MANNING AND OPERATION OF 11KV SUB STATION AND ALLIED WORKS AT NAMS.
2021_MES_447259_1
GE NAMS - 09 / 21 - 22
Open Tender
Electrical and Maintenance Works
Item Rate
335 days
NAMS CANTT
Class D
Category d v
6 documents required · 6 mandatory
₹500
Yes
GE NAMS
₹80,000
Yes
28 Aug 2021
1 Jun 2021
2 Jul 2021
1 Jun 2021
1 Jul 2021
19 Jun 2021
Amount
Testing of 11KV breaker through Power Grid Corporation of India , through PSEB Protection team are as under:- ( Kathania MAP Ph II) (a) Tests to be carried out on each breaker ( Five in Kathania II)
Testing of 11KV breaker through Power Grid Corporation of India , through PSEB Protection team are as under:- (Khterpal MAP Ph II ) (a) Tests to be carried out on each breaker (Nos of Breaker - Nine in Khetrapal II)
Testing of 11KV breaker through Power Grid Corporation of India , through PSEB Protection team are as under:- (NOC MAP Ph II ) (a) Tests to be carried out on each breaker ( Nos of Breaker - Three in NOC II )
Testing of 11KV breaker through Power Grid Corporation of India , through PSEB Protection team are as under:- (NME MAP Ph II) (a)Tests to be carried out on each breaker ( Nos of Breaker - One in NME Ph II) The following tests are carried out Srl No 1 to 5 (i) IR Value for open (ii) Tripping and closing time in M/S. (iii) Operation - both manual and through motor. (iv) Functioning of indicators.(v) Continuity.(vi) CT ration through primary injection.(vii) Polarity test. (viii) Testing of all the protection relay - i.e. o/c, earth fault, instantaneous, trip suspension, auxiliary relay etc.(ix) Operation /working of charging motor and limit switch.(x) Calibration of all relay, male, female contracts of VCB. Note : (i) Any part/spare found defective during testing shall be repaired/ replaced for which payment shall be made separately against respective items here in after except for minor parts such as packing, nuts bolts, cotton waste etc for which cost shall be deemed to be included in the unit rate quoted for this item. (ii) Test sheet shall be prepared and produced to Engr-In-Charge. (iii) T&P/Power back up/DC Supply required for testing shall be provided by the contractor.
Manning and operation of 11 KV Sub Stn located MAP PH -II Ketrapal MD Accn in three shifts comprising of the following assests :-
A' 11 KV Assests and connected accessories :-
(i) 11KV, Indoor VCB Panel- 09 Nos
(ii) ACB Panel- 01 Nos
(iii) Transformer 11 KV/0.433 KVA 315 KVA – 03 Nos. and 400KVA -01 No.
(iv) Bty bank - 01 Set
(v) Bty charging panel - 01 Set
(vi) Gen Set 100 KVA with AMF panel -01 Nos
(vii) Capacitor bank 01Nos
(viii)Outdoor feeder pillar - 8 Nos.
B Operating staff to be deployed :-
(i) Electrician HS/Sub Station Attendant - One persons per shift in 3 shifts having ITI in electrical engineering or any retired Sub Stn Attendant of any state electricity department conversant with such job .
(a) Period of one shift - 8 Hours.
(b) No of shifts to be deployed per day - 03.
Manning and operation of 11 KV Sub Stn located MAP PH -II Khatania MD Accn in three shifts comprising of the following assests :-
A 11 KV Assests and connected accessories :-
(i) 11KV, Indoor VCB Panel- 05 Nos
(ii) ACB Panel- 01 Nos
(iii) Transformer 11 KV/0.433 KVA 315 KVA – 01 No. and 400 KVA -01 No.
(iv) Bty bank - 01 Set
(v) Bty charging panel - 01 Set
(vi) Gen Set 100 KVA with AMF panel -01 Nos
(vii) Capacitor bank 01Nos
(viii)Outdoor feeder pillar - 3 Nos.
B Operating staff to be deployed :-
(i) Electrician HS/Sub Station Attendant - One persons per shift in remaining 3 shifts having ITI in electrical engineering or any retired Sub Stn Attendant of any state electricity department conversant with such job and educated qualification not less than ITI from the recognised institutes.
(a) Period of one shift - 8 Hours.
(b) No of shifts to be deployed per day - 03.
Manning and operation of 11 KV Sub Stn located MAP PH -II RED COLONY MD Accn in three shifts comprising of the following assests :-
A' 11 KV Assests and connected accessories :-
(i) 11KV, Indoor VCB Panel- 05 Nos
(ii) ACB Panel- 01 Nos
(iii) Transformer 11 KV/0.433 KVA 315 KVA – 01 No. and 400 KVA-01
(iv) Bty bank - 01 Set
(v) Bty charging panel - 01 Set
(vi) Gen Set 100 KVA with AMF panel -01 Nos
(vii) Capacitor bank 01Nos
(viii)Outdoor feeder pillar - 3 Nos.
B Operating staff to be deployed :-
(i) Electrician HS/Sub Station Attendant - One persons per shift in 2 shifts having ITI in electrical engineering any retired Sub Stn Attendant of any state electricity department conversant with such job and educated qualification not less than ITI from the recognised institutes.
(a) Period of one shift - 8 Hours.
(b) No of shifts to be deployed per day - 03.
(C ) Nature of Duties of operation staff
(i) Sub Station attendant / Electrician have to operate and maintain all the assets listed under item No. 6.01 A,7.01A & 8.01A here in before.
(ii) Maintaning and recording of the records of all the Instruments all as directed by Engineer-in-Charge and register/log sheet will be provided by contractors.
(iii) Monitoring of periodical functioning of the instruments listed in Sub Station standing order/particular splecifications as per laid down periodically.
(iv)Recording daily break down /shut down in the log sheet other than reading such as trip record, breakdown its duration, preparing permit slip etc.
(v) Carrying out necessary periodical test of earthing of complete Grid quarterly and recording it on test sheet.
(vi)Testing of DC batteries healthiness, checking of gravity of batteries, functioning of battery bank replacement of worn-out fuses, weekly and making the test/record sheet.
(vii) Testing, cleaning, checking of bty terminal, Ammeter, voltmeter periodically and maintain log book for running of Gen Set of capacity100 KVA.
The sub station attendant / electrician for taking out trolleys of switch gears etc, recording the reading of instruments, watch and ward for complete assets installed with in the premises of the installation and daily cleaning of the installed machinery of installation and complete area of Sub Station.
The contractor will ensure that the area within the boundary wall /fencing of the sub stn remains foliage free/grass free.
Existing foliage / grass will be uprooted by machinery / maually as per the requirement and safety of cables.
whereas fencing / boundary wall does not exist, surrounding area 10m on all sides from sub station wall will be cleaned/mainted as mentioned in sub clause 8.25
(D) PROTECTIVE CLOTHING/UNIFORM/TOOLS :- The duty SBA/Electrician shall wear uniform as approved by the GE/ Engineer-in-Charge. The tools kit consisting of Insulating plier, screw drivers, DE Spanner set shall always be in possission of the duty SBA. The uniform and tool kit shall be arranged by the contractor. SBA /Elect will not be attand to enter the sub stn without protective clothings.
(E) Duty Roster. Necessary duty roster shall be prepared by the contractor every months and approved by JE&Engineer-in-Charge monthly.
(F) One mobile set to be provided at 11 KV Sub Stn permanently for communication by contractor without extra cost.
(G) Payment of wages : The Garrison Engineer is the principal employer as such payment to contractor staff deployed shall be made not less than minimun wages as per govt policy. Payment to staff deployed to made through e-payment i.e. aadhar linked bank account & evidence to be produced as directed.
(H) The necessary Furnitures like table Chair and other writing materials (incl log book) will be provided by the contractor by him self without any extra charges all the rates are incl in the quoted rate only.
(J) Penal Charges. The fwg panel charges are charged as under:-
(i) Absent of duty attandent. Recovery @ Rs. 1000/- per day per shift for Electrician.
(iii)Not carring out the periodical test as per periodicity, recovery @ Rs. 5000/- Per month lump sum.
(iv) Non cleaning of the area recovery @ Rs. 5000/-per month
Earthing complete with galvanised steel earth plate with electrode 60mmx60cmx6 mm thick buried directly in ground.(earth pit of size not less than 2.25 mtr. Deep below normal ground level) with top edge of plate not less than 1.5 mtr. Below normal ground level, connecting to the galvanized iron strip earth lead 32x6mm size, by means of bolt,nuts,checknuts and washers of galvanised iron and 32x6mm earth lead protected by provision of GI light grade pipe 40mm bore including provision of concreate pit in PCC(1:2:4) type B-1 using 20mm graded stone aggregates with 40mm thick cover of RCC(1:2:4) reinforced with XPM(weight not less than 4kg/Sqm) with 6mm dia Ms bar handle made to shape.Complete all to as shown in electrical plate No 3 of MES Sch 2009 (Part-I) connected main switch board all as specified and testing on completion.
(a) Earth electrode as mentioned above
(b) Main earthing lead of 32X6 mm GI strip from earth electrode to test point up to 7.5 mtrs.
(c) Connecting earthing lead and electrode all as specified and testing complete.
(d) Adequate quantity of charcoal and salt .
(e) GI protection pipe of 40 mm dia light grade of length not more than 5.00 mtrs.
(f) PCC pit all as per SSR with RCC cover.
M &L Earthing complete with galvanised steel earth plate with electrode 60mmx60cmx6 mm thick buried directly in ground.(earth pit of size not less than 2.25 mtr. Deep below normal ground level) with top edge of plate not less than 1.5 mtr. Below normal ground level, connecting to the galvanized iron wire 4 mm dia (as earth lead wire), by means of bolt,nuts,checknuts and washers of galvanised iron and 32x6mm earth lead protected by provision of GI light grade pipe 40mm bore including provision of concreate pit in PCC(1:2:4) type B-1 using 20mm graded stone aggregates with 40mm thick cover of RCC(1:2:4) reinforced with 6mm dia Ms bar handle made to shape.Complete all to as shown in electrical plate No 3 of MES Sch 2009 (Part-I) connected main switch board all as specified and testing on completion.
(a) Earth electrode as mentioned above
(b) Main earthing lead of 4 mm dia GI wire from earth electrode to test point up to 7.5 mtrs.
(c) Connecting earthing lead and electrode all as specified and testing complete.
(d) Adequate quantity of charcoal and salt .
(e) GI protection pipe of 40 mm dia light grade of length not more than 5.00 mtrs.
(f) PCC pit all as per SSR with RCC cover.
Material and labour for PCC 1:4:8 type D-2 using 40mm graded broken stone aggregate as in mass concrete in foundation of poles complete all as soecified.
Material & labour for cleaning away all grass vegetation, scapling shrubs bushes under grouth roots and trees not exceding 30 cm grith and removing rubbish upto distance of 50 mtr out the periphery of area under cleaness, existing foliage / grass will be uprooted by machinery / maually as per the requirement and safety of cables complete all as specified and directed.
Material & labour for cleaning of Power House surrounding (Loc NME & NOC MAP Ph II)11 months within the boundary wall /fencing of the sub stn remains foliage free/grass free. Existing foliage / grass will be uprooted by machinery / maually as per the requirement and safety of cables.whereas fencing / boundary wall does not exist, surrounding area 10m on all sides from sub station wall will be cleaned/mainted as mentioned as above.Removing rubbish upto distance of 50 mtr out the periphery of area under cleaness including internal cleaning complete all as specified and directed. Penal Charges:- Non cleaning of the area recovery @ Rs. 2000/-per month. Note :- Cleaning of each power house ie NME or NOC as pr this item will be treated as one Job.
Supply and fixing in replacment danger notice plate of 1.6mm thick mild steel sheet , virtreous enameld white, with letters , figures and conventional skull and bones in signal red colour and fixed with MS clamps , bolt and nuts of approved size for LT 20 X 15 CM size complete all as specified and directed.
Ditto all as per items No 14 but for HT of size 25 x 20CM
Supply & Fix in replacement flood Light Luminaire 120 watt with .high power SMD LED cool white, supply voltage 220/240/50 Hz, light engine driver base.pole adapter,pressure die cast polycarbonate,powder coated in IP 66 Including protection over temperature complete all as specified.
Supply & Fix in replacement flood Light Luminaire 150 watt with .high power SMD LED cool white, supply voltage 220/240/50 Hz, light engine driver base.pole adapter,pressure die cast polycarbonate,powder coated in IP 66 Including protection over temperature complete all as specified.
Supply & fixing in replacement of lighting arrestor metal oxide type gap less hreavy duty single pole suitable for rated system voltage 12 KV and working rated 9 KV normal discharge complete all as specified.
S&F DC Power back min 2Hrs battery backup 24V DC including charging equipment suitable for 11KV 800Amp VCB operting system complete all as specified .
supply and fixing in replacement of ACB 800Amp gear box with tripping gear machanisam including all minor parts for repair of the ACB complete all as specified directed
M & L in replacement of out door type aluminuam bus bar chamber feeder box of cap 300 Amp , 3 phase, 4 wire, 415 Volts with porcelain insulator of size 90 x 60 x 45 cm made out of 3.15 mm CRCA Sheet duly painted with two coats of synthetic enameld paint over a red oxide primer and fixed and supported with anlge iron grouted in PCC 1:2:4 upto 0.30 mtr high from ground level all as directed by Engr-In-Charge.
Material and Labour in replacement straight through joint/End temination kit of heats shrinkable outdoor type suitable for 185 sqmm HT 3 core 11000 volts XLPE cable type complete all as specified and directed.
Supply and fixing in replacement of male female contacts of gang operative switch made out of brass and rated capacity 200 amps ,make matching with the existing switch complete all as specified and directed .
Supply and fixing in replacement of copper ribbon suitable for 200 amps rated capacity gang operative switch, 45 CM long complete all as specified and directed .
S & F in replscement of MCCB Capacity 36 KA 4 pole 315 Amps adjustable thermal megnate to release type with preader and aluminium lugs all as required at site.
-do- but 250 Amp 36 KA
-do- but 200 Amp 36 KA
-do- but 160 Amp 36 KA
Supply laying & testing in replacement cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (Heavy duty_) LT 1100 volt grade with stranded aluminium conductor of size 300 sqmm 3.5 core complete all as specified and directed.
All as per srl item No 31 here-in-before but of size 185 Sqmm 3.5 core.
All as per srl item No 31 here-in-before but of size 70 Sqmm 3.5 core.
All as per srl item No 31 here-in-before but of size 50 Sqmm 3.5 core.
All as per srl item No 31 here-in-before but of size 35 Sqmm 3.5 core.
All as per srl item No 31 here-in-before but of size 25 Sqmm 3.5 core.
All as per srl item No 31 here-in-before but of size 16 Sqmm 4 core.
Supply and installed in replacement of 2 KVA invertor with battery backup upto 5 hrs including maint free batteries of cap 180Ah x 2 Nos including necessary wiring all as specified and directed Make:- Exide/Luminious/Microtech
Cleaning and preparation of old painted surface of LT steel pole 09/11 mtr long excluding planting depth complete and painting with one coat of aluminium paint including channels/ brackets, street light brackets, cross arms and making black & white strips with synthetic enamelled paint 30cm height, each alternative strip upto 1.5 mtr height and writing pole numbers and applying two coats of white wash on PCC coping complete all as specified and directed by Engr-in-Charge.
Supply and fixing of micro prismatic reflective sheet, min 5 cm wide 3 Nos, with adhesive base for dirtectly fixing on HT/LT steel tubular/PCC pole without nail or any other fixing material at suitable height, in Red,White&Yellow colour complete all as directed.
Material and labour for preparing old painted surface of panel board by cleaning removing of old paint by scratching with wire brush / sand paper etc and including denting of broken / rusted surface and applied two coat of synthetic surface enamel paint by spray painting outside surface of panel as existing colour of panel all as specified and directed.
Material and labour for repairing existing LT Panel doors of front , back and internal sheets complete with new locking arrangement complete all as specified and directed. Note: Any part/spare found defective such as packing, nuts bolts,hinges & (welding machine works) etc shall be repaired/replaced which cost shall be deemed to be included in the unit rate quoted for this item.
Supply only in replacement PVC insulation tape for 1100 Volt LT Cable insulation min 20 mtr length and 25mm width Make :- Kinjal/Steel Grip/Anchor
S&F in replacment disc type insulator porcelain vitreous 145mm high and 255 mm dia ball and socket type white, brown or green working pressure 11000 volts as specified and directed by Engr-in charge.
Supply,laying & fixing double wall corrugated (DWC) pipes made of high density polythyline (HDPE) with all accessories i.e. all type of joints,Sockets,Elbows,bends and End caps etc.. all as specified and directed by Engr in Charge.of fwg sizes Make;-Telerex/Tirupati or E-in-C approved Make (a) of size 77mm outer dia and 63mm inner dia
M & L for air break gang operated triple pole mechanically operated mounted on HT insulators and galvanised steel frame with operating rod of 25mm bore medium grade GI pipe suitable for operation while standing on ground for current rating 200 Amps suitable for 11000 volt 50 Hz supply including 12 insulator and drop out fuse carrier element all as specified and directed by Engineer-in-charge.
Excavation in trenches not exc 1.5 mtr and n. exc 1.5 mtr depth for laying of GI Pipe etc and getting out in any type of soil complete all as specified and directed by Engineer-in- Charge.
Returning filling in and including , spreading, levelling , watering and well raming in layers not exceeding 25 cm complete all as specified.
Removing excavated material n. exc 50m and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed.
M & L for sub class "B" brick covering laid dry flat (width equal to be length of the bricks) over sand cushioning along the length of cable complete all as specified and directed.
Material and labour for sand cushioning with a layer of fine sand 8 cm thick before laying the cable and 15 cm after laying the cable in trenches to cover under ground cable complete all as specified and directed. Note :-Punned down thickness of sand shall be considered for measurement)
Supply and fixing in replacement aluminium thimble of size 50 sqmm
Supply and fixing in replacement aluminium thimble of size 95 to 120 sqmm
Supply and fixing in replacement aluminium thimble of size 185 to 240 sqmm
Supply and fixing in replacement aluminium thimble of size 300 to 400 sqmm
Servicing of HT VCB 11KV,630A of Crompton make alongwith tripping system and testing of vaccum circuit breaker 11KV, 630A, 25KA including taking out Breaker/trolley and carried out the fwg repair/tests made for smooth operation
(a) Cleaning and greasing of mechanism- 01 Job
(b)Tightning testing of mechanism parts- 01 Job.
(c ) Alignment testing and adjustment of mechanism- 01 Job.
(d) Operation, testing of trip and close electrical and manual mode- 01 Job.
(e) Spring charging testing electrical and manual mode- 01 Job.
(f) Cleaning of panel insulater CT &PT unit- 01 Job.
(g) Cleaning and tightning of control/wiring CT &PT unit- 01 Job.
(h) Cleaning and testing of relay with current injection method- 01 Job.
(j) Testing of auxillary relay - 01 Job.
(k) Allingment of trolley, checking/greasing of shutter /lock of breaker
Note :- (a) Service will be carried out through any reputed Manfacturer authorised (ie L&T, Schenieder, CG,Kirloskar & ABB) Service Engineer only. (b) The cost of minor spare parts i.e nut and bolts, springs, grommets, dust cover, ring of isolator contacts, clips, pin for release prop, 'Y' Phase shround, over ride stop pin etc. unless or otherwise mentioned here-in-after but essentially required to make the panel serviceable shall be deemed to be included in the quoted rate.
Supply and fixing in replacement CT unit 100/50/5A, 15 VA 50Hz suitable for 11KV VCB Make CG
Supply and fix spring charging electric motor suitable for CG VCB of cap 630 Amp with complete accessories as per existing.
Supply and fixing in replacement of 11KV support insulator suitable for 11KV VCB dismantling and mantling of VCB Panel labour charge,high quality 11KV VCB busbar Insulation Material and Nutbolts included in quoted rates complete all as specified
Supply and fixing in replacement RYB indicator suitable for 11KV VCB complete all as specified.
Supply and fixing in replacement of Amp meter suitable for 11KV VCB DM 3 252 complete all as specified.
Supply and fixing in replacement of volt meter suitable for 11KV VCB DM 3 251 complete all as specified.
Supply and fixing in replacement Earth fault relay instant under voltage relay/over voltage relay complete all as specified.
Supply and fixing in replacement PT unit complete suitable for 11KV VCB 11000V/24V complete all as specified and directed.
Supply only Barrel type 11000 KV fuse wire of 2.5 Amp to 40 Amp rating of make PACTIL/JAIPURIA/RMCO
Testing of 11KV breaker through Power Grid Corporation of India , through PSEB Protection team are as under:- (NRC MAP Ph II ) (a) Tests to be carried out on each breaker ( Nos of Breaker - Five in NRC II)
Santokh Singh and Associates
M/s MAHAJAN CONSTRUCTION CO.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .