Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹73.0 LAccepted-AOC 26 36 EAST PATEL NAGAR NEW DELHI DELHI 110008 | WEST DELHI | DELHI | 110008 | L1 | Accepted-AOC L1 | |
| 2 | L2₹78.9 L+₹5.9 L (8.07%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹85.5 L+₹12.5 L (17.1%)Rejected-Finance 04 L BLOCK MARKET SECTOR 11 NOIDA 201301 UP GAUTAM BUDHA NAGAR | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201301 | L3 | Rejected-Finance L3 | |
| 4 | L4₹85.9 L+₹12.9 L (17.6%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L4 | Rejected-Finance L4 | |
| 5 | L5₹1.0 Cr+₹27.6 L (37.8%)Rejected-Finance 12 BHARTI AARTIST COLONY VIKAS MARG NEW DELHI 110092 | EAST | DELHI | 110092 | L5 | Rejected-Finance L5 |
Tender Value
Refer Docs
EMD Value
₹1.4 L
Closing Date
26 Feb 2025, 6:00 pmClosed
CWE PATIALA
HQ COMMANDER WORKS ENGINEER BLDG No 26 NEW LALBAGH PATIALA 147001 Contact 01752200082
REPLACEMENT OF 09 X BER TRANSFORMERS UNDER AGE(I) AT MIL STN DAPPAR
2025_MES_694011_1
CWE/PAT/T-72/2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
DAPPAR
Please refer Tender documents.
6 documents required · 6 mandatory
₹1,000
AGE(I) DAPPAR
₹1.4 L
21 Mar 2025
21 Jan 2025
28 Feb 2025
21 Jan 2025
26 Feb 2025
13 Feb 2025
21 Jan 2025 - 12 Feb 2025
Amount
Disconnecting and dismantling safely Old existing Transformer of any capacity from its location and depositing to MES Store yard or location as directed by Engr-in-Charge. Supply, installation, testing and Commissioning of oil cooled, copper wound step down transformer of capacity 63 KVA Pole mounted outdoor type with latest feature complete with standard fitted HT 11 KV 3 Phase 4 wire, 50 C/S oil immersed naturally cooled externally cooling tube delta connection on primary side HT 11 KV and star connection on secondary LT 433 V with tappings at + 2.5 % to + 7.5 % on HV side and to be changed by hand operated off load tap changing gear including first filling of transformer oil of dielctric strength not less than 60 KV with all fittings and accessories such as LT box with gland, HT box with gland, silica gel breather ,oil level indicator gauge, drain out valve (oil tank), exhaust vent ,air release valve, temp gauge, cast iron wheel etc comply with EEL2 (Level-2) IS 1180 2014 with amendment 1,2,3 & 4 . Following items/Accessories included in this rate and no extra cost will be paid for these items complete all as specified and directed by Engr-in-charge.
(a) Name,Rating and diagram plate (b) Off circuit tap changing switch if not opted for OLTC (c) Earthing terminals (d) Lifting lugs (e) Magnetic oil level indicator (having contact for alarm and trip) (f) Oil drain valve with plug (g) Oil filter valve with plug (h) Conservator with oil filling hole with cap (i) Thermometer pocket (j) 4 " dial type thermometer stem type & with MRP ( if OTI not opted) (k) Air release plug (l) Silica gel breather (m) Removable inspection opening on top cover (ON & above 160 KVA) (n) Explosion vent ( if PRV not opted) (o) Bi-directional CI rollers (on & above 1000 KVA) otherwise unidirectional (p) Oil temp indicator (having contact for alarm and trip) (q) Winding temp indicator (having contact for alarm & trip) (r) Pressure Relief Valve (having contact for alarm & trip). Note :- (a) Transformer shall be precommisioned by SEI after installation ,before issue of completion. (b) Cost of all necessary T&P and measuring device shall be provided by the contractor without any extra cost. (c) Predispatch inspection from factory to be done by rep of Accepting officer deemed to be included. (d) Any other item which is required for efficient functioning of transformer deemed to be included in the quoted rate. During currency of dismantling of existing transformer and commissioning of new transformer load will be shifted to trolley mounted transformer held with establishment. Shifting of trolley mounted transformer with HT/LT cable and accessories etc safely from MRS/ existing location to required location will be carried out by the contractor at his own cost
Disconnecting and dismantling safely Old existing Transformer of any capacity from its location and depositing to MES Store yard or location as directed by Engr-in-Charge. and Supply, installation, testing and Commissioning of oil cooled, copper wound step down transformer of capacity 250 KVA plinth mounted outdoor type with latest feature complete with standard fitted HT 11 KV 3 Phase 4 wire, 50 C/S oil immersed naturally cooled externally cooling tube delta connection on primary side HT 11 KV and star connection on secondary LT 433 V with tappings at + 2.5 % to + 7.5 % on HV side and to be changed by hand operated off load tap changing gear including first filling of transformer oil of dielectric strength not less than 60 KV with all fittings and accessories such as LT box with gland, HT box with gland, silica gel breather oil level indicator gauge, drain out valve (oil tank), exhaust vent, air release valve, temp gauge, cast iron wheel etc comply with EEL2 (Level-2) IS 1180 2014 with amendment 1,2,3 & 4. Following items/Accessories included in this rate and no any extra cost will be paid for these items complete all as specified and as directed by Engr-in-charge.
(a) Name, Rating and diagram plate (b) Off circuit tap changing switch if not opted for OLTC (c) Earthing terminals (d) Lifting lugs (e) Magnetic oil level indicator (having contact for alarm and trip) (f) Oil drain valve with plug (g) Oil filter valve with plug (h) Conservator with oil filling hole with cap (i) Thermometer pocket (j) 4 " dial type thermometer stem type & with MRP (if OTI not opted) (k) Air release plug (l) Silica gel breather (m) Removable inspection opening on top cover (ON & above 160 KVA) (n) Explosion vent (if PRV not opted) (o) Bi-directional CI rollers (on & above 1000 KVA) otherwise uni-directional (p) Oil temp indicator (having contact for alarm and trip) (q) Winding temp indicator (having contact for alarm & trip) (r) Pressure Relief Valve (having contact for alarm & trip). Note :- (a) Transformer shall be precommisioned by SEI after installation ,before issue of completion. (b) Cost of all necessary T&P and measuring device shall be provided by the contractor without any extra cost. (c) MInor addition/ alternation & rendering/ plastering of existing platform of transformer as per requirement of site or as directed by Engr-in-Charge deemed to be included in the quoted rate. (d) Predispatch inspection from factory done by rep of Accepting officer deemed to be included. (e) Any other item which is required for efficient functioning of transformer deemed to be included in the quoted rate. During currency of dismantling of existing transformer and commissioning of new transformer load will be shifted to trolley mounted transformer held with establishment. shifting of trolley mounted transformer with HT/LT cable and accessories etc safely from MRS/ existing location to required location will be carried out by the contractor at his own cost .
All as per srl item No 2.00 here-in-before and 2.1(a) to 2.1(r) including Note above but Supply, installing, testing and commissioning of Outdoor type step down transformer of 11000/ 433 volts (at no load), AC, 3 phase 50 Hz capacity 315 KVA core type copper wound, EE level-2 oil immersed, including PCC foundation ,platform as per manufacturer recommendation (one meter high from ground level) shall be provided by contractor without any extra cost, as directed by Engr-in-Charge.
All as per srl item No 2.00 here-in-before and 2.1(a) to 2.1(r) including Note above but Supply, installing, testing and commissioning of Outdoor type step down transformer of 11000/433 volts (at no load), AC, 3 phase 50 Hz capacity 315 KVA core type copper wound, EE level-2 oil immersed, as directed by Engr-in-Charge.
All as per srl item No 2.00 here-in-before and 2.1(a) to 2.1(r) including Note above but Supply, installing, testing and commissioning of Outdoor type step down transformer of 11000/433 volts (at no load), AC, 3 phase 50 Hz capacity 400 KVA core type copper wound, EE level-2 oil immersed,as directed by Engr-in-Charge.
All as per srl item No 2.00 here-in-before and 2.1(a) to 2.1(r) including Note above but Supply, installing, testing and commissioning of Outdoor type step down transformer of 11000/433 volts (at no load), AC, 3 phase 50 Hz capacity 500 KVA core type copper wound, EE level-2 oil immersed, but PCC foundation ,plateform as per manufacturer recommendation ( one meter high from ground level) shall be provided by contractor without any extra cost, as directed by Engr-in-Charge.
All as per srl item No 2.00 here-in-before and 2.1(a) to 2.1(r) including Note above but Supply, installing, testing and commissioning of Indoor type step down transformer of 11000/433 volts (at no load), AC, 3 phase 50 Hz capacity 630 KVA core type copper wound, EE level-2 oil immersed,as directed by Engr-in-Charge.
Material & labour for danger notice plate of 1.6 mm thick mild steel sheet vitreous enamelled white, with letters figures and conventional skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for HT 11 kV of size 25 x 20 cm complete all as specified and as directed.
Material & labour for 50mm bore galvanized steel tubing light grade (ISI marked) protection of earthing strip fixed to pole/walls or laid in floors, road crossing ducts with all necessary fittings and fittings and fixed with clamps, bolts, nuts and washers etc complete all as specified and directed.
Material & labour for earthing complete with 600x600x6 mm surrounded by a mixture of charcoal and salt in alternate layers burried directly in ground vertically in a pit of depth not less than 2.25 metre deep below normal ground level with top edge of the earth plate at a depth of not less than 1.5m below ground level, connected to and including G.I. Strip of size 32x6mm as earthing lead by means of bolts,nuts and check nuts and washers of galvanised iron 40 mm bore light grade GI pipe for watering with funnel, wire mesh and including necessary excavation and earth work, PCC 1:2:4 type B-1 pit and 50 mm thick RCC M-25 (Design mix) reinforced with XPM (weight not less than 3 kg/sq m) pit cover, CI frame, charcoal and common salt filling in alternate layers complete all as shown and specified in electrical plate No 5 of SI part I of 1991. all as specified and directed.
Supply, laying of HT cable in trenches /ducts/ fixing on pole XLPE insulated, screened, earthed, PVC bedded, galvanised steel strip, electric power cable (heavy duty) of size 3 x 95 sqmm with aluminium conductor suitable for 11 KV (E) grade as per relevent IS including latest amendment for IS testing, commissioning complete all as specified Note:- (a) Earth work & GI pipe will be measured and paid seperately. (b) Necessary GI clamps made out of GI strip 32mm x 6mm as per site requirement deemed to be included in the quoted rate.
Material & labour Heat shrinkable outdoor type end termination cable jointing kit suitable for earthed 3 core 95 sqmm HT 11KV XLPE aluminium conductor cable incl testing and commissioning after making necessary connectios. NOTE- a. The quoted rate is deemed to be inclusive of cost of saddling or clamping of cable all as directed by Engr-in-Charge. Note: Being a maintenence work, work will be carried out in phases as directed by engr-in-charge after ensuring feeder wise shut down from MRS.
Nirmal Enterprise (BID ID -3249637)
GEPS PROJECTS (BID ID -3250312)
R D Bansal (BID ID -3243814)
Vijaypower Generators Limited (BID ID -3250168)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .