Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
14 Aug 2026, 3:00 pmClosed
Admn Officer Store and Purchase
Aruna Asaf Ali Marg, Post Box No. 10502, New Delhi
Dismantle safe disposal of the existing 02 nos of Cooling Towers and SITC of MS piping Electricals
2026_IUAC_845977_1
Dismantle safe disposal of 2 No Cooling Towers
Open Tender
Miscellaneous Works
Works
180 days
IUAC
AS per Enquiry
2 documents required · 2 mandatory
₹10
Yes
IUAC, New Delhi
₹30,000
Yes
24 Jul 2026
24 Jul 2026
14 Aug 2026
25 Jul 2026
14 Aug 2026
25 Jul 2026
25 Jul 2026 - 31 Jul 2026
Foundation made of RCC pillars / beams of suitable size and number (Cooling tower will be installed at 3 ft high from water tank roof level) suitable for Cooling Tower as per Manufacturer's design. M.S. Tor Bar Jaal, 150 mm grid made of 8 mm minimum dia M.S. tor bars, made with water proof cement: sand: concrete mixture 1:1.5:3, properly leveled and 12.5 mm thick plastered with water proofing cement. Duly painted with water proofing paint.
Steel C- Channel base, Heavy Duty Hot Deep Galvanized Steel, Size-200x75x8 mm, bottom flange shall be grouted on RCC beams with 5/8” Dia bolts, Top flange shall be bolted to Cooling tower bottom ends. Intermittent support grid of 750 mm of L- Section-50x50x6 mm shall be provided including one coat of epoxy primer and two coats of Grey Shade epoxy paint. Suitable for item no. 1.01
Local on / off push button control of cooling tower fan motor on cooling tower for each tower including weather proof (IP55) FRP / PVC box and controls. Cable as per item rate -1.14.1.
MS Pipe, ERW, Black, Heavy Class, 6.35 mm thick, IS 3589 including fittings like tee, bends, reducers, necessary clamps, vibration isolators but excluding valves, strainers, gauges, flanges and welding of all joints as per specifications and as required of following sizes:8" NB Size
M.S. Flanges, rating – 150 lbs, ANSI B16.5, RF-serrated type including gaskets, bolts, nuts & washers etc. as required as following: 8" NB Size
Butter fly Valve shall be as per IS 13095:2020 with CI body, SS-304 disc (CF8), Black Nitrile Liner, AISI 410 shaft, lever operator and PN -16 pressure rating.8" NB Size
Bituminous wrap of 3 mm thick conforming to IS: 10221 over the pipe for the following sizes: 8” NB Size
Anti corrosive Painting: Exposed metal surface of pipes must be applied with one coat of red-oxide primer & two coats of PU enamel paint of Approved shade. 8” NB Size
Wall Mounting Pipeline Support:Including MS-C-section (75 mmx 40mm x 4.5mm), U-Clamps of 8 mm diameter, Anchor fasteners (nut, bolt and washer), Rubber padding of 3 mm thick and Painting (one coat primer + two coat synthetic enamel) etc.
Star-Delta starters of suitable capacity and number suitable for the quoted cooling towers fans (2 no. of 20 HP) with MCCB, contactors, timer, O/L relay, single phase preventor, On-Off indications, push buttons, VAF Meters etc complete as required.To be replaced into the existing cubical after dismantle of old parts.
Industrial Glass Thermometer, Range 0-50 Deg C, Size- 3/4” BSPT, M.S. Long Threaded Heavy-Duty Socket welded on pipe, long heavy-duty bellow made from brass bar.
Power Cable XLPE insulated PVC sheathed, steel / wire armoured, cables of following sizes forelectric from supply main panel to various loads including interconnections from starters to motors on suitable cable trays /supports, including suitable double compression glands, Terminal lugs, connections etc. as per specifications as required:3 core x 16 sq mm aluminium conductor, 1.1 kV rating for cooling towers (specifications as above) in existing cable tray
Power Cable XLPE insulated PVC sheathed, steel / wire armoured, cables of following sizes forelectric from supply main panel to various loads including interconnections from starters to motors on suitable cable trays /supports, including suitable double compression glands, Terminal lugs, connections etc. as per specifications as required:4 core x 1.5 sq mm copper conductor, 1.1 kV in existing cable tray (specifications as above)
Dismantle of old cooling tower of 300 TR each including foundation, electrical connections, piping disconnections etc.
Dismantle of old M.S. Pipe of 8” NB.
Demolishing cement Nominal concrete 1:4:8 or leaner mix (i/c equivalent design mix concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - In - charge.
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means of any width & dimension etc. including getting out, back filled & disposal of surplus earth lead upto 200 m & lift upto 1.5 m, as directed by Engineer- In-charge
Re-filling available excavated earth , boulders/stones, concrete debris (excluding rock ,laying within range of 400 mtr ) below plinth, , the concrete floor ,C.C pavements etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering.
Providing and laying in position cement concrete of 1:2:4 (1 Cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 40 mm nominal size)grade.
Brick work with common burnt clay F.P.S (nonmodular) bricks of class designation 7.5 in foundation and plinth in:Cement mortar 1.4 (1 cement : 4 coarse sand)
Discount offered for the buyback of scrapped 8” NB M.S. Pipeline and disposal of same out of IUAC campus.
Discount offered for the buyback of 2 nos of scrapped old cooling towers of 300 TR (each) Heat Rejection capacity on as is where is basis up-to the nearest pipe flanges of cooling towers, motor termination points etc. and disposal of all the scrap out of IUAC campus.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.40 MB
BOQtoIndentNo469SSKS.xls
Tender Documents • 0.08 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .