MIDEL) POWER LINK, POWER OIL, SAVITA
Supply & fix in repair pin type, porcelain, vitreous, white / brown / green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised nut, 100 mm height, 65 mm dia for 1100 volts grade complete all as specified and directed by Engr-in-charge.
Supply & fix in repair pin type, porcelain, vitreous, white / brown / green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised nut, 150 mm height, 150 mm dia for 11000 volts grade complete all as specified and directed by Engr-in-charge.
Supply & fix in repair disc type, porcelain, vitreous white / brown / green insulator including one galvanised mild steel straps washers insulator bolts, washers , nut, 145 mm height, 255 mm dia for 11000 volts grade complete all as specified and directed by Engr-in-charge.
Supply & fix in repair shakle type, porcelain, vitreous, white / brown / green insulator including one galvanised mild steel straps washers insulator bolts, washers , nut, 100 mm height, 115 mm dia for 1100 volts grade complete all as specified and directed by Engr-in-charge.
Supply and fix in repair stay assembly for LT pole complete with accessories as shown in Electrical Plate No 1 (Dia of stay rod 16 mm) complete all as specified and directed by Engr-in-charge.
M&L for plain cement concrete 1:4:8, type D- 2, (using 40 mm graded stone aggregate) as in foundation complete all as specified and directed by Engineer-in-Charge
S&F in repair MCCB 4 pole, 63 amps with breaking capacity 16 KA, 415 volts, fixed in existing panel & connecting complete all as specified and directed.
S&F in repair MCCB 4 pole, 100 amps with breaking capacity 16 KA, 415 volts, fixed in existing panel & connecting complete all as specified and directed.
S&F in repair MCCB 4 pole, 160 amps with breaking capacity 25 KA, 415 volts, microprocessor release type, fixed in existing panel & connecting complete all as specified and directed.
S&F in repair MCCB 4 pole, 200 amps with breaking capacity 25 KA, 415 volts, microprocessor release type, fixed in existing panel & connecting complete all as specified and directed.
S&F in repair MCCB 4 pole, 250 amps with breaking capacity 25 KA, 415 volts, microprocessor release type, fixed in existing panel & connecting complete all as specified and directed.
S&F in repair MCCB 4 pole, 400 amps with breaking capacity 25 KA, 415 volts, microprocessor release type, fixed in existing panel & connecting complete all as specified and directed.
Supply and installation, testing, commissioning, factory made, CPRI approved, outdoor type, LT Panel board of size 900 mm x 600 mm x 450 mm, confirming to IS 5039 with IP-54 protection, made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 HZ supply, mounted on and including MS angle section 40 x 40 x 5 mm frame with front openable, double door with provision of locking arrangement dust & varmin proof , gasket, TPN busbar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof, overall powder coated, including taking down old Feeder pillar board complete all as specifed and directed & Connisting of the following switchgear:-
Solid aluminium bus bar 150 Amp for 3 phase , 100 Amp for neutral - 01 set
MCCB 4 Pole , 100 Amps, rupturing capacity 25 kA, 415 Volts, adjustable type - 01 Nos as incoming
MCCB 4 Pole , 63 Amps, rupturing capacity 16 kA, 440 Volts, adjustable type - 03 Nos as outgoing
Indicator Lamp 22.5 mm dia LED type 240 Volts AC to show three phase availability- 01 set
Note :- Quoted rates shall be deemed to include for grouting / fixing of feeder pillar board over & including brick masonary plateform of hight 450 mm GL, with old size brick set in CM 1:4, with PCC 1:4:8 type D2 in foundation, 15 mm redering in CM 1:6 on exposed surfaces, 100 mm thick PCC 1:3:6 type C1 using 20mm graded stone aggregate as in padding on top and grouting legs of panel.
Supply and installation, testing, commissioning, factory made, CPRI approved, outdoor type, LT Feeder pillar board (kiosk type), confirming to IS 5039 with IP-54 protection, made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 HZ supply, mounted on and including MS angle section 40 x 40 x 5 mm frame with front openable, double door with provision of locking arrangement dust & varmin proof , gasket, TPN busbar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof, overall powder coated, including taking down old Feeder pillar board complete all as specifed and directed & Connisting of the following switchgear:-
Solid aluminium bus bar 300 Amp for 3 phase , 150 Amp for neutral - 01 set
MCCB 4 Pole , 200 Amps, rupturing capacity 25 kA, 440 Volts, adjustable type - 01 Nos as incoming
MCCB 3 Pole , 63 Amps, rupturing capacity 16 kA, 440 Volts, adjustable type - 02 Nos as outgoing
MCCB 3 Pole , 25 Amps, rupturing capacity 10 kA, 440 Volts, adjustable type - 02 Nos as outgoing
MCB SPN 10 Amps, rupturing capacity 10 KA, 240 Volts - 05 Nos as outgoing
Indicator Lamp 22.5 mm dia LED type 240 Volts AC to show three phase availability- 01 set
Note :- Quoted rates shall be deemed to include for grouting / fixing of feeder pillar board over & including brick masonary plateform of hight 450 mm GL, with old size brick set in CM 1:4, with PCC 1:4:8 type D2 in foundation, 15 mm redering in CM 1:6 on exposed surfaces, 100 mm thick PCC 1:3:6 type C1 using 20mm graded stone aggregate as in padding on top and grouting legs of panel.
Supply and fixing in repair GI Bracket made of 40 mm dia GI pipe medium grade 1.5 metre long, bend to shape for street light for steel / RCC pole as per site requirement including MS clamp with nut, bolt, washers complete all as specified and directed by Engineer-in-Charge
S&F in repair PVC seperator suitable for 1100 V, ACSR Conductor over head line complete all as specified and directed by Engineer-in-Charge.
Deployment of manpower / tools etc for maintenance of gang operated air break isolators switch out door type 9 / 12 insulators double stack, triple pole, rotating type double break per pole for 11000 volts, 3 phase, 50 Hz, AC supply system having 200 / 400 Amps capacity by oiling, greasing, adjustment of lever and making the same smooth functional complete all as specified. complete all as specified and directed
Supply and fix in replacement male contact / moving contact for gang operated air break device 11 KV complete all as directed at site by Engr-in-charge.
Supply and fix in replacement female contact / fixed contact jaw for gang operated air break device 11 KV complete all as directed at site by Engr-in-charge.
Supply & fix in repair Air break gang operated switch with 12 No's insulators outdoor type, triple pole, mechanically operated, suitable for vertical installation, single break, provided with locking arrangement, consisting of MS Channel, HT post type insulator copper alloy, high pressure, assembly drop out fuses, operating rod 25 mm dia GI pipe, medium grade for operating from 1.2 m above GL complete including drop out fuses conforming to IS rated voltage 11 KV and for current rating 200 Amp all as specified including taking down old Air break gang operated switch .
Surface dressing n exc 15 cm deep in any type of soil, including trimming of ground, to remove vegetation and / or small inequalities complete.
Material and labour for spreading of clean & dry stone aggregate of nominal size not more than 20 mm (free from organic impurities) laid around 4 / 6 pole HT structure / surrounding area of outdoor RMU, manually without damaging any equipments, cable or parts, spreading & leveling of finished gravel uniformly in layers n. exc 150 mm thick, complete all as specified and directed. Note:- Preparation of ground level for laying of aggregate will be measured and paid separately vide BOQ item No 73
S&F in repair Anti climbing devices spikes type fabricated out of MS bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and directed by Engr-in-Charge.
S&F in repair HT Danger notice plate of size 250 mm x 200 mm x 1.6 mm thick of mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour and fixed to pole with MS clamps, bolts and nuts of approved size complete all as specified and directed by Engr-in-Charge.
Supply and installation, testing, commissioning, factory made, bus bar chamber of size 1200 mm x 1000 mm x 600 mm size, CPRI approved, outdoor type, confirming to IS 5039- with IP-54 protection, made out of 3.15 mm thick CRCA sheet, 415 Volt, 3 phase , 50 Hz supply mounted on and including MS angle section 50 x 50 x 5 mm frame with front and back openable, with provision of locking arrangement dust & vermin proof , gasket, TPN busbar of size 400 amps for phase, 200 amps for neutral, insulated with colour coated heat shrinkable sleeves, mounted on proper insulator, provision for 08 Nos LT connection, with gland, welding hinges, dust & vermine proof, overall powder coated, including taking down old busbar chamber complete all as specified and directed.
Note :- Quoted rates shall be deemed to include for grouting / fixing of feeder pillar board over & including brick masonary plateform of hight 450 mm GL, with old size brick set in CM 1:4, with PCC 1:4:8 type D2 in foundation, 15 mm redering in CM 1:6 on exposed surfaces, 100 mm thick PCC 1:3:6 type C1 using 20mm graded stone aggregate as in padding on top and grouting legs of panel.
Supply and installation, testing, commissioning, factory made, bus bar chamber of size 1200 mm x 1000 mm x 600 mm size, CPRI approved, outdoor type, confirming to IS 5039- with IP-54 protection, made out of 3.15 mm thick CRCA sheet, 415 Volt, 3 phase , 50 Hz supply mounted on and including MS angle section 50 x 50 x 5 mm frame with front and back openable, with provision of locking arrangement dust & vermin proof , gasket, TPN busbar of size 200 amps for phase, 100 amps for neutral, insulated with colour coated heat shrinkable sleeves, mounted on proper insulator, provision for 08 Nos LT connection, with gland, welding hinges, dust & vermine proof, overall powder coated, including taking down old busbar chamber complete all as specified and directed.
Note :- Quoted rates shall be deemed to include for grouting / fixing of feeder pillar board over & including brick masonary plateform of hight 450 mm GL, with old size brick set in CM 1:4, with PCC 1:4:8 type D2 in foundation, 15 mm redering in CM 1:6 on exposed surfaces, 100 mm thick PCC 1:3:6 type C1 using 20mm graded stone aggregate as in padding on top and grouting legs of panel.
M/S NEW FAROOQ TRADERS
M/S ZAHOOR ENTERPRISES
M/s Jaipal Associates
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .