Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.3 LAccepted-AOC | L1 | Accepted-AOC L1 Bidder | |
| 2 | L2₹6.6 L+₹22,855 (3.57%)Rejected-Finance BINDODPUR KALIBARI KATIHAR 854105 BIHAR | KATIHAR | KATIHAR | BIHAR | 854105 | L2 | Rejected-Finance Higher bid value | |
| 3 | L3₹6.7 L+₹29,960 (4.69%)Rejected-Finance | L3 | Rejected-Finance Higher bid value |
Tender Value
₹6 L
EMD Value
₹12,000
Closing Date
8 Jun 2020, 6:00 pmClosed
AGE (I) (AF) PURNEA
AGE (I) (AF) PURNEA,CHUNAPUR,PURNEA
REPAIR/REPLACEMENT OF LT FEEDER PILLAR BOX,PANEL BOARDS AND CONNECTED WORKS AT MOUZA DALAN AND SIRSA CAMP AT ARMY STATION KATIHAR UNDER AGE (I) (AF) PURNEA
2020_MES_344112_1
C/8846/E8
Open Tender
Civil Works
Item Rate
180 days
AGE (I) (AF) PURNEA
AS PER NIT
7 documents required · 7 mandatory
₹500
AGE I AF PURNEA
₹12,000
Yes
25 Jun 2020
12 May 2020
13 Jun 2020
12 May 2020
8 Jun 2020
26 May 2020
Amount
Excavation in trenches n.exc 1.5 mtr wide & n.exc 1.5 m depth in soft /loose soil & getting out for laying of LT cable all as specified & directed by Engr- in Charge.
M&L Returning filling including spreading, levelling, watering & well ramming in layers n.exc 25 cm in soft /loose soil complete all as specified & directed by Engr -in - Charge .
Removing excavated spoil n.exc 50 m & depositing where directed at a level n.exc 1.5 m above the starting point complete all as specified & directed by Engr - in Charge.
M & L Sand covering /cushioning for underground cable protection complete all as specified and directed by Engr- in Charge.
M&L for burnt bricks sub class 'B' laid perpendicular over & cushioning for cable protectioncomplete all as specified & directed at site by the Engr- in Charge.
Relaying of old bricks obtained from existing trenches for protection of UG LT cable all as specified & directed by Engr- in -Charge.
Taking out old unserviceable LT cables of any sizes & type from the trenches or pipe etc and deposited all as specified & directed by Engr- in - Charge.
M & L for connecting and testing of XLPE insulated, armoured heavy duty electric cable with aluminum conductor ,1100 V grade,cross-sectional area 50 Sqmm and 3.5 core laid in trenches including aluminium lugs as required for connection complete all as specified and directed by Engr- in - Charge.
M&L for laying XLPE insulated, screened, PVC bedded, galvanised steel strip or wire, armoured, heavy duty electric power cable with aluminium conductor, 1100 volt grade of cross sectional area 25 Sqmm, 3 ½ core after taking down old unserviceable cable from any position.
Taking down old U/S LT panel board/ feeder piller box after disconnecting LT cables from existing panel and making good disturded surface ground complete all as spaecified & directed by Engr- in -Charge.
M&L for painting of LT Panal board externally & Internally with two coat of super quality synthetic eneamel paint as per existing colour over a coat of red oxide by spraying includng preparation of painted surfaces to remove all dust/ oil marks etc after disconnecting the electric supply from LT panel and write with red colour paint of following alll as specified & directed by the Engr- in -charge.
Material & Labour only for taking out LT Panal board by disconnecting its all incoming and outgoing cables from MCCBs from its position by breaking of PCC and fixing the same on another or same postion by Making PCC of Type(1:3:6) Type C2 of 1 m height from ground level to save feeder piller from water logging during rainy season and making connection of its all outgoing and incoming cables complete as directed by Engr-in-charge.
S & F cable route indicator (blue in colour) for LT UG cable of 1100 volts made out from cast iron plate 80 mm dia, bolted with 40 x 5 m flat iron of height 0.30 mtr embaded in PCC (1:3:6) type C2 (using 40 mm graded aggregate) of size 200 x 200 x 200 mm block, including taking down old unserviceable one, complete all as specified and directed.
M&L Straight Through (Epoxy) Cable Joint Kit including Jointing Materials for making Joints of UG Electric Cable 1100 Volt Grade Heavy Duty with PVC/XLPE insulated Aluminium Stranded Conductor, Nominal Cross-Sectional area 50 sqmm, 3½ Core and Testing complete all as specified and as directed.
All as per item no 18 above but Nominal Cross-Sectional area 70 Sqmm , 3½ Core and Testing complete all as specified and as directed.
All as per item no 18 above but of Nominal Cross-Sectional area 120 Sqmm 3½ Core and Testing complete all as specified and as directed.
S&F in replacement MCCB 200 Amp 36 KA 4 poles 415 volts including connecting testing with existing cables complete all as directed by Engr- in-Charge.
S&F in replacement MCCB 100 Amp 25 KA 4 poles 415 volts including connecting testing with existing cables complete all as directed by Engr- in-Charge.
S&F in replacement MCCB 63 Amp 25 KA 4 poles 415 volts including connecting testing with existing cables complete all as directed by Engr- in-Charge. Note:-The contract sum shall be arrieved at after deducting amount of schedule of credit from the total quated amount.
M/S. R.D. Construction
M/s. Rakesh Roshan
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .