Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.8 LAccepted-Finance RUDRANAGAR P S SAGAR 24 PARGANAS SOUTH | L1 | Accepted-Finance Lowest Bidder | |
| 2 | L2₹7.0 L+₹21,335 (3.14%)Rejected-Finance | L2 | Rejected-Finance Higher Bid | |
| 3 | L3₹7.5 L+₹74,775 (11.0%)Rejected-Finance NARAN PALLY PURBO BARDHAMAN PIN 713 101 | PURBA BARDHAMAN | WEST BENGAL | 713101 | L3 | Rejected-Finance Higher Bid | |
| 4 | L4₹8.1 L+₹1.3 L (19.6%)Rejected-Finance | L4 | Rejected-Finance Higher Bid | |
| 5 | L5₹8.2 L+₹1.4 L (20.1%)Rejected-Finance 3 C DR JAGABANDHU LANE KOLKATA 700012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | L5 | Rejected-Finance Higher Bid |
Tender Value
Refer Docs
EMD Value
₹17,965
Closing Date
31 Mar 2025, 1:00 pmClosed
EE, South 24 Pgs Elect Divn
57/2, Diamond Harbour Road, Kolkata - 700 023
Compound illumination in the Campus of west Bengal University of Animal and Fishery Sciences at Chakgaria, District of South 24 Parganas
2025_WBPWD_827978_1
WBPWD/EE/S24PED/eNIT128/24-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
University of Animal and Fishery Sciences at Chakg
Please refer Tender documents.
4 documents required · 4 mandatory
₹17,965
South 24 Parganas Electrical Division
22 Apr 2025
17 Mar 2025
2 Apr 2025
17 Mar 2025
31 Mar 2025
25 Mar 2025
24 Mar 2025
Amount
Supply & delivery of 7.0 Mtr Hot Dip Galvanized (86-65 micron dry film thickness) Octagonal Pole, as per BSEN 10025; ASTM A572; IS 5986: IS 4759/2629, ASTM A123 and BSEN IS 1461 standard. The pole should be 7.0 Mtr long, bottom dia-130 mm, top dia-70 mm, thickness-4 mm (without galvanosation), continuously tapered and shall have octagonal cross section with pole cap at top, necessary cleat attachment/hanger for arm brackets. Base-plate having dimension 200x200x12 mm and 4 nos 'J' Type foundation bolt with double nut and plate washer, bolt dia 24 mm, bolt length-700 mm, Projected bolt length - 100 mm(these dimention are subjected to tolerance as per IS-2102 except for bending radius). The pole will consist of a built-in loop-box having one number 32 A, 3 Phase 3 Way connector with Neutral link on porcelain insulator (for incoming/outgoingcable and luminaries connection), and 1 numbers (6-32 A) SPMCB. The door opening shall be complete with a closefitting, vandal resistance, weatherproof door (to IP-55 of IS:2147), providing with a heavy duty double internal lock with special paddle key. The door opening shall be carefully designed and reinforced with welded steel section, so that the mast section at the base shall be unaffected and undue buckling of the cut portion is prevented. The Pole should be supplied with adequate templates for the purpose of construction of base foundation. The pole should have earthing terminals 02(two) nos at a height of 600 mm from the base plate for connection of earth continuity wires/ conductors. (Make:- Transrail/ Valmont/ Bajaj/Utkarsh as per choice of EIC)
Erection of upto 7.0 Mtr octagonal GI (Hot Dip Galvanised in single dip) pole 1.6 Km from the store to work-site with foundation of M20 grade concrete for 7.0 Mtr GI Octagonal Pole with all the materials like sand, cement, stone chips, reinforcement steel, binding wire etc as relavent IS Code. soil bearing capacity at site as 10 T/sqmtr., by PCC Base foundation having (L-1000mm x W 1000mm x H-100mm) & RCC foundation having dimention [L-500mm x W- 500mm x (H-1200mm-below the GL & 200mm-above the GL)] including neatly cemented finish (3mm thick) above ground level. There should be multiple alkathene pipes upto 1.2 mtrs of 50 mm dia of adequate length for distribution of incoming & outgoing cables for street light wiring as directed by EIC in the CC foundation of octagonal poles.
S&F 40NB (as per IS 1161) Class 'B' pipe 1.5 mtr. long detachable type G.I. Single arm bracket, suitable for pole head. The arm bracket shall be properly welded with 4 mm. thick stifner plate of pole sleeve for strengthening incl. properly fixing arrangement with the pole by bolts, nuts and washer as per direction of EIC. (86-65 micron dry film thickness) (Make:- Transrail/ Valmont/ Bajaj/Utkarsh as per choice of EIC) (As per IS 5986: IS 4759/2629, ASTM A123 and BSEN IS 1461 standard.
S&F 40NB (as per IS 1161) Class 'B' pipe 1.5 mtr. long detachable type G.I. Double arm bracket, suitable for pole head. The arm bracket shall be properly welded with 4 mm. thick stifner plate of pole sleeve for strengthening incl. properly fixing arrangement with the pole by bolts, nuts and washer as per direction of EIC. (86-65 micron dry film thickness) (Make:- Transrail/ Valmont/ Bajaj/Utkarsh as per choice of EIC) (As per IS 5986: IS 4759/2629, ASTM A123 and BSEN IS 1461 standard.
Supplying and Drawing 1.1 kV three core stranded 'FR' PVC insulated & unsheathed 1.5 sqmm copper cable (Make - Polycab / Havells / RR Kabel / Finolex)
S & D of 240V, 10800 Lumens (minimum) LED Street Light Fittings with IP 66/ 67, IK 10 protection including 10 KV SPD with CCT 5700K & Luminious efficacy 120Lumen/Watt minimum or better, burning hour 100000 at L70850, LED Driver should with stand 415V for 8 hours Inbuilt surge protection 4 KV and 10 KV Surge protection inside lumunaries. The LED luminaires and accessories shall have BEE Certification & LED should be with lens (Light efficacy will not get depriciated less than equal to 70% of the rated value over the lifetime of the Luminaries) (Make: Havells/ Philips(Signify) / WIPRO/ Crompton) (Manufacturer warranty should not less than 3 years).
S & D of 240V, 8400 Lumens (minimum) LED Street Light Fittings with IP 66/ 67, IK 10 protection including 10 KV SPD with CCT 5700K & Luminious efficacy 120Lumen/Watt minimum or better, burning hour 100000 at L70850, LED Driver should with stand 440V for 8 hours Inbuilt surge protection 4 KV and 10 KV Surge protection inside lumunaries. The LED luminaires and accessories shall have BEE Certification & LED should be with lens (Light efficacy will not get depriciated less than equal to 70% of the rated value over the lifetime of the Luminaries) (Make: Philips(Signify) / WIPRO/ Crompton) (Manufacturer warranty should not less than 3 years) on existing minipole with replacecing the old one,.
Fixing only outdoor / street light type fluorescent light fitting complete with all accessories to be fixed/projected from the wall of the building incl. making holes to building, S&F 40 mm dia GI pipe (ISI-Medium) 1.50 mts. average length, with GI socket at one end and thread at the other end & suitable bend to house the fitting & making necy. connections with S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall and painting
SUPPLY & LAYING OF CABLES, Loop box
Supply of 1.1 KV grade 2/4 Core XLPE/PVC Insulated & Sheathed Armoured Aluminium Conductor cables of following sizes [Make : Gloster/Polycab/havells/RR kabel] a) 2 Core 6 Sqmm
Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting
i) 2 Core 6 Sqmm
Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed.
i) 2 Core 6 Sq.mm
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/ PVC armoured cables as below as to GS.
i) 2 Core 6 Sqmm
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. S&F solderless socket etc as per GS.
i) 2 Core 6 Sqmm
Supplying & fixing medium gauge GI Pipe (ISI-Medium) Protection with necessary fittings and jointing metarials as required. 32 mm
Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint.
EARTHING:
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level By ISI-Medium GI pipe.
Excavation of soil for installation of Earth Electrode and filling & ramming. For Soft Soil
Connecting the equipments to earth busbar including S&F GI (Hot Dip) wire of size 8 SWG on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages
Connecting the equipments body to earth busbar including S&F 20 mm x 3 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc.
S&F of 230 V.,150 wattage LED outdoor type Flood light fitting, made up of pressure die cast aluminium housing with toughened glass and high power LED's with secondary lenses, of following specifications with 5 years warrenty. i. IP66 protection ii. 10 KV SPD included iii. Efficacy ≥110/120 LPW. iv. CCT - 5500-6000 K.(Philips/CG/Wipro or Havells-JETALEGANZAFLS150WLED730P60DTOTG)
Supplying and fixing MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment - 4 Way
Supplying and fixing 415 V 32A FP MCB Isolator on din rail of existing DBs and necessary connection.
S&F of 250V double door AC Timer DB [equivalent of 2+8 way SPNDB] with sheet steel enclosure, pnosphitised powder coated neutral bar, DIN rail with IP-43 potection comprising with 1 no. 25A DPMCBIsolator, 2 no. 16A SPMCB ('C' curve 10KA), 1no. Programmable Digital time switch-24 hrs with minimum switching of 15 minutes, and 1 no. 18A/25A 2-Pole power contractor with inner-outer plate & internal wiring by suitable size of cu. wire incl. 1 no. Auto-Manual bypass toggle switch and provision for earthing attachment, incl. LED indication light for running condition with mechanical locking arrangement, as directed by EIC.. [Compound Light] [Make-ABB/L&T/Crabtree]
Note: 1) All the above rates should be quoted inclusive of all taxes, duties and all ancilery charges with cost of maintenance, servicing, supply & replacement of spares for 1 (One) year from the date of commissioning. 2) Total is rounded off to the nearest rupees.
BHARAT INFOCOM (BID ID -6274543)
SREE GURU ENGINEERING (BID ID -6272361)
DEBNATH ENGINEERING WORKS (BID ID -6273832)
S. A. ENTERPRISE (BID ID -6283565)
ELECTROMAX (BID ID -6278322)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .