Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹99.9 CrAdmitted-Finance | ₹99.9 Cr | L1 | Admitted-Finance |
| 2 | L2₹125.7 CrAdmitted-Finance | ₹125.7 Cr | L2 | Admitted-Finance |
| 3 | L3₹131.8 CrAdmitted-Finance | ₹131.8 Cr | L3 | Admitted-Finance |
| 4 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Others-As per summary report |
| 5 | Not Admitted-Fee/PreQual/Technical 109 PALTAN BAZAR DEHRA DUN UTTARAKHAND 248001 UDYAM UK 05 0031531 05AAAFJ8447J1Z7 B R | DEHRADUN | UTTARAKHAND | 248001 | - | - | Not Admitted-Fee/PreQual/Technical Others-As per summary report |
| Sl No | Description | Qty | Unit | KAPAHI CONSTRUCTION COMPANY L1 | KEC International Limited L3 | Rabina Enterprises Pvt Ltd L2 |
|---|---|---|---|---|---|---|
| 1.00SUB HEAD - I: CIVIL WORK | ||||||
| 2.00 | Surface dressing of the ground including removing vegetation and in-equalities not exceeding 15 cm deep and disposal of rubbish, lead upto 50 m and lift upto 1.5 in all kind of soil | 9,325 | Sqm | 1 ₹9,325 | 20 ₹1.9 L | 20 ₹1.9 L |
| 3.00 | Earth work in bulk excavation for foundation, footing by mechanical means (hydraulic excavator) over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 m2 on plan) including disposal of excavated earth lead upto 50 meters and lift upto 1.5 m which includes surface dressing and Contours wihtout damaging public property & Govt. Property. All kinds of soil | 28,500 | Cum | 153 ₹43.6 L | 188 ₹53.6 L | 140 ₹39.9 L |
| 4.00 | Earth work in excavation by mechanical means (hydraulic excavator) in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed, within a lead of 50 meters wihtout damaging public property & Govt. Property in All kinds of soil | 7,200 | Cum | 153 ₹11.0 L | 230 ₹16.6 L | 170 ₹12.2 L |
| 5.00 | Earth work in bulk excavation by manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 m2 on plan) including disposal of excavated earth lead upto 50 meters and lift upto 1.5 m, wihtout damaging public property & Govt. Property in All kinds of soil. | 1,862 | Cum | 53 ₹98,686 | 267 ₹5.0 L | 170 ₹3.2 L |
| 6.00 | Extra for every additional lift of 1.5 m or part thereof in excavation/banking excavated or stacked material outsite the mucipal limits in All kind of soil. | 4,661 | Cum | 50 ₹2.3 L | 12 ₹55,932 | 60 ₹2.8 L |
| 7.00 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering all work up to plinth level in 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate) 40mm nominal size crushed. | 1,412 | Cum | 4,800 ₹67.8 L | 5,816 ₹82.1 L | 4,900 ₹69.2 L |
| 8.00 | Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-incharge. Note: - Cement in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is content considered payable or recoverable separately. All works upto plinth level (InclWater Tank) | 9,499 | Cum | 7,200 ₹6.8 Cr | 7,646 ₹7.3 Cr | 7,000 ₹6.6 Cr |
| 9.00 | Providing and laying in position machine batched and machine mixed design mix M-30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-incharge. Note: - Cement in this item is @ 340 kg/ cum. Excess or less cement used as per design mix is content considered payable or recoverable separately. All works upto plinth level. | 518 | Cum | 3,000 ₹15.5 L | 7,793 ₹40.4 L | 7,100 ₹36.8 L |
| 10.00 | Extra for providing richer mixes at all floor levels. Note:- Excess/ less cement over the specified cement content used is payable/ recoverable separately. Providing M-30 grade concrete instead of M-25 grade BMC/RMC. (Note:- Cement content considered in M-30 is @ 340 kg/cum) | 2,000 | Cum | 400 ₹8 L | 110 ₹2.2 L | 100 ₹2 L |
Tender Value
₹110.5 Cr
Closing Date
15 Nov 2021, 6:00 pmClosed
XEN PWD Udhampur
Udhampur
Please refer to BOQ
2021_PWDJK_143617_1
e-NIT No. 99 of 2021-22 dated 12.10.2021
Open Tender
Civil Works
900 days
Udhampur
Please refer to tender document
3 documents required · 3 mandatory
₹12,000
CAO PW RandB Department Jammu
Exempted
Jammu
10 Dec 2021
12 Oct 2021
16 Nov 2021
13 Oct 2021
15 Nov 2021
13 Oct 2021
21 Oct 2021
Amount
SUB HEAD - I: CIVIL WORK
Surface dressing of the ground including removing vegetation and in-equalities not exceeding 15 cm deep and disposal of rubbish, lead upto 50 m and lift upto 1.5 in all kind of soil
Earth work in bulk excavation for foundation, footing by mechanical means (hydraulic excavator) over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 m2 on plan) including disposal of excavated earth lead upto 50 meters and lift upto 1.5 m which includes surface dressing and Contours wihtout damaging public property & Govt. Property. All kinds of soil
Earth work in excavation by mechanical means (hydraulic excavator) in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed, within a lead of 50 meters wihtout damaging public property & Govt. Property in All kinds of soil
Earth work in bulk excavation by manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 m2 on plan) including disposal of excavated earth lead upto 50 meters and lift upto 1.5 m, wihtout damaging public property & Govt. Property in All kinds of soil.
Extra for every additional lift of 1.5 m or part thereof in excavation/banking excavated or stacked material outsite the mucipal limits in All kind of soil.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering all work up to plinth level in 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate) 40mm nominal size crushed.
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-incharge. Note: - Cement in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is content considered payable or recoverable separately. All works upto plinth level (InclWater Tank)
Providing and laying in position machine batched and machine mixed design mix M-30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-incharge. Note: - Cement in this item is @ 340 kg/ cum. Excess or less cement used as per design mix is content considered payable or recoverable separately. All works upto plinth level.
Extra for providing richer mixes at all floor levels. Note:- Excess/ less cement over the specified cement content used is payable/ recoverable separately. Providing M-30 grade concrete instead of M-25 grade BMC/RMC. (Note:- Cement content considered in M-30 is @ 340 kg/cum)
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-incharge. Note: - Cement in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is content considered payable or recoverable separately.All works above plinth level upto floor V level.
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded brick aggregate 40 mm nominal size below flooring, retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchors blocks, plain window sills, fillets etc upto floor V level, including curing but excluding the cost of centring, shuttering and finishing.
Brick work with common burnt clay F.P.S (non modular) bricks of class designation 75 upto plinth level in cement mortar 1:4 (1 cement : 4 fine sand).
Providing and laying DPC 50mm thick in 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size crusher aggregate).
Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level with 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size)
Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level with 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)
Brick work with common burnt clay F.P.S (non modular) bricks of class designation 75 in super structure in cement mortar 1:6 (1 cement : 6 fine sand).
Extra for brick work with common burnt clay bricks/cement concrete bricks in superstructure above plinth level upto floor five level.
Half brick masonry with bricks of class designation 75 in foundation, plinth and superstructure upto floor V-level in cement mortar 1:4 (1 cement : 4 coarse sand).
Extra for providing and placing in position 2 Nos. 6mm dia. M.S. bars at every third course of half brick masonry (with F.P.S bricks).
Applying a coat of residual petroleum bitumen of grade VG-10 of approved quality using 1.7 kg per square meter on damp proof course after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil.
Reinforcement for RCC work including straightening, cutting, bending, placing in position and binding all complete TMT bars.
Centering and shuttering including strutting, propping etc. and removal of form work for :-
Foundations, footings, bases of columns.
Suspended floors, roofs, landings, balconies and access platforms.
Columns, pillars, piers, abutments, posts and struts.
Lintels, beams, plinth beams, girders, bressumers and cantilevers.
Edges of slabs and breaks in floors and walls upto 20cm wide.
Retaining walls, return walls, wall (any thickness) including attached pilasters, buttresses, plinth and string courses fillets etc.
Weather shade, chajjas, corbels etc. including edges.
Stairs (excluding landings) except spiral stair cases.
Shelves (cost in situ).
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc. including cost of de-shuttering and decentring at all levels, over a height of 3.5m, for every additional height of 1 mtr. of part thereof (Plan area to be measured). Suspended floors, roofs landing, beams and balconies (Plan area to be measured).
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead upto 50 m and lift upto 1.5 m.
Supplying and filling in plinth with fine sand under floors including, watering, ramming consolidating and dressing complete.
6mm thick cement plaster to ceiling of mix 1:3 (1 cement : 3 fine sand).
15mm cement plaster on the rough side of single or half brick wall of mix in 1:6 (1 cement : 6 fine sand).
15mm cement plaster on the rough side of single or half brick wall of mix 1:4 (1 cement : 4 fine sand).
12mm cement plaster of mix 1:6 (1 cement : 6 fine sand).
18 mm thick moulded cement mortar band in two coats under layer 12 mm thick with cement mortar 1 : 5 (1 cement : 5 coarse sand) top layer 6mm thick with cement mortar 1 : 4 (1 cement : 4 fine sand) for 4 cm width.
Extra for plastering exterior walls of the height more than 10 Mtrs from ground level for every additional height of 3 Mtrs or part thereof.
Add or deduct for plaster drip coarse / groove in plastered surface of moulding to RCC projections.
Making of grove 12mm x 10mm between brick and RCC.
Providing and laying Double Charged vitrified floor tiles in 600x1200mm (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622 of approved make of Somany, Kajaria and Johnson in all colours and shades, laid on 20mm thick cement mortar 1:4 (1cement :4 coarse sand) including grouting the joints with white cement and matching pigments etc. complete.
Providing and laying glossy finished full-body vitrified premium quality floor tiles of 60x60cm sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622 of approved make of Somany, Kajaria and Johnson make in colours and shade Ethnic-Berlinetta White, Crown White, Dacia White, Dacia Green, Dacia Pink, Dacia Ivory, Dacia Grey, Dacia Brown, Dacia Pearl, Dezzling White, Evalia, S&P Grey, S&P Brown, Ultra White, Haze Grey and Border of Royale- Crown Mint, Crown Pink, Crown Snow, Micra Brown and Radiant- Lawrence Gold, Lawrence Bianco, Lawrence Grigio, Lawernce Moka, Techstone and Geostone series laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand) including grouting the joints with matching Epoxy etc. complete.
Providing and fixing Ist quality ceramic glazed tiles conforming to IS : 15622 of minimum thickness 5mm thick of approved make like Somany,Kajaria and Johnson make in colour and shades Glosstra Plus-Lithor Light, Lithor Dark, Canica Light, Canica Dark, Gentil Light, Gentil Dark, Sterno light, Sterno Dark, Marfil Beige, Cream Glossy, Arian Bianco, Bello Mint Dark, Camia Light, Verde Dark, Fabro Brown Dark, Marina Blue, Strix Grey Vivo Crema, Vivo Mushroom of size 300x450mm as approved by Engineer in charge in skirting, risers of steps and dodos and verticle surfaceover 12mm thick bed of cement mortar 1:3 (1cement : 3coarse sand) and jointing with grey cement slurry @ 3.3Kg per sqm including pointing in white cement mixed with pigment of matching shade complete.
Providing and fixing ceramic glazed floor tiles (non-skidding) 300x300mm (thickness to be specified by the manufactures) of Ist quality conforming to IS : 13755 of Somay,Kajaria and Johnson make in colour such as white, Ivory, Grey, Fume Red, Brown laid on 20mm thick bed of cement mortar 1:4 (1 cement : 4 coarse sand) including pointing the joints with white cement and matching pigment etc. complete.
40mm thick Agara Red stone slab flooring over 20mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of slab, complete with base of cement mortar 1:4 (1 cement : 4 coarse sand)
Kota stone slab flooring 25 mm thick over 20mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of slab, incl polishing rubbing, plishing and rubbung,complete with base of cement mortar 1:4 (1 cement : 4 coarse sand)
Providing and laying 18mm thick Granite of any colour and shade (area of slab over 0.5 Sqm) gang saw cut mirror polished (pre moulded and pre polished), machine cut for Floor and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing moulding and polishing to edge to give high gloss finish etc. complete at all levels.
Providing and laying 16mm thick Granite of any colour and shade (area of slab over 0.5 Sqm) gang saw cut mirror polished (pre moulded and pre polished), machine cut for Floor and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing moulding and polishing to edge to give high gloss finish etc. complete at all levels.
Providing and laying 16mm thick Granite of any colour and shade (area of slab over 0.5 Sqm) gang saw cut mirror polished (pre moulded and pre polished), machine cut for kitchen platform, vanity counters window sills facias and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing moulding and polishing to edge to give high gloss finish etc. complete at all levels.
Extra for providing edge moulding to 18mm thick Granite stone counters, Vanities etc. over item No. 41 including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-charge
Extra for providing opening of required size and shape for wash basins/kitchen sink in kitchen platform, vanity counters and similar location in marble / stone work including necessary holes for pillar taps etc. including rubbing and polishing of cut edges etc. complete.
Providing and fixing of block door shutters 37mm thick in pine wood filling and finished with 1mm thick laminated on both sides (laminate Make:- Green, Archidply). Door held with 4 No. stainless steel but hinges of size 100mm X 50mm X 2mm of make Kitch, Arch, Blum with necessary stainless screws as per directions of Engineer-in-charge with teak wood beading on periphery of the door.
Extra for providing heavy sheet float glass panes instead of ordinary float glass in glazed doors, windows and clerestory window shutters. (Area of opening for glass panes excluding portion inside rebate shall be measured) 5.0mm thick instead of 4 mm thick
Providing and fixing 10mm thick acid and / or alkali resistant tiles of approved make of Somay, Kajaria, Orient and NITCO and colour Gold plus, Salted peeper light colour using acid and / or alkali resisting mortar bedding and joints filled with acid and / or alkali resisting cement as per IS : 4457 complete as per direction of Engineer-in-charge. In flooring on a bed of 10mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand). Acid and alkali resistant tile (size 60x60cm).
Providing and fixing of exterior wall cladding made of Grc of size 8” x 2 ¼” (Brick type) made by using high quality pigments, with ruff texture finish with acrylic urethane transparent coating to prevent it from aungus nad elgae. Shade / colour to be approved by the Engineer-in-charge. Tiles to be fixed by using grey cement and curing to be done twice a day for proper bonding. The tiles to be fixed on dry plaster surface with spacer of 5mm and then filled it with matching grout and then deep cut pointing horizontally and vertically. Make :- Classic – GRC, Granimitz (UNISTONE).
Wooden planking, tongued and grooved in flooring including fixing with iron screws complete 18 mm thick Second class teak wood
Providing and laying integral cement based water proofing treatment including preparation of surfaces as required for treatment of roofs, balconies, terraces etc. (Make Armocreate of SWC Chryso France) consisting of (a) applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300mm height including cleaning the surface before treatment. (b) Laying brick bats with mortar using broken bricks / brick bats 25mm to 115mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20mm thick layer of cement mortar of mix 1:5 admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining was upto 300mm height including rounding of junction of walls and slaps. (c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg / sqm of cement admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge. (iv) Finishing the surface with 20mm thick joint less cement mortar of mix 1: 4 admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge including laying glass fiber cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300mm / sq 3mm deep. (e) The whole terrace so finished shall be flooded with water far a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by Engineer-in-charge. With average thickness of 120mm and minimum thickness at khurras as 65mm.
Providing and laying water proofing treatment (Make Armocreate of SWC Chryso France) to vertical and horizontal surface of depressed portions of W.C., kitchen and the consisting of (i) Ist course of applying cement slurry @ 4.4 kg /sqm mixed with water proofing compound conforming to IS : 2645 in recommended proportions including rounding of junctions of vertical and horizontal surface. (ii) IInd course of 20mm cement plaster 1:3 (1 cement : 3 coarse sand) mixed with water proofing compound in recommended proportions including rounding of junctions of vertical and horizontal surface. (iii) III course of applying blown or / residual bitumen applied hot at 1.7 kg per sqm of area. (iv) Ivth course of 400 micron thick PVC sheet (Overlaps at joints of PVC sheet should be 100mm wide and pasted to each other with bitumen @ 1.7 kg/sqm.
Making plinth protection 50mm thick cement concrete 1:3:6 (1 cement : 3 course sand : 6 graded stone aggregate 20mm nominal size) over 75mm bed of dry brick ballast 40mm nominal size well rammed and consolidated and grouted with fine sand including finishing the top smooth crushed and curing complete.
Brick edging 7 cm wide 11.4cm deep to plinth protection with bricks of class designation 75mm including grouting with cement mortar 1:4 (1 cement : 4 fine sand) and curing complete.
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate Z. sections and other sections of approved make conforming to IS : 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fastners including necessary filling up of gaps at junctions at top, bottom and sides with required PVC / neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / panelling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge (glazing and panelling to be paid for separately) (2.60mm or 12 gauge).
For fixed portion. Powder coated aluminum (minimum thickness of powder coated 50 microns)
For shutters of doors, windows and ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/neoprene gasket required (Fittings shall be paid for separately). Powder coated aluminium (minimum thickness of powder coated 50 microns)(2.60mm or 12 gauge).
Providing and fixing glazing in aluminium door, window, ventilator shutters and partition etc. with PVC / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer-in-charge. (Cost of aluminium snap beading shall be paid in basic item). With glass panes of 5.00 mm thickness (weight not less than 12.50 kg/sqm). (Saint Govin/Modi Gaurd make)
Providing and fixing 12mm thick prelaminated three layer medium density (exterior grade) particle board Grade-I, Type-II conforming to IS : 12823 bonded with phenol formaldehyde synthetic resin, of approved brand and manufacture in panelling fixed in aluminium doors, windows shutters and partition frames with C.P brass / stainless screws etc. compete as per architectural drawings and directions of Engineer-in-charge. Pre-laminated particle board with decorative lamination on both sides.
Providing and fixing double action hydraulic floor spring of approved brand and manufacture IS : 6315 marked, having brand logo embossed on the body/plate with double spring mechanism and door weight upto 125 kg for doors including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineerin- plate etc. complete as per the direction of Engineer-in-charge with brass cover plate minimum 1.25 mm thickness. (A)
Providing and fixing fly proof stainless steel grade 304 wire gauze with 0.5mm dia wire and 1.4mm wide aperture in aluminium door, window, ventilator shutters and partition etc. with PVC / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer-in-charge. (Cost of aluminium snap beading shall be paid in basic item).
Providing and fixing aluminium tower bolts ISI marked (anodized anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete.
Providing and fixing aluminium sliding door bolts ISI marked (anodized anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete. 300x16mm.
Providing and fixing aluminium handles ISI marked (anodized anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete.
Providing and fixing aluminium hanging floor door stopper ISI marked anodized (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete. Single rubber stopper.
Providing and fixing aluminium pull bolt lock anodized ISI marked (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade with necessary bolt nuts and washers etc. complete.
Providing and fixing double action hydraulic floor spring of approved brand and manufacture IS : 6315 marked, having brand logo embossed on the body/plate with double spring mechanism and door weight upto 125 kg for doors including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineerin- plate etc. complete as per the direction of Engineer-in-charge with brass cover plate minimum 1.25 mm thickness. (B)
Providing and fixing 100 mm brass locks (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete.
Providing and fixing 12mm thick frameless toughened glass door shutter of approved brand and manufacture including providing and fixing top and bottom pivot and spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge (door handle, lock and stopper etc. to be paid separately). with all fittings like S.S. Spider and door holding accesseries. (Saint Govin /Modi Gaurd)
Providing and fixing anodized aluminium grill (anodized transparent or dyed to required shade according to IS : 1868 minimum anodic coating of Grade AC 15 of approved design / pattern, with approved standard section and fixing to the existing windows frame with C.P. brass/stainless steel screws @ 200mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodized aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge. (only weight of grill to be measured for payment).
Filling the gap in between aluminium frame and adjacent RCC /Brick/Stone work by providing weather silicon sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-in-charge complete upto 5mm depth and 5mm width
Providing and fixing structural glazing on required portion of the building with aluminium section (12 gauze using 5.5mm toughen glass with all necessary fittings Complete job) as per direction of Engineer-in-charge (AIS CHROMA – VLT – 23, u.v-4, SHGC-26, U Value-3.7.
Providing and fixing of Acoustical ceiling with 30% total area with black painted 8mm thick Hilus Calium Silicate in a way of step including G.I framing as per instructions (manual of manufacturer) and 70% area with 10mm GRG Acoustical panels (diamond made) 595x595Sqm edge with NRD > or 0.75 RH : 99% fire resistance clause A 85-475 (suspension system) laid on powder coated “T” grid (24mm) made “Diamond” with batching of 50mm mineral wool complete job as per drawing.
P/F of 8mm thick Pleni Hilux Calcium Silicate ceiling moisture proof and heat proof with G.I framing. Providing Acoustical wall cladding Upto 4' and Above 4’ upto ceiling level, covering on corner of walls and ends of windows with 8mm thick Hilux Calcium Silicate block painting and combination of 10mm GRG 595x595 Acoustical panel (diamond made) with 50mm thick mineral wood back filler filled and fixed with G.I framing as per instructions and drawings
Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes channels, plates etc. including welding ,grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete ,including fixing the railing with necessary accessories and stainless steel dash fasteners, stainless steel bolts etc. of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.).
Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required in gratings, frames, guard bar, ladder, railings, brackets, gates and similar works.
Providing and fixing false ceiling (ceiling tiles mineral fibre and ceiling 8821 of diamond make) at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25mm widex 1.6mm thick with flanges of 27mm and 37mm at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastner 12.5mm dia x 40mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.5mm of required length with nuts and bolts of required size and other end of angle hanger fixed with G.I channels 45x15x0.9mm running at the spacing of 1200 centre to centre, to which the ceiling section 0.5mm thick buttom wedge of 80mm with tapered flanges of 26 mm each having clips of 10.5mm at 450mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64mm dia x 230mm long G.I wire at every junction, including fixing perimeter channels 0.5mm thick 27mm high having flanges of 20mm and 30mm long, the perimeter of ceiling fixed to wall / partition with the help of rawl plugs at 450mm centre to centre, with 25mm long drive all screws @ 230mm interval, including fixing of gypsum board to ceiling section and perimeter channels with the help of dry wall screws of size 3.5x25mm at 230mm C/C, including jointing and finishing to a flush finish of tapered and square edges of the gypsum board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150mm on both sides of joint and two coats of primer suitable for board, all as per manufactures specification and also including the cost of making openings for light fittings, grills diffusers, cutouts made with frame of perimeter channels suitably fixed all complete as per drawing and specification and direction of Engineer-in-charge. 12.5 mm thick tapered edge gypsum fire resistant board conforming to IS: 2095- Part-I : 2011 (Board with BIS certification marks)
P/F of 8mm thick Pleni Hilux Calcium Silicate ceiling moisture proof and heat proof with G.I framing.
Providing and applying white cement based putty of average thickness 2 mm, of approved brand and manufacture, over the plastered wall surface to prepare the surface even and smooth complete.
Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade new work (two or more coats) over and including priming coat with cement primer.
Applying one coat of water thin able cement primer of approved brand and manufacture on wall surface.
Wall painting with plastic emulsion paint of approved brand and manufacture to give an even shade. Two or more coat on new work.
Finishing wall with premium acrylic smooth exterior paint with silicon additives of required shade on new work (two or more coats applied @ 1.43 ltr./10sqm over and including base coat of water proofing cement paint applied @ 2.20kg/10sqm).
Finishing walls with textured exterior/ interior paint of required shade on New work (two or more coats Rustic Regular of any colour as per Engg. incharge) over and including base coat of exterior primer applied @ 3.00kg/10sqm.
Finishing walls with textured exterior paint of required shade: work (two or more coats on existing cement paint surface applied @ 3.28 ltr/10sqm)
Providing and fixing nickel plated S.S. pipe curtain rods with nickel plated brackets. 25mm dia (heavy type). 4 mm thick exterior grade allmuinum composite sheet with almumium frame work and filling joint with silicon Complete job.
Providing and fixing vertical / roller blinds as per approved make DECK
Providing corrugated G. S. sheet roofing including curved surface fixed with polymer coated J or L hooks, bolts and nuts 8mm diameter with bitumen and G.I limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete (upto any pitch in horizontal/vertical or curved surface)excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. 0.63 mm thick with zinc coating not less than 275 gram/m2
Providing ridges or hips of width 60cm overall width plain G.S. sheets fixed with polymer coated J. or L hooks, bolts and nuts 8mm dia G.I. limpet and bitumen washers complete. 0.63 mm thick with zinc coating not less than 275 gram/m2
Structural steel work in built up sections, trusses of all shape, straight, round, Arch & semi-arch and framed work,including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. Welded
Providing and fixing of polypropylene Carpet floor 8mm thick multi colour in role High density fix with S.R. Adehsive.
Providing corrugated G. S. sheet roofing including vertical surface fixed with polymer coated J or L hooks, bolts and nuts 8mm diameter with bitumen and G.I limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete (upto any pitch in horizontal/vertical or curved surface)excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. 0.50 mm thick with zinc coating not less than 275 gram/m2
Providing ridges or hips of width 60cm overall width plain G.S. sheets fixed with polymer coated J. or L hooks, bolts and nuts 8mm dia G.I. limpet and bitumen washers complete. 0.50 mm thick with zinc coating not less than 275 gram/m2
Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked indicating the BIS License No. with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank (Sintex, Electroplast, star, Lotous or equivalent having valid ISI license) (3000 ltr)
Providing and fixing aluminium composite panel with specific aluminium channel as per approved make with 4mm thick aluminium composite sheet and joint filling with silicone complete as directed by Engineer-in-charge.
Providing and fixing vertical / roller blinds of approved quality as per architectural drawings and the directions of Engineer-in-Charge. N.S.I
Providing and fixing of expansion joint system of approved make and manufactures for various roof locations as per approved drawings and direction of Engineer-In- Charge. The joints shall be of extruded aluminum base members with, self aligning and self centering arrangement support plates as per ASTM B221-02. The system shall be such that it provides watertight roof to roof/roof to corner joint cover expansion control system that is capable of accommodating multidirectional seismic movement without stress to its components. System shall consist of metal profile that incorporates a universal aluminum base member designed to accommodate various project conditions and roof treatments. The cover plate shall be designed of width and thickness required to satisfy movement and loading requirements and secured to base members by utilizing manufacturer’s preengineered self-centering arrangement that freely rotates/ moves in all directions. The self centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. The Joint system shall resists damage or deterioration from the impact of falling ice, exposure to UV, airborne contaminants and occasional foot traffic from maintenance personnel. Provision of Moisture Barrier Membrane in the Joint system to have water tight joint is mandatory requirement. Material shall confirm to ASTM 6063 Roof joint of 100 mm gap horizontal joint cover with 1.5mm thick S.S. Sheet movealbe screw
Providing and fixing of expansion joint system related with wall joint (internal/ external) location as per drawings and direction of Engineer-In-Charge. The joints shall be of extruded aluminum base members, self aligning / centering arrangement and support plates as per ASTM B221-02. The material shall be such that it provides an Expansion Joints System suitable for vertical wall to wall/ wall to corner application, both new and existing construction in office Buildings & complexes with no slipping down tendency amongst the components of the Joint System. The Joint System shall utilize light weight aluminum profiles exhibiting minimal exposed aluminum surfaces mechanically snap locking the multi-cellular to facilitate movement. (Material shall confirm to ASTM 6063.) Wall joint of 100 mm gap
Providing and laying integral cement based treatment for water proofing on horizontal surface at all depth below ground level for underground structures as directed by Engineer-in-Charge and consisting of : i) 1st layer coarse sand) mixed with water proofing compound conforming to stone slab over a 25 mm thick base of cement mortar 1:3 (1 cement : 3of 22 mm to 25 mm thick approved and specified rough IS:2645 in the recommended proportion over the levelling course (levelling course to be paid separately). Joints sealed and grouted with cement slurry mixed with water proofing compound.ii) 2nd layer of 25mm thick cement mortar 1:3 (1 cement: 3 coarse sand) mixed with waterproofing compound in recommended proportions. iii) Finishing top with stone aggregate of 10 mm to 12 mm nominal size spreading @ 8 cudm/sqm thoroughly embedded in the 2nd layer. Using rough kota stone.
Providing and laying integral cement based treatment for water proofing on the vertical surface by fixing specified stone slab 22 mm to 25 mm thick with cement slurry mixed with water proofing compound conforming to IS:2645 in recommended proportions with a gap of 20 mm (minimum) between stone slabs and the receiving surfaces and filling the gaps with neat cement slurry mixed with water proofing compound and finishing the exterior of stone slab with cement mortar 1:3 (1 cement : 3 coarse sand) 20mm thick with neat cement punning mixed with water proofing compound in recommended proportion complete at all levels and as directed by Engineer-in-Charge: Using rough kota stone.
Design manufacture, supply, installation, testing and commissioning of Lift (Gearless with Machine room) of following specifications:- Drive Machine :- Geared Traction Load Capacity :- 884 Kg Passenger Capacity :- 13 persons Control System :- Simplex automatic operation Maximum no. of stops :- 5 Max. rise :- 25 meters Car speed :- 1.5m/s Power Supply :- 3 phase, 400/415V(+/-10) volts, 50(+/-5) Hz frequency Entrance :- Front only Door :- Automatic (Centre opening door) Car inside :- 1100mmX2000mm Hoistway size :- 1850mm X 2350mm Pit(mm) :- 1600 MAKE:- OTIS or Equivalent
Carriage of material by Mechanical Transport including loading / unloading and stacking at site complete.
Sand for an average lead of 40 Kms.
Stone aggregate below 40mm size for an average lead of 10 Kms.
Stone aggregate 40mm size and above for an average lead of 10 Kms.
Bricks for an average lead of 70 Kms
Paver Block
Providing, laying and making kerb channel 30cm wide and 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) over 75mm bed of dry brick ballast 40mm nominal size well rammed and consolidated and grouted with fine sand including finishing the top smooth etc. complete as per direction of Engineer-incharge for paver tiles
Providing and laying 80mm thick factory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge.
Providing and laying 60mm thick factory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge.
Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge).Size 300x250x100mm
SUB HEAD - II: PLUMBING
Providing & fixing of white vitreous China pedestial type water closet (European Type) with cistern (Hindware 92047) (S-30) with CP bolts, nuts, CI chair hanging arrangements, bakelite seat & cover with CP hinges & rubber buffers, CP brass screw, washer with all accessories with WC connector with Rubber Lip / Buffer and side gap filled with silicon sealant wherever required. Including brass / SS screws and washer complete including cutting, making good the walls, floors, slab wherever required as per direction of Engineer-in-charge.
Providing & fixing of white vitreous China pedestial type water closet (European Type) with cistern (A/PHAS-100 Cat No. 201100+Cat No. 21054) with CP bolts, nuts, CI chair hanging arrangements, bakelite seat & cover with CP hinges & rubber buffers, CP brass screw, washer with all accessories with WC connector with Rubber Lip / Buffer and side gap filled with silicon sealant wherever required. Including brass / SS screws and washer complete including cutting, making good the walls, floors, slab wherever required as per direction of Engineer-in-charge.
Providing and fixing water closet squatting pan ( Indian type W.C. pan) with 100 mm sand cast Iron P or Strap, 10 litre low level P.V. C. flushing cistern including flush pipe (of approved make) "manually controlled device (handle lever) conforming to IS:7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required. Orissa pattern white vitreous china W.C. pan of size 580x440 mm with integral type foot rests.
Providing and fixing of C.P. brass Central Hole Basin Mixer without Popup Waste System including with 450mm Long Copper Pipes & Brass Nuts with all fittings and accessories as per direction of Engineer-Incharge. (Jaquar CQT23167 D)
Providing & fixing of white vitreous china wash basin with pedestal (Hindware Cat No. 1008 + Ped Cat No. 11003) with CP brass waste assembly, CP cast brass bottle trap with extension piece (Jaquar Cat No. 769B + Parko1535 or approved equivalent), 450mm long CP copper connections pipes (Jaquar Cat No. 803B or Parko 1535 or approved equivalent), wall flanges and rubber adapters for waste connection complete including CI/MS brackets duly painted, nuts, washers, cutting and making good the walls floors wherever required as per direction of Engineer-Incharge.
Providing & fixing white vitreous china flat back urinal with automatic flushing systems (Hindware 60021) comprising of all plumbing, electronic and electrical items. CP brass flush pipe with CP brass elbow, CP brass spreader, CP wall flange, infrared photo cells, eyes electrically operated solenoid valve, step down transformer / equipment and any other item required to provide satisfactory functioning including necessary wall cutting / chasing and making good, as required for urinal flushing complete as mentioned above as per direction of Engineer-Incharge.
Providing and fixing white vitreous china battery based infrared sensor operated urinal of approx. size 610 x 390 x 370 mm having pre & post flushing with water (250 ml & 500 ml consumption), having water inlet from back side, including fixing to wall with suitable brackets all as per manufacturers specification and direction of Engineer-in-charge.
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS 13983 with C.I. brackets and stainless steel plug 40 mm including painting of fittings and brackets, cutting and making good the walls wherever required:
Kitchen sink with drain board 510 x 1040 mm bowl depth 225 mm.
Kitchen sink without drain board 610 x 460 mm bowl depth 200 mm.
Providing & fixing C.P. hand spray with lever control (health faucet) (Jaquar Cat. No. ALDCHR-565) and flexible hose 1 m long connection with C.P. holder for hand spray complete in all respects as per direction of Engineer-Incharge.
Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C waste fittings complete: Semi rigid pipe 32 mm dia
Providing and fixing 6mm copper backed float glass mirror MODI / SAINT-GOBAIN including 6mm thick BWR type ply board, 40mm stainless steel channel plugged to wall, hard wood treated with two coats of wood preservative, etc. all complete as specified and shown in drawing complete to the satisfaction of Engineer in charge.
Providing and fixing toilet paper holder. (Jaquar Continental ACN1151 N)
Bottle trap 31 mm single piece moulded with height of 270 mm, effective length of tail pipe 260 mm from the centre of the waste coupling 77 mm breadth with 25 mm minimum water seal, weighing not less than 260 gms.
Providing and fixing PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with brackets of the same materials with snap fittings of approved quality and colour, weighing not less than 105 gms.
Providing and fixing 15 mm nominal bore C.P. brass bib cock of approved quality conforming to IS : 8931
Providing and fixing 15 mm nominal bore C.P. brass long nose bib cock of approved quality conforming to IS standards and weighing not less than 810 gms.
Providing and fixing 15 mm nominal bore C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms
Providing and fixing 15 mm nominal bore C.P. stop cock (concealed) of standard design and of approved make conforming to IS : 8931
Providing and fixing 15 mm nominal bore C.P. brass angle valve for basin mixer and geyser points of approved make conforming to IS : 8931
Providing and fixing C.P. Brass extension nipple (size 15mmx50mm) of approved make and quality as per direction of Engineer-in-charge.
Providing and fixing 15 mm nominal bore of standard back type C.P. brass close hole basin mixer pillar tap of approved quality and make,weighing not less than 1.970 kg.
Providing & fixing C.P. S.S. Coat hook / robe hook (Jaquar Cat. No.- ACN-CHR-1161N approved equivalent) fixed to wall/door with plastic rawl plugs and C.P brass screws including cutting and making good the walls wherever required as per direction of Engineer-Incharge.
Plastic/ABS High Speed Hand Dryer Supplying of Touch free ABS Plastic hand dryer , Hand Dry Time : Less than 20 Seconds, Protection Class: IPX1 Blowing Volume: > 90 m3/h, Air Speed : 33 m/s – 37 m/s, Color : White
Providing & fixing S. Steel paper dispenser (Euronics Cat No. EP 01 or approved equivalent) as per direction of Engineer-Incharge.
Providing and fixing complete set of sanitary fixtures for handicapped toilets, Hindware Cat. no. 70002) comprising of EWC - P , Cistern, Seat Cover, Twin Flush Fittings, Wash Basin 450x300, Half pedestal, 1 faucet with spatula lever, 1 hinged rail and 2 grab bars, including cutting and making good the walls and floors wherever required complete as per directions of Engineer in charge.
Providing and fixing stainless steel jali (grating) without hole for waste pipe for floor trap & floor drain Size 125mm dia flat cover matt finish
Providing, storing, handling, shifting, installation, testing & commissioning of vertical / horizontal storage type hot water heater fixed to wall with anchor bolts & nuts, 20mm CP brass cock and 20mm non return valve complete including making connection with 15 mm dia CP connecting pipe on Inlet and Outlet, suitable length of power cable and 15A plough (for pantry & Toilets).
Capacity 15 liters
Capacity 25 liters
Capacity 35 liters
Providing & fixing storage type water cooler with plain & cold water facility of the following capacity, I.S.I marked, stainless steel front panel, C.P brass push cock, inlet float valve with all plumbing and electrical accessories, inlet, outlet, overflow and PVC drain out connection to F.D complete as required (Blue Star / Voltas or equivalent).
Cooling capacity 20 Lts./hr (Model No. Bluestar PC240) Storage capacity 40 Lts.
Cooling capacity 40 Lts./hr (Model No. Bluestar PC480) Storage capacity 80 Lts.
Providing and fixing CP Double Elbow action Surgical Basin mixer (Floor mounted) complete (Vijay Cat No: 1125)
INTERNAL DRAINAGE (SOIL, WASTE,VENT & RAIN WATER DISPOSAL PIPES FITTINGS):
Providing and fixing sound insulated Polyproplene piping (PP) system as per ON EN 1451-Part 1 & EN 12056 Part 1-5 , DIN 1986-100 - class B & D, with 3 layer pipe made of PP/PP-MV/PP in Blue Ral 5014 colour (free from halogen, cadmium and heavy metals), push-fit type, food safe, having high impact and stiffness, offering sound levels of not more than 16 dBA as per DIN 4109 at a flow rate of 4 l/s and having pipe ring stiffness of 6kN/m2 or more as per EN ISO 9969, density and elongation of pipe not more than 1.25gms/cm3 and 0.05mm/m0K respectively, tensile strength to be > 24 N/mm2, cost including all necessary fittings in blue colour, fitted with factory fitted lip ring Pipes and fittings to carry a 20 year guarante including supporting system GI clamps / hangers/G.I structure supports as per approved make with angle & fastner as required. including cost of core/hole cutting and making good the walls and floors wherever required. (Approved Make-Astral silcon/Rehau/shanah )
160mm dia
110mm dia
75 mm dia
Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams.
Providing, laying, testing & commissioning of UPVC pressure pipes of 6 Kg/Sq.cm pressure rating class V (IS : 4985-2000) including fittings, tees, bends, clamps, coupling and adaptors supports, and jointing with solvent joint, testing and necessary earth work in excavation, backfilling, disposal of surplus earth with a lead upto 50m complete, compaction and consolidation including bed concrete (if required), sand bedding all around UPVC pipe & fittings and thrust blocks at bends as per standard design (for Drainage Sump Pump Discharge Header).
110 mm dia
160 mm dia
200 mm dia
Providing and fixing sound insulated Polyproplene piping (PP) system as per ON EN 1451-Part 1 & EN 12056 Part 1-5 , DIN 1986-100 - class B & D, with 3 layer pipe made of PP/PP-MV/PP in Blue Ral 5014 colour (free from halogen, cadmium and heavy metals), push-fit type, food safe, having high impact and stiffness, offering sound levels of not more than 16 dBA as per DIN 4109 at a flow rate of 4 l/s and having pipe ring stiffness of 6kN/m2 or more as per EN ISO 9969, density and elongation of pipe not more than 1.25gms/cm3 and 0.05mm/m0K respectively, tensile strength to be > 24 N/mm2, cost including all necessary fittings in blue colour, fitted with factory fitted lip ring Pipes and fittings to carry a 20 year guarantee. for wash basin, urinals, indirect waste, Bath Tub etc.
Providing and fixing Polyproplene P floor trap with 2/3 inlets of 40/50 mm size and one outlet of 110 mm size, inlet connection extension pipe piece and setting in cement concrete 1:2:4 mix complete including cost of cutting and making good the walls and floor complete where ever required 110 mm inlet & 110 mm outlet.
Providing and fixing floor drain (FD) with 50mm/40mm outlet and one 40mm inlet for waste, with SS grating (adjustable height), having 50mm water seal and in-built NRV (McAlpine mrfg3 ).Providing and fixing floor drain (FD) with 100 mm inlet and 50mm outlet including SS grating
Providing & fixing Polyproplen clean out Plug (FCO & COP) with suitable insert keys for opening, male threaded joint with socket soil pipe/waste pipe of Polyproplen pipe as required. (Both for Pipes running under floor & along ceiling level)
Providing & fixing Polyproplen door cleaning piece male threaded joint with socket soil pipe/waste pipe of Polyproplen pipe as required. (Both for Pipes running under floor )
Providing and laying cement concrete 1:5:10 (1 cement: 5 coarse sand: 10 graded stone aggregate 40 mm nominal size) including bed concrete as per standard design.100 mm diameter S.W. pipe
DOMESTIC / FLUSHING/ COLD & HOT WATER SUPPLY :
PE-AL-PE COMPOSITE PRESSURE PIPE
INTERNAL WATER SUPPLY SYSTEM
Providing and fixing Polyethelene-Aiuminium-Polyethelene (PE-AL-PE) Composite Pressure Pipes conforming to conforming to IAPMO-IGC-308-2014 U.V. stabilised with carbon black having thermal stability for hot and cold water supply, capable to withstand temperature upto 80°Cincluding all special brass fittings of composite material (engineering plastic blend and brassinserts wherever required) e"g. Elbows, tees, reducers,couplers and connectors etc. with clamps at one meter spacing. This includes testing of joints complete as per direction of the Engineer-in-charge:make Kitec, Vista, Maithili .
Internal work-exposed on wall with clamps at 1.00 meter spacing
1216 (16mm OD) pipe
1620 (20mm OD) pipe
2025 (25mm OD) pipe
2532 (32mm OD) pipe
3240 (40mm OD) pipe
4050 (50mm OD) pipe
Internal work concealed with clamps at 1.00 meter spacing including cutting the chases and making good the wall etc.
1216 (16mm OD) pipe
1620 (20 mm OD) pipe
2025 (25 mm OD) pipe
2532 (32 mm OD) pipe
Providing and fixing G.I. pipes complete with G.I. fittings excluding trenching and refilling etc. (external work) (Medium Class)
65 mm dia. nominal bore
80 mm dia. nominal bore
100 mm dia. nominal bore
150 mm dia. nominal bore
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete copatable to connection with composite pipe
15 mm nominal bore
20 mm nominal bore
25 mm nominal bore
32 mm dia. Nominal bore
40 mm dia. Nominal bore
50 mm dia. Nominal bore
Providing and fixing G.l. pipes complete with G.l. fittings and clamps, including cutting and making good the walls etc. INTERNAL WORK-Exposed on wall
15 mm dia. nominal bore (Medium)
20 mm dia. nominal bore (Medium)
25 mm dia. nominal bore (Medium)
32 mm dia. nominal bore (Medium)
40 mm dia. nominal bore(Medium)
50 mm dia. nominal bore(Medium)
Supply, Installation, Testing & Commissioning of Screwed End two way Ball valve:- Body-Forged Brass (IS-6912), Chrome finish; Ball-Copper Alloy (Cu-Alloy), Nickle plated Finish; Seat and Seals - Virgin PTFE (BS6564); Stem - copper alloy(Cu-Alloy), Nickle Plated; Hand Lever- Mild steel with PVC Sleeve to control flow; Screwed Ends to suit BS21BSP/BSPT working pressure (PN 16/25) Make:- NEU-G/RB/I-TAP.
65mm dia.
80mm dia.
100mm dia.
Making connection of G.I. distribution branch with G.I. main of following sizes by providing and fixing Tee, including cutting and threading the pipe etc. complete
25 to 40 mm nominal bore
50 to 80 mm nominal bore
Providing & fixing Auto Air vent for cold water supply risers, suitable for pressure not less than 15 Kg/Sq.cm.
15 mm dia
20 mm dia
Providing and fixing in position of approved quality high pressure rated Brass Float Valve with copper ball float and brass rods of required length suitable for test pressure of not less than 15 Kg/sqcm of the following sizes:
40 mm dia
50 mm dia
Excavation of trenches of required width for pipes etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5m, including getting out the excavated soil, and then returning soil as required, in layers not exceeding 20cm depth including consolidating each deposited layer by ramming, watering etc. and disposing of surplus excavated soil as directed outside the site to the approved dumping ground. Minimum width of the trench should be external dia plus 400mm. Trenches to be excavated with required slope and shall be aligned as per drawing.
Pipes, cables etc, not exceeding 80 mm dia.
Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia
EXTERNAL SEWER AND DRAINAGE SYSTEM
Excavation of trenches of required width for pipes etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5m, including getting out the excavated soil, and then returning soil as required, in layers not exceeding 20cm depth including consolidating each deposited layer by ramming, watering etc. and disposing of surplus excavated soil as directed outside the site to the approved dumping ground. Minimum width of the trench should be external dia plus 400mm. Trenches to be excavated with required slope and shall be aligned as per drawing .
Pipes, cables etc, not exceeding 80 mm dia.
Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia
Providing, fixing, jointing, testing and commissioning of UPVC “NU-DRAIN” for Drainage and sewerage/strom water application Pipe conforming to IS:15328 with all fittings such as bends, tees, elbow. The wall thickness of pipe and technical characteristic conforms to IS:15328 in SN8 stiffness class. The fitting dimension conforming to BS: EN1401-1998. The jointing to be completed with rubber ring/solvent weld joint as suitable at site for above basement level.(Aprroved Make- Supreme/astral/jain)
200 mm diameter
250 mm diameter
300 mm diameter
Providing, fixing, jointing, testing and commissioning of UPVC “ECODRAIN” structured wall Drainage Pipe conforming to IS:16098 (Part-I) with all fittings such as bends, tees, elbow. The wall thickness of pipe and technical characteristic conforms to IS:16098 (Part-I) in SN8. The fitting dimension conforming to BS: EN1401-1998. The jointing to be completed with rubber ring/solvent weld joint as suitable at site for use at non basement area. Make- Supreme/astral/jain
Providing and laying cement concrete 1:5:10 (1 cement: 5 coarse sand:10 graded stone aggregate 40 mm nominal size) including bed concrete as per standard design.
All around S.W. pipe
100 mm diameter S.W. pipe
150 mm diameter S.W. pipe
200 mm diameter S.W. pipe
230 mm diameter S.W. pipe
250 mm diameter S.W. pipe
Upto haunches of S.W. pipe
100 mm diameter S.W. pipe
150 mm diameter S.W. pipe
200 mm diameter S.W. pipe
230 mm diameter S.W. pipe
250 mm diameter S.W. pipe
Providing and fixing square- mouth PVC/S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design.
100x100 mm size P type With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
100x100 mm size P type With Sewer bricks conforming to IS : 4885
150 x 100 mm size P type With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
180 x 150 mm size P type With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
180 x 150 mm size P type With Sewer bricks conforming to IS : 4885
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement: 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone- III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone- III): 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design :
Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) :
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
With Sewer bricks conforming to IS : 4885
Inside size 90x80 cm and 60 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) :
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
With Sewer bricks conforming to IS : 4885
Extra for depth for manholes Size 90x80 cm
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
With Sewer bricks conforming to IS : 4885
Providing orange colour safety foot rest of minimum 6mm thick plastic encapsulated as per IS : 10910 on 12mm dia steel bar conforming to IS : 1786 having minimum cross section as 23 mmx25 mm and over all minimum length 263mm and width as 165mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture’s permanent identification mark to be visible even after fixing. including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 ( 1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design.
Supplying and fixing C.I. cover without frame for manholes:
455x610mm rectangular C.I. cover (light duty) the weight of the cover to be not less than 23 kg.
500 mm diameter C.I. cover (medium duty) the weight of the cover to be not less than 58 kg.
560 mm diameter C.I. cover ( heavy duty) the weight of the cover to be not less than 108 kg
Supplying and fixing C.I. cover 300x300 mm without frame for gully trap (standard pattern) the weight of cover to be not less than 4.5kg.
Making connection of drain or sewer line with existing manhole including breaking into and making good the walls, floors with cement concrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) cement plastered on both sides with cement mortar 1:3 ( 1 cement : 3 coarse sand) finished with a floating coat of neat cement and making necessary channels for the drain etc. complete For pipes 100 to 250 mm diameter
Providing sand cast iron drop connection externally for 60 cm drop from branch sewer line to main sewer manhole including inspection and cleaning eye with chain and lid, sand cast iron drop pipe and bend encased alround with cement concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) with all centering and shuttering required, cutting holes in walls and making good with brick work in cement mortar 1:4 ( 1 cement : 4coarse sand) plastered with cement mortar 1:3 (1 cement :3 coarse sand)on inside of the manhole wall lead caulked joints between sand cast iron pipes and fittings, stiff cement mortar 1:1 ( 1 cement : 1 fine sand) joints between sand cast iron tee and S.W. pipe, making required channels complete as per standard design and specifications :
100 mm dia. sand cast iron drop connection
150 mm dia. sand cast iron drop connection
Extra for depths beyond 60 cm of sand cast iron drop connection complete :
For 100 mm dia. sand cast iron drop connection
For 150 mm dia. sand cast iron drop connection
Providing Horizontal Open well Submersible pumps 3 phase, 5HP,3.7 Kw, with flow upto 1050 LPM, cast Iron impeller, cast iron casting and body with CED coating (corrosion protection) along with 3ph Control panel, Make:- KSB, Grundfos, Wilo. WPO Raptor 50F/3 8224594, 3 Phase, 5Hp, 3.7 KW, Max Head 54 meters, Max LPM 1100 liters, Suction 50mm and 50mm Delivery.
SUB WORK :- FIRE FIGHTING WORKS , ADMACADMIC BLOCK & ANIMAL HOUSE)
Supplying, installation, testing and commissioning of electric driven terrace pump suitable for including control panel automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) Make:- KSB, Grundfos, Wilo. a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure,horiziontal foot mounted type with Class-'F' insulation,conforming to IS-325. (c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. (d) Suitable cement concrete foundation duly plastered and with anti vibration pads.
900 lpm at 35 m Head (acadmic block )
450 lpm at 35 m Head (audotorium block)
Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS3589 i/c fittings like elbows, tees, flanges etc. below 50mm should be of Ductile iron conforming to ASTM A-536, Grade 65-45-12, BSPT threads with FM approval and UL listed. Fittings should be anti rust coated in threadings and anti rust black finish. Make:- NEW/VICTUALIC/TYCO. for fitting above 50mm like elbow, tees, couplings, concentric reducers, flanges etc should be grooved fittings shall be manufactured in two segments of cast ductile iron, conforming to ASTM A-536, Grade 65-45-12. Gasket shall be pressure-responsive EPDM rubber, grade to suit the intended service, conforming to ASTM D-200. Mechanical coupling bolts shall be zinc plated/chrome finish, heat treated carbon steel track conforming to ASTM A-449 and A-183, No welding is to be done anywhere in the fire fighting system. Rubber gasket should be of EPDM grade. The grooving machine shall be supplied by the same company as grooved fittings as to maintain conformity of grooving.Make:- NEW(JTPR)/VICTUALIC/TYCO.
200 mm. dia (wall thickness = 6.3 mm)
150 mm. Dia
Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS3589 i/c fittings like elbows, tees, flanges etc. below 50mm should be of Ductile iron conforming to ASTM A-536, Grade 65-45-12, BSPT threads with FM approval and UL listed. Fittings should be anti rust coated in threadings and anti rust black finish. Make:- NEW/VICTUALIC/TYCO. for fitting above 50mm like elbow, tees, couplings, concentric reducers, flanges etc should be grooved fittings shall be manufactured in two segments of cast ductile iron, conforming to ASTM A-536, Grade 65-45-12. Gasket shall be pressure-responsive EPDM rubber, grade to suit the intended service, conforming to ASTM D-200. Mechanical coupling bolts shall be zinc plated/chrome finish, heat treated carbon steel track conforming to ASTM A-449 and A-183, No welding is to be done anywhere in the fire fighting system. Rubber gasket should be of EPDM grade. The grooving machine shall be supplied by the same company as grooved fittings as to maintain conformity of grooving.Make:- NEW(JTPR)/VICTUALIC/TYCO.
15 mm dia
25 mm dia
32 mm dia
40 mm dia
50 mm dia
65 mm dia
80 mm dia
100 mm dia
150 mm dia
Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required Single headed Gunmetal
Supplying, fixing, testing and commissioning of Waffer type butterfly valve: Body cast iron (IS 210), Epoxy coated; Disc Ductile Iron (ASTM A536), Black Epoxy coated; Seat-Nitrile vulcanized on Hard back up Ring; Stem- Stainless steel Gr.410 (ASTM A276); Hand Lever - Mild steel with notches to control flow; Suitable for insertion b/w BS4504 PN10/16, ASME B16.5 #150 & BS10 Table D/E flanges; Suitable for 16Kg/sqcm working pressure (PN 16); Valve size 200mm and above to be Heavy Duty Gear operated. MAKE;- NEU-G/AUDCO/L&T/KITZ
80 mm dia
100 mm dia
150 mm dia
Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required :
80mm dia
100mm dia
150mm dia
200mm dia
Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.
Providing, installation, testing and commissioning of Cast iron wafer type Dual Plate Check valve conforming to IS 5312; Body-Cast Iron (IS 210), Epoxy coated; Disc- Ductile Iron (ASTM A536), Black Epoxy coated; Seat-Nitrile vulcanized to body. Make:- NEU-G/AUDCO/KITZ.
100mm dia
150mm dia
200mm dia
Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. Make:- NEU-G/AUDCO/KITZ. 150mm dia
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required Gun Metal
Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required: - a) 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585, b) 20 mm nominal internal dia gun metal globe valve & nozzle., c) Drum and brackets for fixing the equipmets on wall., d) Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.40 m
Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required Gun metal
Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :
2 way-100 mm dia M.S. Pipe
3 way - 150 mm dia M.S. Pipe
Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required.
Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :
Pendent Sprinkler
Upright Sprinkler
Horizontal side wall sprinkler
Concealed sprinkler
Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.
Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required.
100mm dia
150mm dia
Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required 150mm dia
Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required.
Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required (E&M)
Providing and fixing MS cabinet (size 750x600x250 mm) fabricated from 16 gauge MS sheet with full front glass door & locking arrangement for pad lock with suitable shelves for keeping 25 Nos. spare sprinklers & one no. spanner properly fixed in shelves. Cabinet shall be painted with enamel paint of approved shade. (Cost shall include 20 Nos. spare sprinklers (5 Nos side wall 20Nos pendent, one No. spanner and 5 rolls of teflon tape ).
Providing & fixing FIRE shaft door with frame section (100X50)mm made up of 1.6mm (16SWG) MS sheet with Powder coated including necessary locking arrangement & 5mm glass with Chest handle as required,including painting (RED Powder Coated ) with "FIRE SHAFT " legend. Size (1200 x 2100) mm
Providing and fixing weather proof lockable cabinet of size notless than 2100mmx900mmx715mm made out of G.I. sheet of 18 gauge thickness having central opening and 4mm thik glazed glass doors(two no.) suitably marked on the out side with the letters FIRE HOSE including necessary locking arrangement and shall be painted with powder coating and two coat of synthetic enamel paint of approved shade. The cabinet shall be suitable to accommodate 2no.or4 no. 15mtr long hose pipe &2no branch pipe nozzle.It shall be mounted on raised brick platform complete as required
PORTABLE FIRE EXTINGUISHERS
Providing & fixing of ISI marked (IS:15683) portable fire extinguisher, carbondioxide type flat base including valve, discharge hose of not less than 10 mm dia. 1 M long & complete in all respects including initial fill with CO2 gas confirming to IS:307-1966 filled to a filling ratio of not more than 0.667 of not more than 0.667 and wall suspension bracket
Capacity 4.5 kg
6 Kg. ABC Powder type fire extinguishers are manufactured and marked to Indian standard IS: 15683. Suitable first aid appliance for fighting fires in Class A, B & C fire that is wood, textile, flammable liquids & gases.
Providing and fixing mechanical foam type fire extingushers consisting of welded M.S. trolley mounted cylindrical body, squeeze lever discharge valve fitted with pressure discharge hose, discharge nozzle, trolley etc., ISI marked as per IS:IS:13386 finished externally with red enamel paint. Capacity 50 lit (D.G.Room)
Providing and fixing carbon-di-oxide fire extingushers trolley mounted with all accessories internal discharge tube,high pressure discharge hose,discharge nozzle, ISI marked as per IS:2878 finished externally with red enamel paint. Capacity 22.5 kg.
SEWAGE TREATMENT PLANT
Sewage Treatment Plant Based on MBBR (Moving Bed Bio Reactor) Technology :
Supply, installation, testing and commissioning of package type pre-fabricated Sewage Treatment Plant based on MBBR technology (Moving Bed Aerobic Bio-reactor) of 175 KLD capacity including all MS structure, mechanical, electrical and instrumentation works as per technical specification mentioned in the document. The scope shall also include to provide the SS bar screen in grit screen chambers, grease separator, primary & secondary treatment of waste water, air blowers, all necessary interconnecting piping & valves, pumps, DMF and ACF filters, chlorinator, ultravoilet dis-infection unit, MCC for operation of all motors, all inter connecting power and control wiring, level controllers & other controls, MS Puddle Flange (Hot dip galvanized after fabrication), inlet, outlet, overflow, vent, manhole cover etc, completed in all respect in ready to use and easy to transport condition. (The entire system to be installed above ground).
Nature of effluent - Domestic Sewage from toilets/kitchen.
Flow Rate - 175 KLD
Sewage Incoming Characteristics
BOD5 - upto 250 - 400 Mg/L
S. Solid - 250 to 450 Mg/L
COD 5 - Upto 600 Mg/L
Oil & Grease - 50 Mg/L
Effluent discharge standard after treatment
BOD5 - Less than 10 Mg/L
S. Solids - Less than 10 Mg/L
COD - Less than 80 Mg/L
Oil & Grease - Less than 5 Mg/L
Sewage Treatment Plant shall include the following items:
Screen Chamber
Oil & Grease Chamber
Sewage equalization Tank
MBBR tank (Moving bed Bio Reactor)
Tube Settling Tank
Sludge Holding tank
Chlorine Contact Tank
Filtration through MGF, ACF, Chlorinator & UV Sterlizer
Air Blowers, Pumps & Equipment
Filter Press
Piping, valves etc
Electrical Panel & Cabling
All piping, valves & level indicator/controller etc. within plant room.
Contractor shall ensure submission of detailed civil General Arrangement drawings (Plan & Section), P & I (Programming & Instrumentation) diagram, schematic diagram for the above mention component & additional component such as inserts, puddle flanges, vent pipes etc. if so required for the complete working of the STP and got it approved by the Engineer in charge.
Only Plateform for STP Plant shall be in the scope of the Owners. The sewerage treatment contractor shall co-ordinate, supervise and get all the inserts installed. All supply of MS/insert plates shall be in the scope of the sewerage treatment contractor.
Supply, installation, testing & commissioning of 2 nos mild steel 5mm FRP Coating perforated corrugated Bar Screen with vertical grating made by 3 mm thick stainless steel plate, spacing of plates 20 mm c/c both sides with suitable lifting arrangement (size 750 mm wide x 600 mm high approx)
Supply, Installation, Testing and Commissioning of the following tanks and chambers in HDPE/PVC as per approved drawings and directions of Engineer Incharge. The cost shall include all the required MS walking platform, handrail, staircase, manhole cover etc.
All above Quoted with minimum 10mm M.S tanks with 5mm FRP coating protection
MBBR tank of capacity as per approved shop drawings & calculation
Tube settler tank of M S as per approved shop drawings & calculation
Sludge holding tank of capacity as per approved shop drawings & calculation
Chlorine Contact tank of capacity as per approved shop drawings & calculation
Treated water tank of capacity as per approved shop drawings & calculation
Quoted with minimum 10mm M.S tanks and all above item as per design requirments (No extra payment shall be paid)
Supply, installation, testing & commissioning of Horizontal type pumps, having cast iron body, C.I. impeller & shaft connected to TEFC motor for 415 volts, 3 phase, 50 cycles A.C. power supply with mechanical /gland seal. Protection complete in all respects including suction and delivery headers with UPVC pipe of required dia, isolation valves, NRV & Pumps shall have following duty:
Raw Sewage Transfer Pump
(Pumps to be suitable to handle Solid handling capacity upto 40 mm size)
Set of two pumps (1 Working + 1 Standby)
Capacity - 10 LPS ( Required- 36M3/hr)
Head - 10-12 Mtr.
H.P. - 2 HP Approx.
Submersible sewage lifting pump
Set of two pumps (1 Working + 1 Standby)
Capacity - 5 LPS
Head - 10-12 Mtr.
H.P. - 2 HP Approx.
(Solid handling capacity upto 40 mm size)
Supply, installation, testing & commissioning of Electromagnetic type flow meter at the outlet point of raw sewage transfer pump of 50 mm size suitable for 0 - 15 KLH flow.
Supply, installation, testing & commissioning of twin type rotary air blower with acoustic encloser, driven through “V” belt or directly coupled through flexible coupling to a TEFC motor of suitable HP Suitable for 415 ± 10% volts, 3 phase, 50 cycles A/C supply. Capable of delivering 70 cum/hr of free air at 0.5 kg/cm2.
Supply, installation, testing & commissioning of Air piping shall comprise of pipes droppers/ laterals with MS (epoxy coated) Header complete with all fittings such as tees, crosses, plugs, sockets, elbows, reducers, supports & clamps, puddle flanges etc including cutting holes in wall, makes chases in wall and making good the same. Contractor to submit detailed P&I indicating their proposal.
Supply, installation, testing & commissioning of fine air diffusers capable of delivering 10-12 cum/hr in MBBR tank for providing areation.
Supply, installation, testing & commissioning of coarse air diffusers capable of delivering 3-6 cum/hr in equalization tank and sludge holding tank for providing areation.
Supply, installation, testing and commissioning of high surface area @ 400 M2/M3 at least ring type media to be used for bacterial growth installed in moving bed bio reactor tanks.
Supply, installation, testing and commissioning of PVC tube deck settling media to be installed in Tube Settling Tank. The Media to be supported on MSEP frame with baffle plate & overflow launder.
Supply, installation, testing and commissioning of single stage horizontal centrifugal self priming pump with with C.I body, bronze impeller, shaft of stainless steel, shaft sleeve of chrome steel and delivery casing in C.I with mechanical seal, connected to a TEFC induction motor suitable for 415+/- 10% volts, 3 phase 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundation, sequence running controller, dry running Protection, 80x40 mm I section base plate bolted to cement concrete foundations complete includingisolation valves, NRV & vibration eliminators on both suction & delivery side of pumps .Vendor to submit performance curves and technical catalogue of the proposed model for review and information.
Sludge Feed / Transfer Pump
(Pumps to be suitable to handle Solid handling capacity upto 8-10 mm size)
Set of two pumps (1 Working + 1 Standby)
Capacity - 5 LPS
Head - 10.0 Mtr.
H.P. - 1.5 HP Approx.
Supply, installation, testing and commissioning of horizontal centrifugal pumping set with cast iron body, bronze impeller, shaft of SS and C.I. base & head with mechanical seal, connected to a TEFC induction motor suitable for 415 +/- 10% volts, 3 phase 50 cycles A.C supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundation, dry running Protection, 80x40 mm I section base plate bolted to cement concrete foundations complete including isolation valves, vibration eliminators on both suction & delivery side of pumps and NRV on delivery side of pumps .Vendor to submit performance curves and technical catalogue of the proposed model for review and information.
Filter Feed Pumps
Set of two pumps (1 Working + 1 Standby)
Capacity - 3.0 LPS ( Suggested and quoted for 5000LPH)
Head - 30.0 Mtr.
H.P. - 3.0 HP Approx.
Supply, installation, testing & commissioning of vertical self supporting filtration unit fabricated from MS sheet as per IS: 2825 (minimum thickness of shell 8 mm and dished ends 10 mm) pressure gauges, sample cock, GI class 'C' face piping, CI butterfly valves and all accessories, with initial charge of filter media including anthracite, painting inside with epoxy paint and outside with two coat of red oxide primer and two or more coat of synthetic enamel paint, testing and commissioning complete.
Mulitgrade Pressure Sand Filter
Capacity - 15000 lph
Filtration rate - 14000 lph/sqm
Filter dia approx. - 800 mm
Working pressure: 3.0 Kg/sq cm.
Test pressure : 4. 5 Kg/sq cm
Activated Carbon Filter
Capacity - 15000 lph
Filtration rate - 14000 lph/sqm
Filter dia approx. - 800 mm
Working pressure: 3.0 Kg/sq cm.
Test pressure : 4. 5 Kg/sq cm
Supply, installation, testing & commissioning of metering pump type chemical doser with 100 lits. PVC/HDPE solution tank, injection fitting assembly, suction and delivery hose upto the point of injection, capacity 0-6 lph, complete in all respects.
Supply, installation, testing & commissioning of all pipings (as described below) and isolation control valves including all necessary fittings and clamps, supports, hangers as required i/c cutting and making good the walls wherever required complete in all respects for making the system complete.
GI : Submerged air piping( We suggest uPVC. GI is never used for submerged piping)
MS Epoxy : Air piping & pumped effluent riser (non-submerged)
UPVC : Interconnecting pipe line after delivery header of pump/filter
Controllers with low voltage relays, stainless steel probes and pvc shroud, control cabling as required length. (No of probes as required for function of each controller).
Filter Feed Pumps
To cut off duty pump on low water level in the chlorine contact tank and high water level in the treated water tank and To start pump at low water level in the treated water tank.
Supply, installation, testing & commissioning of Filter Press of Plate size 18" x 18" x 12 Nos. plate with Screw feed pumps of 5 M3/Hr @ 40 M head capacity (1 working + 1 standby) complete in all respects.
Providing installing testing and commissioning of ultra filteration (UF) system for further polishing treated effluent and capable of producing 5,000 litre/hour. The system shall be complete with UF feed pumps (1W+1S), backwash pumps (1W+1S), cartridge filters (fabricated|), UF membranes flushing / cleaning system complete instrumentation for automation and monitoring rotameters pressure gauges interconnecting pipeword electrical cabling and switchgear, all complete
Electrical Installation for STP
Motor Control Centre
Incoming
200 amps TPN MCCB with the following accessories:
Phase indicating lamps shall be protected by 2 amp SP MCB 3 Sets.
Bus Bar
200 amps TPN (15 KA) copper bus bar with heat shrinkable insulation sleeves.
Outgoing
Spare 25 amps TPN MCB's 2 Nos.
Spare 32 amps TPN MCB's 2 Nos.
Necessary cable alleys, internal/cabling, wiring, cabling from MCC to various pumps/equipment and interlocking, earthing for all equipment shall also included
Notes :
All MCCBs / MCBs shall be of 15 KA breaking capacity and suitable for motor duty application.
All motor starters shall be provided with Automatic level controller.
DOL starters shall be used for motors below 10HP and Star-Delta Starters for other motors .
Provision shall be made for providing potential free contacts to all pumps starters.
MCC for all STP equipments / pumps as described above.
PART B ( O & M Cost) ( for 5 years (60 Months )from Final Handing Over of all Works.) (optional)
Trained operator to operate the STP round the clock including Operator and regular visit of Supervisor.
Per Annum
Including all Charges like AMC , Monthly charges of water analysis and all consumables etc included.
PART:C
Providing & laying UPVC pressure pipes of 6 Kg/Sq.cm pressure rating class 3 (IS : 4985-2000) including fittings, tees, bends, clamps, coupling and adaptors supports, and jointing with solvent joint, testing and necessary earth work in excavation, backfilling, disposal of surplus earth with a lead up to 100m complete, compaction and consolidation Including sand bedding all around UPVC pipe & fittings and thrust blocks at bends as per standard design. 200 OD
Designing, Preparation of Shop Drawings, Supplying, Erection, Testing, Commissioning of all Mechanical, Electrical and other components including getting approval of successful test results from approved / authorized agency from Pollution & Environmental Authorities, Operating & Maintaining upto successful commissioning, for 5 m3/day capacity Sewage Treatment Plant Sewage Treatment Plant near workshop area (Complete system to be compact type, skid-mounted / cabinet enclosed, as per detailed shop drawings to be approved) Suprime/sintex make
HVAC Admin
Variable Refrigerant Flow System Supply Installation Testing and Commissioning of Imported Variable Refrigerant Flow air cooled Outdoor Units suitable for cooling and heating, having all hermetically sealed inverter type Scroll / Twin rotary Compressor(s) ,minimum 2 compressors above 16HP ODU, microprocessor based controller, top discharge type condensing units with R410 A refrigerant , vibration isolators with suitable foundation etc. complete as required. The Outdoor unit should have anti corrosive, black coated fins along with auto dust removal as a standard feature. The unit shall deliver the rated capacity at AHRI conditions and work even at 50 Deg C ambient temperature without tripping. The unit shall be suitable to work on 400 V+/-10% 3 phase , 50 Hz AC power supply. The COP at AHRI in Cooling mode should not be less than 3.8. The quoted cost sould include custom clearence , transit cost , ocean freight & forwarding charges . The ODU should have powerful BLDC fan motor that allows to extend the external static pressure of Outdoor unit shuld be 110 Pa. Make: Carrier/Toshiba/Mitsubishi Electric
Supplying, installing, testing and commissioning of Wall mounted type indoor units each complete with coil, filter, etc. Air conditioners with evaporating unit comprising of cooling coil, blower with motor , and 220 volt, 1 phase, 50 Hz, AC supply all and as per specifications. Make: Carrier/Toshiba/Mitsubishi Electric
4 Way Cassette indoor unit Supply Installation Testing and Commissioning of following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve ,outer cabinet, drain pump, necessary supports, vibration isolation, etc suitable for operation on 230 V +- 10% 50 Hz AC supply Make: Carrier/Toshiba/Mitsubishi Electric
Supply Installation Testing and Commissioning of Cassette Decorative Grill Panel. Make: Carrier/Toshiba/Mitsubishi Electric
High Static Ducted Units Supply Installation Testing and Commissioning of following minimum capacity High Static VRV/VRF Ducted Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve ,outer cabinet, drain pump grill, necessary supports, vibration isolation, etc suitable for operation on 230 V +- 10% 50 Hz AC supply Make: Carrier/Toshiba/Mitsubishi Electric 10 HP
Y Joints Supply, fixing and commissioning of refrigerant joint / Branch distibutors between Outdoors with nitrile rubber insulation, supporting etc. complete as required. Make: Carrier/Toshiba/Mitsubishi Electric
Supply, fixing and commissioning of refrigerant joint / Branch distibutors between Indoors with nitrile rubber insulation, supporting etc.complete as required. Make: Carrier/Toshiba/Mitsubishi Electric
Supply Testing and Commissioning of Cordless Remote controller suitable for Controlling all indoor units as complete as required. Make: Carrier/Toshiba/Mitsubishi Electric
Supply installation Testing and Commissioning of Touch Type centralised controller suitable for Controlling to connect all indoor units as complete as required. Make: Carrier/Toshiba/Mitsubishi Electric
Refrigerant Piping Supply installation Testing and Commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for F/VRV system, complete with fittings, with suitable adjustable ring type hanger supports, ng/brazing including accessories insulated with XLPE Class O tubular insulation/with Class O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories. Make: Totaline/Met Tube/Rajco
6.5 mm dia (OD) (soft drawn) with appropriate tube thickness with 13mm thick insulation
9.5 mm dia (OD) (soft drawn) with appropriate tube thickness with 13mm thick insulation
12.7 mm dia (OD) (soft drawn) with appropriate tube thickness with 13mm thick insulation
15.86 mm dia (OD) (soft drawn) with appropriate tube thickness with 13mm thick insulation
19 mm dia (OD) (Soft/Hard drawn) with appropriate tube thickness with 13mm/19mm thick insulation
22.2 mm dia (OD) (Hard drawn) with appropriate tube thickness with 19mm thick insulation
28.58 mm dia (OD) (Hard drawn) with appropriate tube thickness with 19mm thick insulation
31.8 mm dia (OD) (Hard drawn) with appropriate tube thickness with 19mm thick insulation
34.9 mm dia (OD) (Hard drawn) with appropriate tube thickness with 19mm thick insulation
38.1 mm dia (OD) (Hard drawn) with appropriate tube thickness with 19mm thick insulation
41.27 mm dia (OD) (Hard drawn) with appropriate tube thickness with 19mm thick insulation
44.5 mm dia (OD) (Hard drawn) with appropriate tube thickness with 19mm thick insulation
50 mm dia (OD) (Hard drawn) with appropriate tube thickness with 19mm thick insulation
Drain Piping Supply Installation Testing & Commissioning of rigid UPVC piping with fittings, supports as per specifications and duly insulated with 6 mm thick closed cell nitrile rubber insulation etc. complete as required. Make: Supreme/Prince/Finolex
25 mm dia ( with 6 mm nitrile rubber Insulation)
32 mm dia ( with 6 mm nitrile rubber Insulation)
Supply Installation Testing and Commissioning of Site fabricated GSS sheet metal rectangular ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. Make: Tata/Jindal/Sail
Thickness 24G Sheet
Thickness 22G Sheet
Supply and fixing of following thickness duly laminated aluminium foil finish closed cell Nitrile rubber ( Class O) insulation on duct after applying suitable adhesive for Nitrile rubber . The joints shall be sealed with 50 mm wide and 3mm thick self adhesive nitrile rubber insulation complete as per specifications and as required. (a)13 mm thick insulation with Aluminium foil. Make: Supreme/A Flex/K FLex.
Supply, installation and testing of acoustic lining of ducts with glass wool of 24 Kg/sqcm , the glasswool shall be covered with RP tissue paper and fixed with roofing nut and bolt complete as per specification and complete as per requirement.. Thermal conductivity of the insulation material shall not exceed 0.047 W/moK at an average temperature of 20oC. 25 mm thick acoustic lining Make: UP Twiga/ Ownes Corning
Supply installation and fixing of fire retardant non porous double layer flexible connection between each Ducted Indoor as complete as required.
Grilles Supplying & fixing of powder coated extruded aluminum Supply Air Grills with aluminum volume control dampers as per specifications. Make: Tristar/Airflow/Ravistar
Diffuser Supplying & fixing of powder coated extruded aluminum Supply Air Diffuser with aluminum volume control dampers as per specifications. Make: Tristar/Airflow/Ravistar
Cable Tray Fabrication, supplying and installing of GI tray with cover of following sizes of horizontal and vertical bends, reducers, tees, cross members & other accessories etc. as required and duly supported from the ceiling with dash fastness including painting of suspenders required for accomodating/ laying of refrigerant pipes as complete as required. Make:- Sheetal Industries/Echo Duct
a) 150 x 50 x 1.6 mm(With Cover)
b) 300 x 50 x 1.6 mm(With cover)
Supply & Installation of control cum transmission wiring of 3/2 core x 1.5 sqmm Shielded copper in suitable pvc conduits between indoor and outdoor unit as complete as required. Make: Polycab/Finolex/KEI
Refrigerant gas R-410 for top up as complete as required. Make: Refron/Mefron/Dupont
MS Fabricated (Heavy Duty ) ODU Frame
Supply Installtion Testing & Commisioning of Heat Reclaiim Ventalltion system with Dx Coil as per below specifications 950CMH/135 Pascals ESP/8.25 KW & 10.92 KW should be the fresh air conditioning load in cooling & heating Capacities. Make: Carrier/Toshiba/Mitsubishi Electric
Sub-Head : WIRING
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable Gl box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Make:-CCI/havells/polycab/Anchor/Finolex Group C
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm ERLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm ERLS PVC insulated copper conductor single core cable etc. as required. Make:- CCI/havells/polycab/Anchor/Finolex Group C
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. Make:- CCI/havells/polycab/Anchor/Finolex
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. Make:- CCI/havells/polycab/Anchor/Finolex
2 X 1.5 sq. mm +1X 1.5 sq. mm earth wire (For Light)
2 X 2.5 sq. mm +1X 2.5 sq. mm earth wire (For Light)
2X6 sq. mm +1X 6 sq. mm earth wire
4 X 10 sq. mm +2X 6 sq. mm earth wire
4 X 16 sq. mm +2X 6 sq. mm earth wire
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. Make:- NORTHWEST(PLATIA), SCHNEIDER(ZEN CELO), MK (BLENZE), LEGRAND(ARTEOR).
5/6 A switch
15/16 A switch
3 pin 5/6 A socket outlet
6 pin 15/16 A socket outlet
Telephone socket outlet
TV antenna socket outlet
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing following size/ modules, Gl box alongwith modular base & cover plate for modular switches in recess etc. as required.
1 or 2 Module (75mmX75mm)
3 Module (100mmX75mm)
4 Module (125mmX75mm)
6 Module (200mmX75mm)
Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required.
Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.
Numbering of ceiling fan/ exhaust fan/ fluorescent fittings as required.
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.
Upto 450 mm sweep
Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes.
Supplying & fixing suitable size Gl box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required.
Supplying & Fixing Of Following Sizes Of PVC Conduit Along With Accessories in Surface / Recess Including Cutting the Wall And Making Good the same In Case of recess Conduit as Required Make:- BEC/Precision/AKG/POLYPACK/Anchor
Sub-Head : MCCB, MCB & OB'S
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (but without MCBs and incomer) as required Make:- Schnider ACTI-9/SIEMENS Betagaurd(8GB32)/Hager Novello
4 way (4 +12), Double door (For Light +Power)
6 way (4 +18), Double door (For Light +Power)
8 way (4 +24), Double door (For Light +Power)
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/lsolator) Make:- Schnider ACTI-9/SIEMENS Betagaurd(8GB32)/Hager Novello
6 way, Double door (For Em. Light/UPS)
8 way , Double door (For Em. Light/UPS)
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. MAKE:- SCHNIDER(ACTI - 9)/SIEMENS(BETA GUARD)/L&T (AU).
Single pole
Double pole
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. MAKE:- SCHNIDER(ACTI - 9)/SIEMENS(BETA GUARD)/L&T (AU).
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/recessed steel/PVC conduit as required.MAKE:- BELDEN/PANDUIT/POLYCAB/LEGRAND
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. Make:- BEC/PRECISION/AKG/Polypack/Anchor 25 mm
Sub-Head : EARTHING
Earthing with G.l. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/coke and salt as required. (For Transformer/MLP/MDB/HT Panel/HT Meter)
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/coke and salt as required.
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
Supplying and laying 25 mm X 5 mm G.l strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.l. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.l. nut bolt & spring washer spaced at 50mm)
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Providing and fixing 25 mm X 5 mm G.l. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.l. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/cable as required.
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.l. suspenders including G.l. bolts & nuts, etc. as required.
150 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 50 mm depth X 2.0 mm thickness
600 mm width X 50 mm depth X 2.0 mm thickness
Sub-Head : LIGHTNING CONDUCTOR Make:- OBO/Nimbus/Taran(SGI)/Ashlok
Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.l. tube, having single prong at top, with 85 mm dia 6 mm thick G.l. base plate including holes etc. complete as required.
Fixing of lightning conductor finial (single prong) with base plate including holes etc. complete as required.
Jointing copper / G.l. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/sweating and soldering etc as required.
Providing and fixing G.l. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) ____
Providing and fixing G.l. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) //
Providing and fixing testing joint, made of 20 mm X 3 mm thick G.l. strip, 125 mm long, with 4 nos. of G.l. bolts, nuts, chuck nuts and spring washers etc. complete as required.
Earthing with G.l. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required.
Providing and laying G.l. tape 32 mm X 6 mm from earth electrode directly in ground as required.
Sub-Head : MV CABLE LAYING
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. MAKE:- CCI, Havells, Polycab
Upto 35 sq. mm
Above 35 sq. mm and upto 95 sq. mm
Above 185 sq. mm and upto 400 sq. mm
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.l. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
Sub-Head : MV CABLE JOINTING & END TERMINATION
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. MAKE:- COMET/PEECO/Siemons/Dowells
3½ X 300 sq. mm
3½ X 240 sq. mm
3½ X 150 sq. mm
3½ X 95 sq. mm
3½ X 50 sq. mm
3½ X 35 sq. mm
4 X 25 sq. mm
4 X 16 sq. mm
4 X 10 sq. mm
Sub-Head : MISC. CIVIL ITEMS
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
63 mm dia (OD-63 mm & ID-51 mm nominal)
160 mm dia (OD-160 mm & ID-135 mm nominal)
Sub-Head : FIRE DETECTION AND ALARM SYSTEM Make:- Honeywell/Bosch/Siemens/Notifier
INTELLIGENT FIRE ALARM SYSTEM
Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required.
Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required.
Supplying, installation, testing & commissioning of fault isolator complete with base as required.
Supplying, installation, testing & commissioning of addressable fire control module complete as required.
Supplying, installation, testing & commissioning of addressable manual call point complete as required.
Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
Supplying, installation, testing & commissioning of intelligent interface unit BACnet/ Modbus protocol i.e. supplying communication links between building management system and fire alarm control panel complete as required.
Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required.
Supplying, installation, testing & commissioning of fire fighter phone jack complete as required.
Supplying, installation, testing & commissioning of addressable fire control module complete as required.
Supplying, installation, testing & commissioning of addressable phone control module complete as required.
PUBLIC ADDRESS SYSTEM
Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required.
Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required.
Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required.
CABLING & WIRING
Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required.
Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required.
speaker cable Single pair, 2-core, 1.5 sqmm
speaker cable Four pair, 2-core, 1.5 sqmm
Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required.
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. Make:- CCI/Havells/Polycab/Anchor/Finolex 2 x 1.5 sq. mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. Make:- BEC/PRECISION/AKG/Polypack/Anchor 25 mm
MV SWITCHGEAR PANELS & DISTRIBUTION BOARDS :
Design, manufacture, supply, installation, testing and commissioning of following Utility panels suitable for 415 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 2mm thick CRCA sheet steel for Load bearing members and 1.6 mm thick for non-load bearing members, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber (form-3b Construction). The panel shall be complete with name plate, earthing, numbering, danger plate etc. as required and as per specifications and drawings. The panel shall withstand the fault level of as indicated elsewhere or shown in Single Line Diagram.
Important Notes: Common for all Switchboard:
The BOQ shall be read inconjunction with general notes, specification and Single Line Diagram (attached for Ref.). Incase of any discrepancy between specification, BOQ and SLD, the same shall be brought to the notice of Client/Consultant before quoting the rates, otherwise stringent condition shall be deemed to have been considered.
All MCCB shall be provided with door interlocked rotary handle with ON/TRIP/OFF position indicator, continious variable thermal magnetic O/C and S/C releases. All rating MCCB's shall be thermalmagnetic type.
Incoming MCCBs shall be provided with O/C, S/C, and Earth fault protection releases.
Outgoing MCCBs shall be provided with O/C, short circuit protection.
All feeder doors shall have pad locking arrangement.
All TP feeders shall have solid isolable neutral link.
All MCCB used in starter feeder shall be suitable for motor duty application.
All power contactors including NIC shall be of AC3 duty.
All ACB's shall be with micro processor based releases and Breaker Control Switch (BCS) having lost motion device.
Spare contaCTs of ACB/Relays/Contactor etc. shall be wired upto terminal block.
All switchgear used in starter feeder shall be type-2 co-ordinated. Manufacturer is required to submit manufacturers type-2 co-ordination chart for the make used.
All meters are digital type.
Panel shall be powder coated of approved shade with minimum 60 micron thickness.
ACB's/MCCB's in one particular panel shall be of one similar make.
Size of Voltmeter / Ammeter for incomer also, 96mm x 96mm flush mounted with shrouded terminal shall be used in the panel.
Bus bar chamber shall be kept at top of the all panels.
All bus bar shall be insulated with coloured PVC Sleeve i.e.RYB,BK as per colour code.
Internal wiring of panel shall be with size 2.5sqmm Flexible Copper Conductor for CT circuit and control wiring with 1.5 sqmm.
All Lift Panels transport section should not be more then 1000 mm.
In soft starter Vender should supply power contactor with aux. Contactor & All necessary accessories required etc. (As per BOQ & specification )
All indicating light shall be LED type .
Each vertical section of floor mounted panel shall have independent base frame (75mm x 40mm) size made out of 3 mm sheet steel (LT Panel & DG Panel).
All the makes shall be as per Client approved make list only.
Wherever only voltmeter & ammeter are required, the same may be provided in combined meter suitable for both parameter.
MDB-G.F LOWER SIDE (ADMIN)
INCOMER
1 Nos. 630Amp 36 KA 4P MCCB complete having microprocessor based over current, short circuit & earth fault protection incomer shall be complete with following.
METERING FOR EACH INCOMER
3 Nos. Cast resin current transformers of Class 1.0 for metering.
Three phase indicating lamps (LED type) with MCB.
ON OFF TRIP indicating lamps (LED type).
BUSBAR
1 Set of 800A, TPN Aluminum bus bars with colour coded sleeves.
OUTGOING UNITS
5 Nos. 160Amp TPN MCCB 16KA with thermal magnetic releases.
1 Nos. 250Amp TPN MCCB 16KA with thermal magnetic releases.
2 Nos. 63Amp TPN MCCB 16KA with thermal magnetic releases.
4 Nos. 63Amp TPN MCB 10KA
1 Nos. 32Amp DP MCB 10KA
SUPPLY & INSTALLATION OF MAIN DISTIBUTION BOARD AS DESCRIBED ABOVE. MAKE:- TRICOLITE, ADLEC, ADVANCE PANLES & SWITCHGEAR (P) LTD., SIMON FABRICATOR JAMMU, Electricfield
SDB-1ST. TO 4TH. LOWER SIDE (ADMIN)
INCOMER
1 Nos. 160Amp 36 KA 4P MCCB complete having microprocessor based over current, short circuit & earth fault protection incomer shall be complete with following.
METERING FOR EACH INCOMER
3 Nos. Cast resin current transformers of Class 1.0 for metering.
Three phase indicating lamps (LED type) with MCB.
ON OFF TRIP indicating lamps (LED type).
BUSBAR
1 Set of 200A, TPN Aluminum bus bars with colour coded sleeves.
OUTGOING UNITS
6 Nos. 63Amp TPN MCB 10KA
SUPPLY & INSTALLATION OF MAIN DISTIBUTION BOARD AS DESCRIBED ABOVE MAKE:- TRICOLITE, ADLEC, ADVANCE PANLES & SWITCHGEAR (P) LTD., SIMON FABRICATOR JAMMU, Electricfield
MDB-G.F RIGHT SIDE (ADMIN)
INCOMER
1 Nos. 630Amp 36 KA 4P MCCB complete having microprocessor based over current, short circuit & earth fault protection incomer shall be complete with following.
METERING FOR EACH INCOMER
3 Nos. Cast resin current transformers of Class 1.0 for metering.
Three phase indicating lamps (LED type) with MCB.
ON OFF TRIP indicating lamps (LED type).
BUSBAR
1 Set of 800A, TPN Aluminum bus bars with colour coded sleeves.
OUTGOING UNITS
5 Nos. 160Amp TPN MCCB 16KA with thermal magnetic releases.
1 Nos. 125Amp TPN MCCB 16KA with thermal magnetic releases.
5 Nos. 63Amp TPN MCB 10KA
1 Nos. 32Amp DP MCB 10KA
SUPPLY & INSTALLATION OF MAIN DISTIBUTION BOARD AS DESCRIBED ABOVE MAKE:- TRICOLITE, ADLEC, ADVANCE PANLES & SWITCHGEAR (P) LTD., SIMON FABRICATOR JAMMU, Electricfield
SDB-1ST. TO 4TH. RIGHT SIDE (ADMIN)
INCOMER
1 Nos. 160Amp 36 KA 4P MCCB complete having microprocessor based over current, short circuit & earth fault protection incomer shall be complete with following.
METERING FOR EACH INCOMER
3 Nos. Cast resin current transformers of Class 1.0 for metering.
Three phase indicating lamps (LED type) with MCB.
ON OFF TRIP indicating lamps (LED type).
BUSBAR
1 Set of 200A, TPN Aluminum bus bars with colour coded sleeves.
OUTGOING UNITS
6 Nos. 63Amp TPN MCB 10KA
SUPPLY & INSTALLATION OF MAIN DISTIBUTION BOARD AS DESCRIBED ABOVE MAKE:- TRICOLITE, ADLEC, ADVANCE PANLES & SWITCHGEAR (P) LTD., SIMON FABRICATOR JAMMU, Electricfield
MDB-G.F LEFT SIDE (ADMIN)
INCOMER
1 Nos. 630Amp 36 KA 4P MCCB complete having microprocessor based over current, short circuit & earth fault protection incomer shall be complete with following.
METERING FOR EACH INCOMER
3 Nos. Cast resin current transformers of Class 1.0 for metering.
Three phase indicating lamps (LED type) with MCB.
ON OFF TRIP indicating lamps (LED type).
BUSBAR
1 Set of 800A, TPN Aluminum bus bars with colour coded sleeves.
OUTGOING UNITS
5 Nos. 160Amp TPN MCCB 16KA with thermal magnetic releases.
1 Nos. 125Amp TPN MCCB 16KA with thermal magnetic releases.
2 Nos. 63Amp TPN MCCB 16KA with thermal magnetic releases.
6 Nos. 63Amp TPN MCB 10KA
1 Nos. 32Amp DP MCB 10KA
SUPPLY & INSTALLATION OF MAIN DISTIBUTION BOARD AS DESCRIBED ABOVE MAKE:- TRICOLITE, ADLEC, ADVANCE PANLES & SWITCHGEAR (P) LTD., SIMON FABRICATOR JAMMU, Electricfield
SDB-1ST. TO 4TH. LEFT SIDE (ADMIN)
INCOMER
1 Nos. 160Amp 36 KA 4P MCCB complete having microprocessor based over current, short circuit & earth fault protection incomer shall be complete with following.
METERING FOR EACH INCOMER
3 Nos. Cast resin current transformers of Class 1.0 for metering.
Three phase indicating lamps (LED type) with MCB.
ON OFF TRIP indicating lamps (LED type).
BUSBAR
1 Set of 200A, TPN Aluminum bus bars with colour coded sleeves.
OUTGOING UNITS
6 Nos. 63Amp TPN MCB 10KA
SUPPLY & INSTALLATION OF MAIN DISTIBUTION BOARD AS DESCRIBED ABOVE MAKE:- TRICOLITE, ADLEC, ADVANCE PANLES & SWITCHGEAR (P) LTD., SIMON FABRICATOR JAMMU, Electricfield
VRV SDB-1ST. TO 4TH. LEFT SIDE (ADMIN)
INCOMER
1 Nos. 800Amp 36 KA 4P MCCB complete having microprocessor based over current, short circuit & earth fault protection incomer shall be complete with following.
METERING FOR EACH INCOMER
3 Nos. Cast resin current transformers of Class 1.0 for metering.
Three phase indicating lamps (LED type) with MCB.
ON OFF TRIP indicating lamps (LED type).
BUSBAR
1 Set of 1000A, TPN Aluminum bus bars with colour coded sleeves.
OUTGOING UNITS
2 Nos. 250Amp TPN MCCB 16KA with thermal magnetic releases.
3 Nos. 200Amp TPN MCCB 16KA with thermal magnetic releases.
2 Nos. 160Amp TPN MCCB 16KA with thermal magnetic releases.
4 Nos. 100/125Amp TPN MCCB 16KA with thermal magnetic releases.
SUPPLY & INSTALLATION OF MAIN DISTIBUTION BOARD AS DESCRIBED ABOVE MAKE:- TRICOLITE, ADLEC, ADVANCE PANLES & SWITCHGEAR (P) LTD., SIMON FABRICATOR JAMMU, Electricfield
VRV SDB-1ST. TO 4TH. LOWER SIDE (ADMIN)
INCOMER
1 Nos. 500Amp 36 KA 4P MCCB complete having microprocessor based over current, short circuit & earth fault protection incomer shall be complete with following.
METERING FOR EACH INCOMER
3 Nos. Cast resin current transformers of Class 1.0 for metering.
Three phase indicating lamps (LED type) with MCB.
ON OFF TRIP indicating lamps (LED type).
BUSBAR
1 Set of 600A, TPN Aluminum bus bars with colour coded sleeves.
OUTGOING UNITS
3 Nos. 200Amp TPN MCCB 16KA with thermal magnetic releases.
1 Nos. 160Amp TPN MCCB 16KA with thermal magnetic releases.
4 Nos. 100/125Amp TPN MCCB 16KA with thermal magnetic releases.
SUPPLY & INSTALLATION OF MAIN DISTIBUTION BOARD AS DESCRIBED ABOVE. MAKE:- TRICOLITE, ADLEC, ADVANCE PANLES & SWITCHGEAR (P) LTD., SIMON FABRICATOR JAMMU, Electricfield
VRV SDB-1ST. TO 4TH. RIGHT SIDE (ADMIN)
INCOMER
1 Nos. 500Amp 36 KA 4P MCCB complete having microprocessor based over current, short circuit & earth fault protection incomer shall be complete with following.
METERING FOR EACH INCOMER
3 Nos. Cast resin current transformers of Class 1.0 for metering.
Three phase indicating lamps (LED type) with MCB.
ON OFF TRIP indicating lamps (LED type).
BUSBAR
1 Set of 600A, TPN Aluminum bus bars with colour coded sleeves.
OUTGOING UNITS
1 Nos. 200Amp TPN MCCB 16KA with thermal magnetic releases.
9 Nos. 100/125Amp TPN MCCB 16KA with thermal magnetic releases.
SUPPLY & INSTALLATION OF MAIN DISTIBUTION BOARD AS DESCRIBED ABOVE. MAKE:- TRICOLITE, ADLEC, ADVANCE PANLES & SWITCHGEAR (P) LTD., SIMON FABRICATOR JAMMU, Electricfield
LIFT PANEL
(Loc. Lift Machine Room)
Incoming:
One (1) No. 315A 4P on Load COS.
One (1) No. 315A TPN MCCB
Metering, Indication and Protection :
Three (3) Nos. phase indication lamps and three (3) Nos. status indication lamps with control MCB.
Busbar:
500A, 16kA TPN AL Bus Bar. Bus bar shall be insulated with heat shrinkable sleeves & shall be colour coaded.
Outgoings:
Two (2) Nos 63A 4P MCB
Four (4) Nos 100A TPN MCCB
One (1) Nos. 63A TPN MCCB
SUPPLY & INSTALLATION OF LIFT PANEL AS DESCRIBED ABOVE MAKE:- TRICOLITE, ADLEC, ADVANCE PANLES & SWITCHGEAR (P) LTD., SIMON FABRICATOR JAMMU, Electricfield
UPS SDB (ADMIN)
INCOMER
1 Nos. 250Amp 36 KA 4P MCCB complete having microprocessor based over current, short circuit & earth fault protection incomer shall be complete with following.
METERING FOR EACH INCOMER
3 Nos. Cast resin current transformers of Class 1.0 for metering.
Three phase indicating lamps (LED type) with MCB.
ON OFF TRIP indicating lamps (LED type).
BUSBAR
1 Set of 300A, 4P, Copper bus bars with colour coded sleeves.
OUTGOING UNITS
8 Nos 63A 4P MCB
1 Nos. 100Amp TPN MCCB 16KA with thermal magnetic releases.
SUPPLY & INSTALLATION OF MAIN DISTIBUTION BOARD AS DESCRIBED ABOVE MAKE:- TRICOLITE, ADLEC, ADVANCE PANLES & SWITCHGEAR (P) LTD., SIMON FABRICATOR JAMMU, Electricfield
MCB FOR DB's
Supplying and fixing following rating, four pole, 415 V, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required.
STATIC SINE WAVE INVERTER FOR COMMON AREA :
Design, manufacturing,Testing at works, supply erection, testing (at site) and commissioning of 1Ph AC input & 1Ph AC output Inverter system suitable for 230VAC, 50Hz supply, variation +/-1% , PF 0.8 as per specification. Make:- Microtek/Luminous/Numeric
Design, manufacturing, supply ,erection, testing (at site) and commissioning of One sets of SMF VRLA battery with each inverter, having back up time as mentioned below at full load,with interconnecting cables, cabinets and standard accessories as per specification and as required for the Inverter system.(12V Cells) with wire & assessories etc. Make:- Microtek/Luminous/Numeric
90 Minutes back up for 3 kVA
UNINTERRUPTED POWER SUPPLY SYSTEM
Supply, Installation, Testing and Commissioning of true parallel redundant 1 x 40kVA, online, UPS system suitable for providing power supply to emergency lighting and Computerised Control panel load of approved make, suitable for incoming 440 volts, single phase +10 % -20%, 50 Hz, supply and three phase 440 volts, output voltage, variation ± 1%, including inbuilit , rectifier/dual converter, isolation transformer, static switch, inverter, filters, Bypass & static transfer switch for automatic switch over without giving any break of power, maintenance bypass switch, Microprocessor/software controlled annunciation, protection (including against input phase reversal), and menu run diagnostic module, associated cabling and connections/terminations, erection including associated foundation/masonorey or RCC work for mounting on base channels etc. complete as per specifications and as required.
Supply, Installation, Testing and Commissioning SMF VRLA Battery Banks for UPS stipulated in item 1 above, having 30 minutes back up time at full load with interconnecting cables, racks and standard accessories UPS above. Battery shall comply with relevant regulations & Battery racks shall be made of acid resistant material and shall be supplied inclusive of above item.
Supplying, installation, testing and commissioning of accessories like Battery Rack, Interconnecting links, DC circuit breaker and cable between UPS & battery bank for above UPS.
ELV DATA POINTS
Supply, fixing, testing & commisssioning of Modular RJ-45 with data outlet socket with grid & cover plate in suitable size of 16 SWG GI box.
Supplying, drawing, connecting & testing of 4 pair CAT-6 (E) wire for Data Outlet in existing conduit.
SUPPLY OF FIXTURES
Supply of the following light fixtures complete with housing, reflectors, complete with all accessories i.e. driver, lamp, holders etc. complete as required. Make:- Philips/Bajaj/Havells/Panasonic
Wall/Ceiling mounted luminaire Tube light with LED(Light Emitting Diode) system power: 11W, luminous flux of luminaire 900lm, colour temperature of 4000K, neutral white, CRI>80, 230V constant current driver, 70% of luminous flux after 50,000 operating hours, energy efficient LEDs, direct light emission, aluminium housing powder coated white, satin micro liner prismatic diffuser, electronic control gear, Protection class I, IP20 L = 600mm, B = 21mm, H = 35mm,
Wall mounted Decorative, champagne gold finish fixture with plastic/matlic body suitable for 9/15 W LED lamp base.
Ceiling Mounted luminaire Zing with LED (Light Emitting Diode) system power: 18 W, Luminous flux of luminaire 1980 lm, Colour temperature of 4000 K, Neutral white,SDCM 3, R9 Value should be ≥0, CRI > 80, 230 V constant current driver, 70% of luminous flux after 50,000 operating hours; Energy efficient LEDs, Direct light emission, Luminaire housing in die-cast aluminium, Polyester powder-white coloured coat applied over a 5- stage pre-treatment, Opal protruded diffuser for homogenous light distribution, ZHLS (ZERO HALOGEN LOW SMOKE) internal wiring, Electronic control gear, Protection class II , IP 20, Ø = 180 mm,, H = 55 mm
Surface mounted bulkhead with LED (Light Emitting Diode) system power: 6 W, luminous flux of luminaire 800lm, colour temperature of 5700K, cool white, CRI>80, 230V, direct light emission, aluminium housing, powder coated white, opal diffuser for uniform illumination, electronic control gear, Protection class II, IP65, IK08, L=215mm, B=132mm, H=55mm
Pendant luminaire Vega LED (Light Emitting Diode), system power: 35W, luminous flux of luminaire 3500lm, Colour temperature 5700K, cool white, SDCM 3, CRI >70, 230V constant current driver, 70% of luminous flux after 50,000 operating hours, energy efficient LEDs, direct light emission, housing in aluminium die-cast, powder coated grey, polycarbonate clear diffuser, integral electronic control gear. Protection class I, IP65, Ø = 170 H = 175 mm
LED recessed luminaire Zen22 SM with LED(Light Emitting Diode) system power: 36W, colour temperature of 5700K, 230V constant current driver, 70% of luminous flux after 50,000 operating hours, energy efficient LEDs, CRI>80, luminous flux of 3600 lm,SDCM 3, R9 Value should be ≥0 Electronic Control Gear, direct light emission, Sheet Metal frame, polyester white powder coat applied over a 5-stage pre-treatment Prismatic diffuser for glare-free uniform light Protection class I, IP40, MacAdam 3, T.H.D≤ 10%, UGR<19, driver efficiency ≥ 88%, surge protection of 2.5kV,L = 595mm, B = 595mm, H = 70mm
Pendant/Surface mounted luminaire Slash S with HE-High Efficiency LED (Light Emitting Diode) system power: 30W, luminous flux of luminaire 3300lm, colour temperature of 4000K, CRI>80, 230V constant current driver, 70% of luminous flux after 50,000 operating hours, energy efficient LEDs, direct light emission,anodized luminaire profile, Prismatic diffuser for a homogenous light distribution, ZHLS(ZERO HALOGEN LOW SMOKE) internal wiring, integral electronic control gear, sliding fixing wire suspension. Protection class I, IP40, MacAdam 3,R9 Value should be ≥0, T.H.D≤ 10%, driver efficiency ≥ 88%, surge protection of 2.5kV, L = 1175 mm, B = 52 mm, H = 64 mm
Modular recessed luminaire Slash S with HPE (High Performance Efficiency) LED (Light Emitting Diode), system power: 30W, Luminous flux of luminaire 3300 lm, colour temperature of 4000 K, neutral white, CRI > 80, 230V constant current driver, MacAdam 3, T.H.D ≤ 10%, R9 Value should be ≥0, 70% of luminous flux after 50,000 operating hours, Energy efficient LEDs, Direct light emission, Luminaire profile in aluminium, Polyester powder aluminium white coloured coat applied over a 5- stage pre-treatment, Snap fit prismatic diffuser for a homogenous light distribution ZHLS(ZERO HALOGEN LOW SMOKE) internal wiring, integral electronic control gear, Protection class I, IP 40, , driver efficiency ≥ 88%, surge protection of 2.5kV, L = 1187 mm, B = 64 mm, H = 64 mm, L(ET) = 1175 mm, B(ET)= 52
1200 mm Dia Fan
225MM Dia Ex. Fan
LT NORMAL CABLE
Supplying of following sizes of XLPE/ PVC insulated Aluminum/ Copper conductor and Armoured, overall PVC sheathed 1.1 KV grade cables conforming to relevant IS code and technical specifications. MAKE:- POLYCAB/HAVELLS/CCI
XLPE insulated Al. Ar.Cable
3.5C x 300 sq.mm.
3.5C x 240 sq.mm.
3.5C x 150 sq.mm.
3.5C x 95 sq.mm.
3.5C x 50 sq.mm.
3.5C x 35 sq.mm.
4C x 25 sq.mm.
4C x 16 sq.mm.
CABLE RACEWAY
Fabricating and installation following sizes of Cable raceways made out of HOT DIP sheet steel including horizontal and vertical bends and others accessories as required and duly suspended from the ceiling with MS suspenders and including painting etc. as required.
200mm x 50mm
150mm x 50mm
100mm x 50mm
50mm x 50mm
VIDEO SURVEILLANCE SYSTEM (IP CCTV) Make:- Axis/Sony/Bosch/Pelco
Supply, installation, testing & Commissioning of 1080p IR Bullet camera with 1/2.8‑inch CMOS, Total sensor pixels 1920 (H) x 1080 (V); 30fps Sensitivity – Measured according to IEC 62676 Part 5 (1/30, F1.6), Color 0.06 lx, Mono 0.02 lx, With IR 0.0 lx, 120dB WDR, H.265; H.264; M- JPEG, Automatic Electronic Shutter (AES); Intelligent Dynamic Noise Reduction, Intelligent Defog, Rule based alarms and tracking, Line crossing, Enter / leave field, Follow route, Loitering, Idle / removed object, People counting, Crowd density estimation, 3D tracking based on Duration, Size, Aspect ratio v/h, Speed, Direction, Color, Object classes (Upright persons, Bikes, Cars, Trucks) Privacy Masking, Pixel counter, Memory card slot, IR Range 30mtr, Automatic Varifocal 3.2 to 10 mm, Alarm Input 1/1, Audio Input/output, RJ45, G.711, Audio Streaming Full-duplex / half duplex, ONVIF Profile S, G & T, IP66, IK10, PoE, CE, FCC, UL certified. SD card support up to 2TB. FTP, Dropbox and e-mail applications
Supply, installation, testing & Commissioning of 1080p Dome camera with 1/2.8‑inch CMOS, Effective pixels 1920 x 1080 (2MP), 30fps, Sensitivity – (Measured according to IEC 62676 Part 5 (1/30, F1.6) Color 0.06 lx Mono 0.02 lx With IR 0.0 lx, 120 dB Dynamic range, Electronic Day/Night, Automatic Electronic Shutter (AES), H.265, H.264 MP (Main Profile); M-JPEG Video compression, White balance, Backlight Compensation, Privacy Mask,Rule based alarms and tracking, Line crossing, Enter /leave field, Follow route, Loitering, Idle / removed object, People counting, Crowd density estimation, 3D tracking based on Duration, Size, Aspect ratio v/h, Speed, Direction, Color, Object classes (Upright persons, Bikes, Cars, Trucks), 3.2 to 10 mm Automatic Varifocal (AVF) lens, MicroSD card slot for edge recording, Motion, tamper and audio detection, FTP, IR range upto 30mtrs Dropbox and e-mail applications, 3 axis adjustment, ONVIF Profile S & G & T, PoE, IP66, IK10, CE, FCC, UL certified. SD card support up to 2TB.
Supply, installation, testing & Commissioning of 1080p HD IR PTZ Camera with 1/2.8" progressive scan CMOS, Effective pixels 1945 (H) x 1097 (V) (approximately 2.13M pixels), 30x Optical Zoom (4.5 mm–135 mm)(F1.6 - F4.4), 16X Digital Zoom, Minimum Illumination- Color: 0.0186 Lux , B/W: 0.004 lux, IR: 0 lux; IR distance 180 m (590 ft) (Detection); 120dB WDR, H.265, H.264, MJPEG streams, Intelligent Dynamic Noise Reduction, BLC, White Balance, Pan Range 360° continuous, Tilt Range -90° to 3° (Auto-flip 186°), Pan/Tilt Modes - Pan: 0.1°/s - 240°/s; Tilt: 0.1°/s - 120°/s, Presets 256, Tours, Audio- 1/1 Channel In/Out, Micro SD card support up to, 32 individually configurable privacy masks, Alarm inputs/outputs - 2/1, Dual Power options, Any object, Object in field, Crossing line, Entering field, Leaving field, Loitering, Following route, Idle object, Removed object, Counter, Occupancy, Crowd detection, Condition change, Similarity search, Tampering, Object filters based on Duration, Size, Aspect ratio v/h, Speed, Direction, Color, Object classes (Upright persons, Bikes, Cars, Trucks), IP66 , ONVIF Profiles S & G & T, FCC, CE, UL Certified. SD card support up to 2TB.
Supply, installation and commissioning of Remote compact keyboard, variable speed, USB Joystick Control, for PTZ camera/NVR, UL Listed.
SITC of Rack Server, Windows 2019, 16 GB DDR4 ECC, Intel® Xeon® Silver 4210, OS RAID1, Idrac,1G NVIDIA Quadro P620 (2GB) video card, 450mbps Bandwidth, 3 year warranty
Supply installation Testing and Commissioning of Video Management Software, All Cameras shall be of same make *web based client allows viewing and exporting video without installing any software. *Imports users and roles from existing LDAP servers to reduce administrative overhead,and enables single sign-on (SSO) *Capable of listening for ASCII commands *Check on VMS and camera health using SNMP *Supports IPv4 and IPv6 cameras *Enables and supports Risk Management Framework (RMF),incorporates FIPS 140-3 validated cryptographic modules *TLS-based encryption over HTTPS
Supply & Installation of Surveillance harddrive 12 TB
Supply, Installation, Testing and Commissioning of Workstation PC: Intel(R) Core(TM) i7-3770 Processor (8M Cache, up to 3.90 GHz); Memory: 4GB, NON-ECC, 1600MHZ; RAM: 4GB (1x4GB) Non-ECC DDR3 1600MHz SDRAM Memory; Keyboard: 12 function keys; Chassis: Tower/Workstation; DVD: 8X Slimline DVD+/-RW, Data Only; 20" TFT Monitor; Dual Graphics Card; Network interface card: Integrated Intel(R) 82579LM Gigabit1 Ethernet LAN 10/100/1000; Hard disk: 250GB, 7200 RPM 3.5" SATA 6Gb/s Hard Drive; Operating system: Windows 7 Professional 64 Bit.
SITC 43 inch 4K Smart Monitor for surveillance.
Supplying and fixing Patch Chord - 1 Mtr with appropriate terminal connectors (Used for CCTV I/O connection)
Supply of HDMI Cable 1.5 meters
Supply , Installtion , Testing and Comissioning of following sizes wall mount 4U rack , 2 cable managers.This rack to be used for CCTV, DATA networking also and to be placed in shaft.
SITC 8-Port Gigabit PoE Smart Managed Pro Switch, 8-Port 53 W Power-Over-Ethernet, ProSAFE Lifetime Protection.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. MAKE:- POLYBACK/Precision/AKG/Anchor/BEC) 25 mm
Supplying, laying, marking, making connections and testing of CAT-6 cable . (For CCTV Camera ) Make:- CCI/Havells/Polycab/Legrand.
Supply, installation, testing & commissioning of IP66 Box ( 600 X 400 mm) with bottom lowers for heat dissipation for housing Switches, media converter, power supply units for camera connecting over fiber optics( 2 cameras connected to 1 outdoor box).
Supply & Erection of 75mm dia GI poles suitable for mounting camera required. Provision to be made for cable entry and connection for camera with all fixing arrangement to the pole etc, complete as required. 6.0 m mounting height
Supply and laying of following DWC HDPE P1/2C as per IS 14930-2001(Part-2) at road crossings including excavation, refilling, cutting the road and making good for the same with sealing of ends as required.
63 mm inner dia
100 mm inner dia
Supply, laying, termination, testing and commissioning of following single mode armored- uni tube fiber optic cable complete as required. 6 core fiber optic cable
Supply, laying, termination, testing and commissioning of following armored cable on existing cable tray including the cost of making of connections, complete as required.:-
4 pair CAT 6 Cable
2 core 1.5 Sq.mm.copper power cable
ELV SYSTEM
DATA NETWORKING SYSTEM
Supply, Installation, testing and commissioning of following 24 Port Switch Ethernet work station , layer 2, managed 1 Ghz, Network Switch with POE+ facility and 2 Nos. of Fiber Ports (Make-Cisco, Netgear, Juniper, Legrand)
Supply, Installation, testing and commissioning of 24 Port Patch Panel Category 6, IDC patch panel prepackaged with wiring block with legs with legs insert labels, label holders, jumper troughs, metal back panel, duct assembly, screws, washers and an instruction sheet for termination of incoming pairs and all necessory accessories to complete the work (Make-Amp. Beldon Seimon Derwiser R&M)
Supply and laying of 6 core MM 50/125 micron OM3 , LSZH, Fibers multitube type Optical Fiber Cable of Armoured type. (Make-Amp. Beldon Seimon Derwiser R&M)
Supply, installation, testing and commissioning of 4 pair Category 6 UTP cable consisting of 23 AWG solid copper conductors and as per the specification. The cable should have flexible jacket and ripcord for easy stripability. (Make-R & M, Beldon,Molex Systimax)
Supply , Installation , Testing and Comissioning of CAT6 information outlet (I/O) for Data at user end. (Make-Amp. Beldon Seimon Derwiser R&M)
Supply , Installation , Testing and Comissioning of CAT6 patch cord 3 feet for rack side switch to jack panel connectivity. (Make-Amp. Beldon Seimon Derwiser R&M)
Supply , Installation , Testing and Comissioning of CAT6 patch cord 7 feet for information outlet (I/O) to end user device connectivity. (Make-Amp. Beldon Seimon Derwiser R&M)
Supply , Installation , Testing and Comissioning of 1, 2 and 4 port face plate white for I/O fixing at user side. (Make-Amp. Beldon Seimon Derwiser R&M)
Supply , Installation , Testing and Comissioning of Fiber LIU 12 Port Loaded with pig tails (Make-Amp. Beldon Seimon Derwiser R&M)
Supply , Installation , Testing and Comissioning of Fiber Module MM LC Gigabit (Make-Cisco, Netgear, Juniper, Legrand, Tricom )
Supply , Installation , Testing and Comissioning of Network Rack 18 U 600x800 Floor Mount, 2 cable managers , satationary shelf , 2 Nos. of hardware pkts. This rack is common for Telephone, Data, Access Control system. (Make-Sunshine, Netshell)
Supply , Installtion , Testing and Comissioning of 4U wall mount rack with fans , 2 cable managers , satationary shelf , 2 Nos. of hardware pkts. This rack to be used for CCTV, DATA networking also and to be placed in shaft. (Make-Sunshine, Netshell)
Providing and fixing in position the 25 mm dia conduit FRLS PVC conduits concealed or exposed as called for including all acessories i.e. bends, junction boxes, outlet boxes with cover plates of approved make and design.
EPABX SYSTEM
Supply Installation, Testing and Commissioning of Server Based EPABX Fully Computerized IP System, SIP Compliant. 2U Rack Mountable,Expandable upto 700Ports.and configured as for below Ports P & T(CO Trunk) Line 16 Nos. PRI(30 Channel) 2 Nos. IPExtension Circuit 25 Nos. Digital Extension Circuit 48 Nos Analog Extension Circuit 240 Nos SIP Trunking 48 Nos.
Supply Installation and Commissioning of PC Based centralized Operator Console with all dignostic Software of IP EPABX System (Supplying with PC).
Supply Installation, Testing and Commissioning of Integrated Viocemail System 4 Level IVR software with 6 different languages and 4 time schedule(As per OEM).
Supply Installation and Commissioning of License for web integration for aspire net license integrated with hub exchange Make-NEC/Avaya/Alacatel
Supply Installation Testing and Commissioning of Digital Phone (24Key+ 60-line DSS Console) Backlit keypad Hands-free, full duplex ,Headset support Easy to use soft keys/LCD prompts,Directory dialling,Navigation wheel,Call history,Backlit LCD screen,Bluetooth support (BCAZ),Security lock key XML open interface .Make-NEC/Avaya/Alacatel
Supply Installation Testing and Commissioning of 24Key Digital Phone Backlit keypad Hands-free, full duplex ,Headset support Easy to use soft keys/LCD prompts,Directory dialling,Navigation wheel,Call history,Backlit LCD screen,Bluetooth support (BCAZ),Security lock key XML open interface .Make-NEC/Avaya/Alacatel
Supply Installation Testing and Commissioning of Digital Phone (12Key)Backlit keypad Hands-free, full duplex Headset support Easy to use soft keys/LCD prompts Directory dialling Navigation wheel Call history , Backlit LCD screen,Bluetooth support (BCAZ),Security lock key XML open interface.
Supply Installation Testing and Commissioning of Digital Phone (6Key)Backlit keypad Hands-free, full duplex Headset support Easy to use soft keys/LCD prompts Directory dialling Navigation wheel Call history , Backlit LCD screen,Bluetooth support (BCAZ),Security lock key XML open interface.
Supply Installation Testing and Commissioning of IP Phone (12Key)Backlit keypad Hands-free, full duplex Headset support Easy to use soft keys/LCD prompts Directory dialling Navigation wheel Call history , Backlit LCD screen,Bluetooth support (BCAZ),Security lock key XML open interface.
Supply Installation, Testing and Commissioning of Analog Speaker Phone with backlight.
Supplying, of 100 Pair anealed tinned copper conductor PVC insulated and sheathed armoured copper telephone cables with suitable clamps, saddles and including making terminal joints complete as required.
Supplying, of 50 Pair anealed tinned copper conductor PVC insulated and sheathed armoured copper telephone cables with suitable clamps, saddles and including making terminal joints complete as required.
Supplying, Installation, Testing & Commissioning of of 50 Port telephone Jack Panel
BED HEAD PANEL
Providing and Fixing of Bed Head Panel Horizontal Bed Head Panel made by high strength aluminium section,thickness of aluminium section 3 mm. Bed Head Panels offered by us are available in Aluminum Powder coated with provision for Gas Outlets & Electrical 5/15 Amps switch sockets
SUBSATION EQUIPMENTS
TWO POLE STRUCTURE WITH GO-DO SWITCH
Supplying, fixing, testing and commissioning of two pole structure for receiving 11 KV 3 phase incoming line for dept. comprising of :-
2 nos 11 mtrs long, Steel pole as per sate electicity board(SEB) specifications.
Cement Concrete foundation (1:2:4), 2250 mm below ground and 450 mm above including excavation and refilling etc as shown on drawings.
Steel cection, channels, angles, flats, clamps, GI nuts, bolts and required hardware etc. of different sizes for cross arms, bracings, supports for pole, insulators, lightning arrestors, GO switch, GI pipe for 11 KV cables, supports for terminations, including anti climbing barbed wires, danger plate as per specification of SEB.
11 KV class disc / pin / support insulator complete with clamps and fixing hardware etc.
3 nos , one per phase ,11 KV station class thyrite type lightning arrestors complete with mounting arrangement on the incoming overhead line along with earthing connections complete as per specification and as required.
1 set of G.O. Air break switch with DO fuse 400 Amp. With gang operated devices, with pad locking arrangement. Operating rod, supports, complete with operating handle and locking arrangement complete as per UHBVN.specification and as required.
50 Mtrs. - size 6/1/4.09 mm ACSR Conductor and connectors for tapping the connection and for connections with in two pole structure with heat shrinkable insulating sleeves for protection of connections etc as shwon on drawing.
50 mtrs -Earth connection with 50 x 6 mm GI Strip.
SUPPLY & INSTALLATION OF TWO POLE STRUCTURE WITH GO-DO SWITCH
11 KV ENERGY METER
Supply, fixing , testing and commissioing of Energy meter for the 11 KV connections including testing of the meter by SEB lab and control cabling from CTPT to the meter complete with all respect as per the norms and the requirement of SEB.
11KV HT PANELS (NEAR METER)
Design, manufacture, assembly,Testing & inspection at works, supply, and delivery (at Site), of 11kV, 350 MVA, in-door type Switchgear Panel with horizontal Isolation and Horizontal draw out vacuum circuit breaker, having anti pumping and trip free feature and complete In metal clad floor mounted vermin proof panel board, fabricated out of minimum 2mm thick CRCA sheet as per specifications. The panel shall be complete with all accessories / fitting / wiring, cable termination boxes suitable for 3C x 185 Sqmm XLPE armored, aluminium conductor cable for incoming and outgoing feeder, foundation bolts etc. The Panel shall be complete with required for Metering and protection relays,CTs/PTs and other related accessories, as required as per SLD and as per specifications. The Panel Shall consisting of following:-
1 Nos 11 kV, 350 MVA, 630A, Electrically operated, draw-out VCB complete with stored energy mechanism for manual operation, three position isolator/ earthing switch with manual operating mechanism & auxillary switch with 6NO + 6NC contacts, busbars, interlocking and earth bar etc.as per specifications. Incommer shall be provided with necessary auxiliary relays, control switches, emergency hand trip devices and mechanical ON / OFF indicator etc.
Breaker shall be provided with the following for metering Indication and protection:
One (1) set of CTs of ratio 200/10/5-5A with metering and protection cores. Metering core shall be of class 0.5 and of 5VA, the core for protection shall be of 15VA and class 5P10.
One (1) set of PTs of ratio 11KV/rt3 / 110V/rt3 , class 0.5 and of burden 100 VA.
One (1) No. Multifunction meter (MFM-1) with RS-485 Port suitable for measurement of voltage, currents, power factor, frequency, Energy (KWH, KVARH KVAH), Power (KW, KVA and KVAR), harmonics and maximum demand indication.
One (1) Set of phase indication lamps with 2Amp SP MCB for protection (Red, Yellow and Blue).
One (1) set of Red/ Green indicating lamp for close and open position.
One (1) No. amber indicating lamp for auto trip.
One (1) No. clear indicating lamp for trip circuit healthy.
One (1) No. blue indicating lamp for spring charged.
One (1) Set of Power Pack
One (1) No Hooter
One (1) Set of Multifunctional, Protection Relay with communication compatibility and with min. protection 51, 51N, 27 & 59
Master Trip Relay.
Trip circuit supervision relay
Note : Necessary Co-ordination shall be done by the Panel Manufacturer / Vendor with the vendor of "Gas flooding system" for fire protection, for making suitable provisions in the panels, at the Design stage, Manufacturing stage, stage of testing at works & stage of commissioning at site.
SUPPLY & INSTALLATION OF MAIN DISTIBUTION BOARD AS DESCRIBED ABOVE
OIL TYPE TRANSFORMER
Supplying, installation, testing and commissioning of 1600KVA, 11/0433 KV, 50 Hz, Dyn 11, outdoor ONAN type,copper wound transformer with OFF load tap changing arrangement on HV side in steps of +/- 2.5% & -7.5%, having cable end boxes on HV side suitable for 3x185sqmm XLPE cable of 11 KV grade arrangement on LV side complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 2026 (Part 1 to Part 5 & as per specification attached complete in all respects as required at site. MAKE:- KOTSONS/KIRLOSKAR/AREVA-SCHNEIDER/GTBSYNERGY
OIL TYPE TRANSFORMER
Supplying, installation, testing and commissioning of 500KVA, 11/0433 KV, 50 Hz, Dyn 11, outdoor ONAN type,copper wound transformer with OFF load tap changing arrangement on HV side in steps of +/- 2.5% & -7.5%, having cable end boxes on HV side suitable for 3x185sqmm XLPE cable of 11 KV grade arrangement on LV side complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 2026 (Part 1 to Part 5 & as per specification attached complete in all respects as required at site. MAKE:- KOTSONS/KIRLOSKAR/AREVA-SCHNEIDER/GTBSYNERGY
11KV HT PANEL (NEAR TRANSFORMER)
Design, manufacture, assembly,Testing & inspection at works, supply, and delivery (at Site), of 11kV, 350 MVA, in-door type Switchgear Panel with horizontal Isolation and Horizontal draw out vacuum circuit breaker, having anti pumping and trip free feature and complete with copper bus bar, enclosed in metal clad floor mounted vermin proof panel board, fabricated out of minimum 2mm thick CRCA sheet as per specifications. The panel shall be complete with all accessories / fitting / wiring, cable termination boxes suitable for 3C x 300 Sqmm XLPE armored, aluminium conductor cable for incoming and outgoing feeder, foundation bolts etc. The Panel shall be complete with required No. of bays for Metering and protection relays,CTs/PTs and other related accessories, as required as per SLD and as per specifications. The Panel Shall consisting of following:-
Incomer
1 Nos 11 kV, 350 MVA, 630A, Electrically operated, draw-out VCB complete with stored energy mechanism for manual operation, three position isolator/ earthing switch with manual operating mechanism & auxillary switch with 6NO + 6NC contacts, busbars, interlocking and earth bar etc.as per specifications. Incommer shall be provided with necessary auxiliary relays, control switches, emergency hand trip devices and mechanical ON / OFF indicator etc.
Each incomming Breaker shall be provided with the following for metering Indication and protection:
One (1) set of CTs of ratio200/100/5+5A with metering and protection cores. Metering core shall be of class 0.5 and of 5VA, the core for protection shall be of 15VA and class 5P10.
One (1) set of PTs of ratio 11KV/rt3 / 110V/rt3 , class 0.5 and of burden 100 VA.
One (1) No. Multifunction meter (MFM-2) with RS-485 Port suitable for measurement of power factor, Energy (KWH, KVARH KVAH) & Power (KW, KVA and KVAR), (Conzerv EM6434 or Equivalent make).
One (1) Set of phase indication lamps with 2Amp SP MCB for protection (Red, Yellow and Blue).
One (1) set of Red/ Green indicating lamp for close and open position.
One (1) No. amber indicating lamp for auto trip.
One (1) No. clear indicating lamp for trip circuit healthy.
One (1) No. blue indicating lamp for spring charged.
One (1) Set of Multifunctional, Protection Relay with communication compatibility and with min. protection 51, 51N
Master Trip Relay.
Trip circuit supervision relay
One (1) Set of Power Pack
One (1) No Hooter
Busbar:
1 Sets of 700 Amp, duly insulated with Color coded heat shrinkable PVC sleeved, TP copper busbar of 350MVA fault rating.
1 Nos of 24 V, Power Pack of suitable back up rating for Indication, Annunciation and trip coil operation as required and as per specifications.
Outgoings (3 Nos.):
3 Nos 11 kV, 350 MVA, 630A, Electricaly operated, draw-out VCB complete with stored energy mechanism for manual operation, three position isolator/ earthing switch with manual operating mechanism & auxillary switch with 6NO + 6NC contacts, busbars, interlocking and earth bar etc.as per specifications. Outgoing shall be provided with necessary auxiliary relays, control switches, emergency hand trip devices and mechanical ON / OFF indicator etc.
Each Breaker shall be provided with the following for metering Indication and protection:
One(1) set of CTs of Dual ratio 100/50/5+5A with metering and protection cores. Metering core shall be of class 1.0 and of 5VA, the core for protection shall be of 15VA and class 5P10.
One (1) set of Red/ Green indicating lamp for close and open position.
One (1) No. amber indicating lamp for auto trip.
One (1) No. clear indicating lamp for trip circuit healthy.
One (1) No. blue indicating lamp for spring charged.
One no. 4 window Audio/visual annunciator system complete with hooter, Ack, test & Reset PBs for annunciation of WTI Alarm / Trip etc.
One (1) Set of Multifunctional protection relay with Communication Compatibility with minimum protection 50,50N,51, 51N .
Master Trip Relay.
Trip circuit supervision relay
Note : Necessary Co-ordination shall be done by the Panel Manufacturer / Vendor with the vendor of "Gas flooding system" for fire protection, for making suitable provisions in the panels, at the Design stage, Manufacturing stage, stage of testing at works & stage of commissioning at site.
11KV HT PANEL as described above OF MAKE:- ABB/SCHNEIDER/SIEMENS
MAIN LT SWITCHGEAR PANELS:
Design, manufacture, supply, installation, testing and commissioning of following Utility panels suitable for 415 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 2mm thick CRCA sheet steel for Load bearing members and 1.6 mm thick for non-load bearing members, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber (form-3b Construction). The panel shall be complete with name plate, earthing, numbering, danger plate etc. as required and as per specifications and drawings. The panel shall withstand the fault level of as indicated elsewhere or shown in Single Line Diagram.
Important Notes: Common for all Switchboard:
The BOQ shall be read inconjunction with general notes, specification and Single Line Diagram (attached for Ref.). Incase of any discrepancy between specification, BOQ and SLD, the same shall be brought to the notice of Client/Consultant before quoting the rates, otherwise stringent condition shall be deemed to have been considered.
MAIN LT Panel Shall Be TTTA Type As Per IEC 61439 1&2 Integrated Test Certificates Incommer Rating Wise. As Per IS 1893 For Seismic Zone 5 Complaint
All MCCB shall be provided with door interlocked rotary handle with ON/TRIP/OFF position indicator, continious variable thermal magnetic O/C and S/C releases. All rating MCCB's shall be thermalmagnetic type.
Incoming MCCBs shall be provided with O/C, S/C, and Earth fault protection releases.
Outgoing MCCBs shall be provided with O/C, short circuit protection.
All feeder doors shall have pad locking arrangement.
All TP feeders shall have solid isolable neutral link.
All MCCB used in starter feeder shall be suitable for motor duty application.
All power contactors including NIC shall be of AC3 duty.
All ACB's shall be with micro processor based releases and Breaker Control Switch (BCS) having lost motion device.
Incoming ACBs shall be provided with O/C, S/C, Instentaneous short circuit and Earth fault protection releases.
Spare contaCTs of ACB/Relays/Contactor etc. shall be wired upto terminal block.
All switchgear used in starter feeder shall be type-2 co-ordinated. Manufacturer is required to submit manufacturers type-2 co-ordination chart for the make used.
All meters are digital type.
Panel shall be powder coated of approved shade with minimum 60 micron thickness.
ACB's/MCCB's in one particular panel shall be of one similar make.
Size of Voltmeter / Ammeter for incomer also, 96mm x 96mm flush mounted with shrouded terminal shall be used in the panel.
Bus bar chamber shall be kept at top of the all panels.
All bus bar shall be insulated with coloured PVC Sleeve i.e.RYB,BK as per colour code.
Internal wiring of panel shall be with size 2.5sqmm Flexible Copper Conductor for CT circuit and control wiring with 1.5 sqmm.
All Lift Panels transport section should not be more then 1000 mm.
In soft starter Vender should supply power contactor with aux. Contactor & All necessary accessories required etc. (As per BOQ & specification )
All indicating light shall be LED type .
Each vertical section of floor mounted panel shall have independent base frame (75mm x 40mm) size made out of 3 mm sheet steel (LT Panel & DG Panel).
Wherever only voltmeter & ammeter are required, the same may be provided in combined meter suitable for both parameter.
Main LT Panel TTTA Type As Per IEC 61439 1 & 2 Integrated Test Certified Incommer Rating Wise IS 1893 Seismic Zone V Complaint
Incoming : (TRANSFORMER)
Metering & indication and Annunciation for Transformer Supply incoming breakers :
Each transformer supply breaker shall be provided with the following:
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents, Power Factor, Frequency, Power & Energy (Siemens Smart 7KT or equivalent) with one set (3 Nos.) of CTs of ratio 2500/5A Class 1.0, 15VA.
One set (3 nos.) phase indication lamps with control MCB.
One (1) set of 2500/5 A, C.L 1.0 CTs for input to APFC relay.
Protection Relays & Interlocking for transformer breaker:
Each Transformer breaker to be provided with :
One (1) no. REF (CAG14) or equivalent relay with stabilising resistance for transformer REF protection with 4 nos. 1200/1A,CL-PS CTs of suitable VA and knee point voltage.
Trip Circuit supervision relay (VAX-31 of Areva or Equivalent).
Master trip relay (VAJH-13 of Areva or Equivalent).
Incoming : (D.G SET)
Metering & indication and Annunciation for Transformer Supply incoming breakers :
Each transformer supply breaker shall be provided with the following:
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents, Power Factor, Frequency, Power & Energy (Siemens Smart 7KT or equivalent) with one set (3 Nos.) of CTs of ratio 1000/5A Class 1.0, 15VA.
One set (3 nos.) phase indication lamps with control MCB.
Protection Relays & Interlocking for transformer breaker:
Trip Circuit supervision relay (VAX-31 of Areva or Equivalent).
Master trip relay (VAJH-13 of Areva or Equivalent).
Notes :
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
Operation interlocks as per specification & drawings indicating sufficient nos. of potential free contacts for interlocking/indication annunciation/ control etc shall be provided by the bidder as required.
Bus Coupler :
1 no.2500 Amps, 415 V, 65KA four pole EDO ACB Bus coupler breaker complete with Micro Processor Release O/L & S/C shunt trip release, anti pumping protection, ON/OFF/ indication etc.
Electrical & mechanical interlocking shall be provided between two incomers and one bus coupler.
Busbar :
2 Sets of 3200A, 65kA,TPN Al. Busbar insulated with heat shrinkable sleeves and shall be colour coded.
Separate earth bar of 50 x 6 mm Aluminium shall be provided.
Outgoings :
Each outgoing feeder shall be provided with ON/OFF/ Trip indication lamps with back-up SPMCB.
2no.800 Amps, 65KA TP MCCB complete with Micro Processor Release, Ext ROM ON/OFF/Trip indication etc.
1 No. 800A, 65KA TPN MCCB.
13 No 630/500A 65KA TPN MCCB
2 No 315A 65 KA TPN MCCB
4 No 160A 65 KA TPN MCCB
1 No 63A 65 KA TPN MCCB
Note : Necessary Co-ordination shall be done by the Panel Manufacturer / Vendor with the vendor of "Gas flooding system" for fire protection, for making suitable provisions in the panels, at the Design stage, Manufacturing stage, stage of testing at works & stage of commissioning at site.
Main LT Panel described as above OF MAKE:- ABB (ArTuK) / Schneider electric (BLOKSET )/ Siemens ( SIEPAN ) /L&T (Ti) or their authorized licensee channel partner (in case of channel partner, the name shall be got approved from Engineer-in-charge). In all cases standard design inspection shall be done by licensor, who shall be fully responsible for performance of the panel.
Capacitor Panels (500 kVAR) MAKE:- TRICOLITE, ADLEC, ADVANCE PANLES & SWITCHGEAR (P) LTD., SIMON FABRICATOR JAMMU, PRISTINE
Incoming :
Metering, Indication and Protection :
One (1) set of RYB phase indication lamps with control SP MCB.
Busbar :
1250A TPN Al. Busbar insulated with heat shrinkable sleeves and shall be color coded.
Separate earth bar of 50 x 6 mm of Aluminium shall be provided.
Outgoings :
500 KVAR Capacitor Panel in steps of 3 nos. of 2 x 50 kVAR banks 3 nos. of 2 x 25 kVAR banks, 2 Nos. of 1 x 25 kVAR banks,2 No.of 1X 10 kVAR bank and 2 No.of 1X 5 kVAR bank
Notes:
Each capacitor bank should have its individual MCCB/MCB & Contactor suitable for capacitor duty including fuses for each capacitor unit as per specifications and approved SLD.
Enclosure of capacitor panel shall be liberally designed to take care of internal heat emission by capacitor unit without forced cooling and to limit the temperature rise with in permissible limit. However, louvers are allowed to facilitate extra cooling.
Enclosure shall be so designed as to keep the space for Detuned reactors for future if required.
Capacitors shall be of Heavy duty grade MPP type.
HT CABLE
Supplying of following sizes of XLPE/ PVC insulated Aluminum/ Copper conductor and Armoured, overall PVC sheathed 11 KV grade cables conforming to relevant IS code and technical specifications. Make:- cci/havells/polycab
3C x 240sq.mm.
HT CABLE LAYING (DSR ITEM)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Above 120 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
Above 120 sq. mm and upto 400 sq. mm
HV CABLE JOINTING & END TERMINATION (DSR ITEM)
Supplying and making indoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
Supplying and making outdoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
MISC. CIVIL ITEMS (DSR ITEM)
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
63 mm dia (OD-63 mm & ID-51 mm nominal)
160 mm dia (OD-160 mm & ID-135 mm nominal)
EXTERNAL LIGHTING
Supplying, erection, testing and commissioning of HOT dip galvanized octagonal steel pole of 7 meter height made out of 3mm thick sheet having 2 NOS. bracket length of 500mm long including built in connector control box with flush cover and supplying and fixing of 6 Amp SP MCB C-Series and 32 Amp heavy duty connector etc. for making connections with suitable size of copper wire and thimbles / lugs in the connector box, base plate of 200mm x 200mm x 12mm thick, bolt size 4 nos 24mm long, bolt length 750mm, projected bolt length 125mm and anchor plate thickness of 3mm. The pole shall be installed in cement concrete foundation (1:3:6) i.e. 1 cement, 3 coarse sand and 6 graded stone with the help of anchor bolts of 3/4" dia by laying iron bar mesh fabricated with 6mm dia iron bar, earthing of pole, connection etc. complete as required.
Supplying, erection, testing and commissioning of HOT dip galvanized octagonal steel pole of 7 meter height made out of 3mm thick sheet having bracket length of 500mm long including built in connector control box with flush cover and supplying and fixing of 6 Amp SP MCB C-Series and 32 Amp heavy duty connector etc. for making connections with suitable size of copper wire and thimbles / lugs in the connector box, base plate of 200mm x 200mm x 12mm thick, bolt size 4 nos 24mm long, bolt length 750mm, projected bolt length 125mm and anchor plate thickness of 3mm. The pole shall be installed in cement concrete foundation (1:3:6) i.e. 1 cement, 3 coarse sand and 6 graded stone with the help of anchor bolts of 3/4" dia by laying iron bar mesh fabricated with 6mm dia iron bar, earthing of pole, connection etc. complete as required.
Supplying and fixing of Street light fixture 70 Watts LED complete with glass cover etc. and its wiring with 3 x 2.5 sq.mm PVC insulated copper wire from junction box complete ).
Providing and fixing 6SWG dia GI Wire on surface or in recess for loop earthing along with existing surface/recessed conduit/sub main wiring/cable as required.
Supplying, laying and connecting 2 nos 2.5. sq.mm copper conductor PVC insulated 1100 volts grade wires from terminal block to light fixture along with end terminations and including the cost of 1 no. 2.5 sq.mm PVC insulated copper wire for earthing of the light fixture complete as required.
EXTERNAL LIGHTING FEEDER PILLAR OUT DOOR TYPE
INCOMER
1 Nos. 63Amp 16KA 4P MCCB complete having microprocessor based over current, short circuit & earth fault protection incomer shall be complete with following.
1 Nos. 60Amp AC3 4P Contactor with timer be complete as required.
METERING FOR EACH INCOMER
3 Nos. Cast resin current transformers of Class 1.0 for metering.
Three phase indicating lamps (LED type) with MCB.
ON OFF TRIP indicating lamps (LED type).
BUSBAR
1 Set of 100A, TPN Aluminum bus bars with colour coded sleeves.
OUTGOING UNITS
15 Nos. 6/32Amp TPN MCB 10KA
SUPPLY & INSTALLATION OF EXTERNAL LIGHTING FEEDER PILLAR AS DESCRIBED ABOVE OF MAKE:- TRICOLITE, ADLEC, ADVANCE PANLES & SWITCHGEAR (P) LTD., SIMON FABRICATOR JAMMU, PRISTINE
Supplying of following sizes of XLPE/ PVC insulated Aluminum/ Copper conductor and Armoured, overall PVC sheathed 1.1 KV grade cables conforming to relevant IS code and technical specifications. Make:- cci/havells/polycab
4C x 25 sq.mm.
4C x 16 sq.mm.
2C x 10 sq.mm.
Sub-Head-I : DG set & Auxiliary works
D.G. Set
Design, manufacture, supply, erection, testing & commissioning of DG Sets of the ratings as given below, having self excited & self regulated 415 V, 3 Phase, 4-Wire, 50 Hz, 0.8 p.f. Alternator coupled with multi-cylinder, turbo-charged/ turbo-charged after cooled as called for, Diesel Engine capable to generate the power not less than the required BHP to achieve the alternator capacity as given below, with Heat exchanger cooled radiator, Hospital type silencers and Electronic governor suitable for Synchronised Operation including Engine control panel, 24 V batteries of suitable rating, battery-charger with battery leads and complete with all standard accessories & protection as required and as specified in the specifications, including first filling of lube oil providing common base plate, anti vibration pads, drip trays, foundation bolts, nuts, bolts, cable termination/adopter box sutiable to terminate upto 7 nos. of 3.5Cx240 sq.mm. XLPE cables/ or Flanges suitable for 2000A / 1600A TPN Al. Bus Duct respectively etc as required for a complete installation including initial filling of fuel and lubricants MAKE:- SUDHIR/KIRLOSKER/MAHINDRA/CATTERPILLAR
required during trial run of DG sets on full load for 12 hours followed by 10% overload for one hour in any 12 hours duration, as per specifications & drawings complete with RCC/PCC foundation for DG set as per the structural detail for Dynamic Load submitted by the Vendor and approve by the Consultant.
Note : The exhaust system should have exhaust bellow just near to DG sets and before the exhaust silencer to accommidate the expansion in the exhaust system.
1010 KVA (Without Acoustic Enclosure)
Design, manufacture, supply, erection, testing & commissioning of following rating of DG Sets in Accoustic Enclosure, having self excited & self regulated 415 V, 3 Phase, 4-Wire, 50 Hz, 0.8 p.f. Alternator coupled with multi-cylinder, turbo-charged/ turbo-charged after cooled as called for, Diesel Engine capable to generate the power not less than the required BHP to achieve the alternator capacity as given below, with Air-cooled radiator, hospital type silencers and Electronic governer suitable for Synchronised Operation including providing of AMF relay, 1250A/ 1000A Circuit Breaker as called for, & Engine control panel, 24V batteries of suitable rating, battery-charger with battery leads and complete with all standard accessories & protection as required and as per specifications, including first filling of lube oil providing common base plate, anti vibration pads, drip trays, foundation bolts, nuts, bolts, cable termination/adopter box sutiable to terminate upto 6 nos. of 3.5Cx300 sq.mm. XLPE cables, as required for a complete installation including initial filling of fuel and lubricants required during
trial run of DG sets on full load for 12 hours followed by 10% overload for one hour in any 12 hours duration, as per specifications & drawings complete with RCC/PCC foundation for DG set as per the structural detail for Dynamic Load submitted by the Vendor and approve by the Consultant.
Note : The exhaust system should have exhaust bellow just near to DG sets and before the exhaust silencer to accommidate the expansion in the exhaust system.
500 KVA (With Acoustic Enclosure)
625 KVA (With Acoustic Enclosure)
Exhaust Piping
Supply, installation, testing & commissioning of Class ‘C’ M.S. pipe including bends, flanges, supports etc. as required complete with 75 mm dia fibre glass wool insulation with 26 swg aluminium sheet cladding.
300 mm dia pipe
250 mm dia pipe
200 mm dia pipe
Fuel Day Oil Tank ,Vall valves & stainers
Supply, fabrication, installation testing & commissioning of M.S. day oil tanks of following capacity fabricated out of min. 6mm thick sheet installed on steel frame with all associated accessories, filters, breathers and fittings including level indicator, complete as required, including level controller for automatic operation of pumps. The tank shall be suitably treated with anti corrosive treatment on inside & outside surface complete with PCC foundation 75mm thick (1:3:6)
990 Litre
Fuel Oil Piping
Supply, installation, testing and commissioning of following 'C-class' M.S. piping conforming to IS:1239 for fuel piping complete with all necessary fittings and valves between day oil storage tanks & DG sets/ priming motor including jointing of pipes, painting of pipes with two coats of red oxide & two coats of black enamel paint.
32 mm dia Pipe
25 mm dia Pipe
32 mm dia Ball valves
25 mm dia Ball valves
Y-strainer suitable for 32mm dia. pipe.
Y-strainer suitable for 25mm dia. pipe.
Cooling System
Supply, installation, testing and commissioning of Induced Draft Counter flow type FRP cooling tower of following rating of DG & suitable for heat rejection capacity equivalent to the indicated DG Set with FRP water basin PVC fillings with integral louvres and drift eliminators hot water distribution by gravity, complete with statically and dynamically balanced axial flow gear driven fans with TEFC induction motor suitable for operation on 415 ± 10% Volts, 3 phase, 50 HZ, A.C. supply, complete with suction screen, make up and quick fill arrangement, overflow and drain connections, suitable inspection ladder, access arrangement for cooling tower interior, and concrete foundation, steel supporting structure, and vibration mountings etc. complete as per specifications.
Suitable for 1000 KVA DG set (approx 110 TR)
Supply, installation, testing and commissioning of cooling tower water pump set of suitable capacity against a head of 25 Mtrs., each comprising the following and complete as per specifications for the above system.
Monoblock pump of 900 LPM for 1010 KVA DG sets (2W+1S)
Supply, installation, testing and commissioning of following sizes of Nominal Bore (NB) MS 'C'-class pipe suitable for Heat Exchanger to cooling tower along with necessary clamps, supports, hangers and fittings including painting as per specs
200 mm dia (NB)
150 mm dia (NB)
125 mm dia (NB)
100 mm dia (NB)
Providing Accoustic insulation in DG Rooms walls & roof by providing 50 mm thickfiber glass blanket of 42 Kg/Cu.M density on angle iron frame and making a grid of 500mmx500mm. The fiber glass blanket will be covered with 20 gauge, GI chicken wire mesh and hold to wall/roof by means of Hilti, Dash fasteners or approved equivalent. This will be further covered with 26 gauge perforated GI sheet fitted to angle iron with self tapping screws or other suitable fasteners in grid of 600x600mm. A thick coat of bitumin primer will be applied to wall before putting up this accoustic lining.
Boq for Electrical Panels & Bus trunking
The contractor shall consider the following details in their item rates, wherever required:
Supporting rigid steel framework.
Cubicle types 2mm thick CRCA
Complete with inter connections and distribution busbars.
Proper bonding to earth.
Embossed PVC plates on boards, showing circuit diagrams.
Padlocking of panel doors.
Padlocking of MCCB’s handle in off position.
Providing cable supports within cable Alley.
ACBs for all incomers shall have led indication for fault type, Microprocessor failure and LCD display for curves & parameters.
TPN ACB mean 3 pole & neutral
TPN MCCB mean 3 pole & neutral
ACB’s shall have minimum 35 MVA breaking capacity, unless specified otherwise.
All Incomers MCCB of Meter board panels shall be provided with Earth-fault module with CTs of suitable rating complete
MCB’s shall have 10 KA breaking capacity.
All motor feeders' MCCB / MCB shall be suitable for motor duty application.
All DOL & Star-Delta Starters shall be provided with SPPR (single phase preventor relay) and 2 nos. of Aux.Contacts for Remote operation/monitor.
All MCCB's shall be provided with Extended Rotatry operating handle.
The Panel fabricator shall provide Al./ Copper Bus-bars link from Breakers wherever more than two nos. of cables are terminated in the breakers.
All breakers in panels shall have a fault level as indicated in single line diagram.
Readymade 16SWG Sheet steel Enclosure with cutout For MCBs
All DBs shall be Double Door type
Embossed PVC plates on boards & DB chart inside of the DB door.
All MCBs in Panel shall be suitable for motor duty application.
PLC based AMF & Synchronisation control Panel-1 for D.G.sets for L&P
INCOMER FOR GENERATORS 1nos.-500 KVA )
Each Incomer for D.G. set shall be provided with the following:
1 no. 800A TP EDO ACB with 500A Neutral Isolation Contactor having programmable trip setting for releases with the following microprocessor based integral protection:
Voltage restraint IDMTL Overcurrent relay,
Unbalance Load protection
Reverse power Protection.
U/V & O/V protection
Master trip relay
Restricted Earth fault relay along with 800/1A PS class CT to be mounted on neutral of D.G. set
In addition to above relays shall be provided for the following protection:
Anti Pumping device
Trip circuit supervision relay
The ACB shall be complete with 3nos. 800A/5A, 15VA, 5P10 CTs for protection .
Metering & Indication
1 set of R,Y,B phase indicating lamps with 3 nos. 2A SP MCBs.
1 No. Load Analyser cum digital Multifunction Meter with 3 nos. 800/5A, CL-1 CTs, as required.
1 Set of Breaker ON-OFF-TRIP, Spring charged & Trip circuit healthy indication Lamps
1 set of Indication Lamps for NeutraI Isolation Contactor ON & OFF and Battery charger ON
INCOMER FOR GENERATORS 1nos.-630 KVA )
Each Incomer for D.G. set shall be provided with the following:
1 no. 1000A TP EDO ACB with 500A Neutral Isolation Contactor having programmable trip setting for releases with the following microprocessor based integral protection:
Voltage restraint IDMTL Overcurrent relay,
Unbalance Load protection
Reverse power Protection.
U/V & O/V protection
Master trip relay
Restricted Earth fault relay along with 800/1A PS class CT to be mounted on neutral of D.G. set
In addition to above relays shall be provided for the following protection:
Anti Pumping device
Trip circuit supervision relay
The ACB shall be complete with 3nos. 1000A/5A, 15VA, 5P10 CTs for protection .
Metering & Indication
1 set of R,Y,B phase indicating lamps with 3 nos. 2A SP MCBs.
1 No. Load Analyser cum digital Multifunction Meter with 3 nos. 1000/5A, CL-1 CTs, as required.
1 Set of Breaker ON-OFF-TRIP, Spring charged & Trip circuit healthy indication Lamps
1 set of Indication Lamps for NeutraI Isolation Contactor ON & OFF and Battery charger ON
INCOMER FOR GENERATORS 2 no.- (1010 KVA )
Each Incomer for D.G.set shall be provided with the following:
1 no. 1600A TP EDO ACB with 500A Neutral Isolation Contactor having programmable trip setting for releases with the following microprocessor based integral protection:
Voltage restraint IDMTL Overcurrent relay,
Unbalance Load protection
Reverse power Protection.
U/V & O/V protection
Master trip relay
Restricted Earth fault relay along with 1600/1A PS class CT to be mounted on neutral of D.G. set
In addition to above relays shall be provided for the following protection:
Anti Pumping device
Trip circuit supervision relay
The ACB shall be complete with 3nos. 1600A/5A, 15VA, 5P10 CTs for protection .
Metering & Indication
1 set of R,Y,B phase indicating lamps with 3 nos. 2A SP MCBs.
1 No. Load Analyser cum digital Multifunction Meter with 3 nos. 1600/5A, CL-1 CTs, as required.
1 Set of Breaker ON-OFF-TRIP, Spring charged & Trip circuit healthy indication Lamps
1 set of Indication Lamps for NeutraI Isolation Contactor ON & OFF and Battery charger ON
BUS COUPLERs
1no.2000A FP EDO ACB (65KA) with all accessories required.
3 Sets of Breaker ON-OFF-TRIP, Spring charged indication Lamps as required.
INTERLOCKING
Incomers from D.G. sets & Bus couplers shall be electrically & mechanically interlocked.
The Interlocking scheme shall be such that Bus Bar shall be fed individually by only One D.G. sets under normal operation (No syncronisation) or all the bus bars shall be fed by any D.G.set in case of Synchronisation mode.
BUS BARs
2 Sets of 3200A, TPN Aluminum bus bars with colour coded PVC sleeves
OUTGOINGS
2nos.2500A FP EDO ACB
2 nos. 315A TPN MCCB
2 nos. 160A TPN MCCB
Microprocessor based PLC Synchronisation Panel
Design, manufacture, assembly, supply, Installation , Testing & Commissioning of PLC based Logic Control having follwing features:
Auto Synchronisation system.
Auto Load sharing among D.G. sets.
The automatic operations to be incorporated in the panel are as follows:-
The system will directly accept Digital meter & voltmeter signals for Electrical parameter monitoring and control. Only 1 no. Phase Angle Transducer shall be provided for all the DG Set Synchronization.
DG Panel’s logic shall be able to automatically start generators when mains supply fails by closing the DG switchgear for generator supply. It shall also transfer the power from emergency to mains supply, when the main healthy voltage persists for more than two minitues.
The Transfer of load shall take place only when the generator output reaches 90% of its rated voltage and frequency.
Automatic load transfer should take place within thirty seconds of mains fail.
‘B’ checkup alarm of each D.G. set after 300 hours of running for proper maintenance.
All parameters of individual D.G. set shall be monitored & necessary commands shall adjust the parameters of that D.G. Set feeding the bus bar of Main Panel.
Auto synchronizing system shall verify the phase angle of D.G. sets and also compensate for ACB closing time by initiating closing of the breaker ahead of the actual predictable synchronism thereby ensuring a phase difference of zero degree.
System shall also monitor the slip frequency and the beat voltage of the machine or system.
Neutral Isolation switch of Generator running in the system shall not trip until the Neutral Isolation switch of other Generator is closed in the event of shutting off of first Generator and starting the other.
Active power shall be made equal on all the sets automatically with the help of ACTIVE LOAD BALANCING system through Governor Control.
Reactive power shall be balanced automatically with the help of quadrature droop kit already fitted on the machine.
However if qudrature droop system is not functioning accurately ‘REACTIVE LOAD BALANCING’ system shall control the motorised potentiometer to achieve KVAR regulation within preset band.
In the event of set failing to synchronize, alarm from Annunciator would invite attention of operator for manual intervention.
It shall be possible to alter crucial setting / time delays through MAN MACHINE INTERFACE. (through BMS Software)
Relays shall have compatibility for future interface with BMS Software graphic displays / report generation.
System shall have TOTAL MANUAL synchronization facility.
The Microprocessor (PLC) shall start DG sets in sequence as per the readings of KW/KVA meter provided on transformer & D.G. set incomers at the instant of power failure and the sequence of operation will be as specified.
The PLC shall start the the two bigger set to fed the two bus of the Hospital feeders first and it will share the load of the other two bus if the total demand load on the two segement on each side of central Bus-coupler is below 90% of the capacity of the running D.G.set,by closing the smaller rating of bus-coupler.
The PLC system shall able to monitor the Load on the each Bus-section individually.
If the Total/ Individual demand Load on Bus-section increases from the 90% capacity of the running D.G. sets then the PLC will start the other D.G. sets one by one as per the Demand load requirement, and after sysnchronising with the system bus it will transfer the proportional load on the set by closing the Incomer of that set, and accordingly switch OFF the smaller D.G. sets as per the Demand Load on that Bus.
Similiary during the reduction of Demand load the Relay will switch OFF or Switch ON the relevant D.G.sets as per preset demand load.
On restoration of grid supply, Incomer Switches from D.G. sets and Bus coupler shall be switched ‘OFF’ in preset sequence and then switch ON the Incomer ACB of Transformer. DG Set shall continue to run for three minutes at reduced speed after DG Switch has been switched ‘OFF’ after that the D.G. set will be Switched Off.
The PLC panel shall be provided with all the necessary protection switches, relays, potential free contacts , Anuunciation windows, etc as required to achieve the above logic and complete with the following:
D.G. control Panel with Mannual synchronization for Each D.G. set with the following:
1 No. Digital Multifunction Meter
1 No. D.C. Voltmeter for Battery
1 No. D.C. Ammeter for Battery
Switch for Speed Raise & Low
Switch for Voltage Raise & Low
Push Button for D.G. Start
Push Button for D.G. Stop
Emergency Stop Push Button
16 windows Annunciator with hooter.
Field Failure Relay
Out of Step protection Relay
AMF Relay
3 nos. Potentiometers
AUTO SYNCHRONIZING
1 No. PLC Comprising of:
Main Processing unit
Power Monitor 3000.
Digital input Modules
Digital output Modules
EPROM for Main Processor
Panel view 550
1 No. Double Voltmeter
1 No. Double Frequency Meter
1 No. Synchroscope
1 No. Synchronizing Switch
1 Set Dark Lamps
Manual Overriding facility from Auto Synchronizing.
Auto / Manual / Test Switch
2 Nos. 16 windows Annunciator with hooter for status indicator for breakers.
Mimic with Led Indicator for Power supply Status
The PLC shall be complete with all necesaary switches, fuses etc. as given below, to fulfill the desired application as required.
Aux. Relays
Indicating Lights & Push Buttons
Control fuses/ MCBs
Load Analyser (Power monitor 3000)shall have following features: -
Voltage, current, frequency, P.F., KVA, KVAR, KW, KVAH, KVARH, KWH measurement for single and three phase source.
50 ms update rates for metering results
Port for PC compatibility
Output Control via control relays or PLC
Input monitoring via status inputs
Time stamped data logging of system measurements and events
Total Harmonic Distortion
Configurable trend log, upto 45,000 records
Firmware upgrades without removing module
Annunciation Window for each Generator as follows:
Electrical Fault
Excitation Failure
Reverse Power
Emergency Shutdown
Over Speed
Low Lube Oil Pressure
High Water Temperature
Engine Overheating
Cooling Water Flow Failure
Bearing Temperature High
Winding Temperature High
Low Fuel Level
Spare- 4nos.
Annunciation Window for Auto Synchronising
DG - 1 Fails to Start
DG - 1 Fails to Synchronize
DG - 1 Neutral Discrepancy
DG - 1 ACB Fails to close
DG - 2 Fails to Start
DG - 2 Fails to Synchronize
DG - 2 Neutral Discrepancy
DG - 2 ACB Fails to close
DG - 3 Fails to start
DG - 3 Fails to synchronize
DG - 3 Neutral discrepancy
DG - 3 ACB Fails to close
DG - 4 Fails to start
DG - 4 Fails to synchronize
DG - 4 Neutral discrepancy
DG - 4 ACB Fails to close
Bus coupler - Fails to close
Spare-3nos.
For Power Supply Status Indicator (Mimic)
DG - 1 Supply available
DG - 1 Neutral '‘ON/ OFF'
DG - 2 Supply available
DG - 2 Neutral '‘ON/ OFF'’
DG - 3 Supply available
DG - 3 Neutral ‘'ON/ OFF'’
DG - 4 Supply available
DG - 4 Neutral ‘'ON/ OFF'’
Bus coupler - ‘'ON/ OFF'’
Mains Supply available
All the above mentioned components like I/O ports, relay modules, synchronisation relay, annunciation window shall be housed in the Synchronisatio Panel.
The PLC control panel shall be complete in alll respect to accompolished the desired operation and the vendor shall supply all the necessary switches fuses, relays, CTs, Digital/ Analogue Input/Output racks for interface, 1 KVA UPS backup with SMF battery
Contractor shall provide the detail of NO & NC contacts required in the D.G.sets' control panel for AMF & Auto-synchronisation proccess which will be provided alongwith the motorised potentio-meter with the D.G.set within the accoustic enclosure.
Supply Installation, testing & Commissioning for the above Panel-1. as described above MAKE:- TRICOLITE, ADLEC, ADVANCE PANLES & SWITCHGEAR (P) LTD., SIMON FABRICATOR JAMMU, Electricfield
DG Auxillary Panel -1
INCOMER
2Nos. 315A TPN MCCB (35 KA)
METERING & INDICATION
2 sets of R,Y,B phase indicating lamps
2 No. (0-500V) Voltmeter with Built-in VSS each with 3 nos. 2A SP MCB
2 No. (0-250A) Ammeter each with ASS with 3 nos. 250/5A CT's
BUS-BAR
2 Set of 250A TPN Aluminium Bus Bar with colour coded PVC Sleeves
BUS COUPLER:
1 No. 250A TPN MCCB (35KA)
INTERLOCKING
Incomers for L.T. Panel & Bus coupler shall be electrically & mechanically interlocked.
OUTGOINGS
2 Nos. 80A TP MCCB (45 KA)
4 Nos. 63A TP MCCB (45 KA)
5 Nos. 40A TP MCCB (45 KA)
6 Nos. 10A / 32A TP MCB (10 KA)
4 Nos. 10A / 32A DP MCB (10 KA)
5 Nos. S/D starter with self illuminated Push button for ON & OFF and suitable rating of contactor and O/L relays, suitable for 10 HP Motor.
4 No. DOL starter with self illuminated Push button for ON & OFF and suitable rating of contactor and O/L relays, suitable for 7.5 HP Motor.
2 No. space for S/D starter with self illuminated Push button for ON & OFF.
Connector Block/Strip of suitable no.of pairs complete with wiring upto all Starters, for interlocking the pumps & Cooling tower's fan with individual D.G.set.
INTERLOCKING
The starters shall automatically start the CT Pumps and fans with their respective DG Sets
Supply Receiving, fixing, testing & commissioning of of D.G Auxillary Panel as described above MAKE:- TRICOLITE, ADLEC, ADVANCE PANLES & SWITCHGEAR (P) LTD., SIMON FABRICATOR JAMMU, Electricfield
SANDWICH TYPE BUS TRUNKING
Design, supply, installation, testing and commisioning of following ratings of powder coated sheet steel enclosed (IP 42) 415V, 50 Hz., Three phase & neutral Aluminium conductor Bus Duct suitable for 25 MVA fault rating, including bends/elbows, transposition piece, expansion joint, Terminal End connector & all flexible connections as per specifications with all accessories, supports, hardwares and termination of bus duct to switchgear.
800/1000A TPN Aluminium Bus Duct (35 MVA fault rating) in weather proof Enclosure
2000A TPN Aluminium Bus Duct (35 MVA fault rating) in weather proof Enclosure
2500A TPN Aluminium Bus Duct (35 MVA fault rating) in weather proof Enclosure
Copper flexible End Termination for 800/1000A TPN
Copper flexible End Termination for 2000/2500A TPN
Rabina Enterprises Pvt Ltd
KEC International Limited
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Tendernotice_1.pdf
PDF • 0.42 MB
BOQ_305846.xls
BOQ • 1.91 MB
NewSBDFinal.pdf
Tender Documents • 1.02 MB
SITEPLAN.pdf
Additional Documents • 0.19 MB
D1.pdf
Additional Documents • 2.52 MB
D2.pdf
Additional Documents • 2.00 MB
Conditions.pdf
Additional Documents • 0.21 MB
Electrical.pdf
Other Document • 0.26 MB
Download all tender documents and submit your bid