Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹15.2 LAccepted-AOC | L-1 | Accepted-AOC Tender accepted due to the lowest tenderer | |
| 2 | L-2₹16.6 L+₹1.1 L (7.27%)Rejected-Finance 88 GIRRAJ NAGAR KALWAD ROAD JOTHWARA JAIPUR 302012 JAIPUR CITY NORTH RAJASTHAN 302012 | JAIPUR | RAJASTHAN | 302012 | L-2 | Rejected-Finance Not being L1 | |
| 3 | L-3₹17.0 L+₹1.4 L (9.25%)Rejected-Finance | L-3 | Rejected-Finance Not being L1 | |
| 4 | L-4₹19.1 L+₹3.6 L (23.2%)Rejected-Finance | L-4 | Rejected-Finance Not being L1 |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
30 Jun 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
AGE (I) Niwaru
AGE (I) Niwaru
AGE(I) N-31 OF 2023-24 REPAIR AND MAINT SOLAR WATER HEATER SYSTEM LIGHTING CONDUCTOR AND EARTHING SYSTEM AT NIWARU MIL STN UNDER AGE (I) NIWARU
2023_MES_601254_1
AGE(I)/N-31 of 2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
AGE (I) Niwaru
CLASS E
6 documents required · 6 mandatory
₹500
Yes
AGE (I) Niwaru
₹40,000
Yes
7 Jul 2023
5 Jun 2023
3 Jul 2023
5 Jun 2023
30 Jun 2023
17 Jun 2023
Amount
Material & Labour for Earthing complete with galvanised steel earth plate electrode 600mm×600m.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to using galvanised iron strip 25×4mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel, 15 mm bore galvanised iron medium grade watering pipe, 40 mm bore galvanised iron light grade pipe for earth strip protection, including all excavation earth work in any type of soil, PCC 1:3:6 type C1 for chamber of internal size 300 mm x 300 x 300 mm with 120 mm thick wall and 700 mm x 700 mm x 150 mm thick bed concrete, RCC 1:2:4,type B1, reinforced with welded steel wire fabric or XPM jali (weight not less than 4.00 Kg/Sqm) with cast iron frame, funnel with wire mesh, test point etc complete all as specified and directed. Note: (i) Earth strip and GI protection pipe up to length 7.5m shall deemed to be included in rate of above item. (ii) The earth resistance value shall be less than 5 Ohm. Failing to achieve the value contractor shall re-do without any extra cost.
Material & Labour for Earthing complete with copper plate 600mm×600mm ×3 mm thick electrode buried directly in ground (earth pit not less than 3 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to 20mm×3mm copper strip as earthing lead by means of bolts, nuts, check nuts and washers, galvanised iron or steel 15 mm bore galvanised iron medium grade watering pipe, 40 mm bore galvanised iron light grade pipe for earth strip protection, including all excavation earth work in any type of soil, PCC 1:3:6 type C1 for chamber of internal size 300 mm x 300 x 300 mm with 120 mm thick wall and 700 mm x 700 mm x 150 mm thick bed concrete, RCC 1:2:4,type B1, reinforced with welded steel wire fabric or XPM jali (weight not less than 4.00 Kg/Sqm) with cast iron frame, funnel with wire mesh, test point etc complete all as specified and directed.all as shown in electricalplate No. 5 connected to earthing test point all as specified or indicated including testing on completion. Note: (i) Earth strip and GI protection pipe up to length 7.5m shall deemed to be included in rate of above item. (ii) The earth resistance value shall be less than 1 Ohm. Failing to achieve the value contractor shall re-do without any extra cost.
M&L for Chemical Earthing complete with CPRI tested 50mm bore pure copper earth electrode pipe with wall thickness of copper pipe not less than 20 gauge, of length 3000mm, pipe in copper strip Technology with NABL tested, RoHS compliant earth enhancement compound 50 Kg in each bore hole in tripod configuration (three numbers of 50mm dia pure copper electrode pipe) interconnected with 20x3mm size copper strip and connected by means of exothermic brazing & porected by GI pipe light grade 32mm bore and PCC (1:2:4) type B1 earth chamber & cast iron earth pit cover 300x300x3mm connecting to test point & testing on ground complete includingexcavation, earth work, boring in any type of soil strata & cleaning of site complete all as specified and directed. Note :- (i) Cost of 20x3mm size copper strip and 32mm bore GI pipe light grade required for interconnection of three numbers of pure copper 50mm dia earth electrode is deemed to be included in unit quoted rates. Copper strip of suitable size from earth pit to test point/equipment shall be measured and paid seperately. (ii) Cost of earth work, boring, PCC earth pit, CI cover, testing of earth after completion, connecting and commissioning is deemed to be included in unit quoted rates. (iii) Marking & painting of earth pit with iron plate of suitable size is deemed to be included in unit quoted rates (iv) The boring will take place for 350mm dia and 3m depth for three numbers of pure copper earth electrode pipe to form tripod configuration. Earth enhance compound to be filled around the earth electrode in 100mm dia in 3 layers of 1m each by means of PVC pipe of 100mm dia as casing/formwork. The remaining volume of bore shall be filled with clay soil available in vicinity in 3 layers of 1m each. The PVC pipe shall be removed sinultaneously. The cost of all this is deemed to be included in the quoted rate. (v) Minimum distance between each earthing is not less than 3m. (vi) Testing of earthing shall be conducted and result should be less than 1.00 Ohms. (vii) On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost.
Material & Labour for chemical earthing complete with pure copper earth plate electrode (98% conductivity when annealed) of size 900 mm x 600 mm x 5 mm thick buried directly in ground (earth pit not less than 4.00 m deep below normal ground level) with top edge of the plate not less than 4.00 m deep below normal ground connected to and including copper earth strip 32 mm x 6 mm by means of copper bolts nuts check nuts and washer, returning & filling the pit with excavated soil mixing with charcoal 250 KG, Crystal salt 200 KG, magnesium sulphate of 150 KG and vegetable soil all around the plate up to 350 mm above from top edge of plate and ballance portion filling with excavated soil in layers n.exc 25 mm thick, 15 mm bore galvanised iron medium grade watering pipe, 40 mm bore galvanised iron light grade pipe for earth strip protection, including all excavation earth work in any type of soil, PCC 1:3:6 type C1 for chamber of internal size 300 mm x 300 x 300 mm with 120 mm thick wall and 700 mm x 700 mm x 150 mm thick bed concrete, RCC 1:2:4,type B1, reinforced with welded steel wire fabric or XPM jali (weight not less than 4.00 Kg/Sqm) with cast iron frame, funnel with wire mesh, test point etc complete all as specified and directed. Note: (i) Earth strip and GI protection pipe up to length 7.5m shall deemed to be included in rate of above item. (ii) The earth resistance value shall be less than 1 Ohm. Failing to achieve the value contractor shall re-do without any extra cost.
Supply and fix copper strip 20mm x 3 mm with saddles & ceramic insulators and fixing screws etc for roof/down conductor above ground including jointing with rivets/ brazing etc all as directed by engineer-in-charge complete.
Supply and fix Aluminium strip 25mm x 3 mm with saddles & ceramic insulators and fixing screws etc for roof/down conductor above ground including jointing with rivets/ brazing etc all as directed by engineer-in-charge complete.
Supply and fix copper strip 32mm X 6 mm withsaddles & ceramic insulators and fixing screws etc for roof/down conductor above ground including jointing with rivets/ brazing etc including taking down of old strip of any type all as directed by engineer-in-charge complete.
Supply and fix test point terminal block made of gun metal / phosphorus bronze/copper of size 75x75x25mm drilled and screwed including 3 Nos 8mm dia 25mm long hexagonal head screw all as specified and directed.
Supply and fix air termination single pointed Copper rod 12mm dia ,900mm long complete all as directed. Note:- Air termination will be fixed with the help of ceramic insulator, PCC foundatio and GI pipe all as directed by Engineer-in-Charge.
S & F GI tubing light grade for mechanical protection of earth strip for lightning protection & by means of MS clamps with necessary bolts, nuts and washers etc complete all as specified of size 25 mm bore. Note:- (i) GI pipe will be used to support the Air termination. (ii) There will be Insulators between the GI pipe and Airtermination.
M&L for PCC 1:2:4, type B1, using 20mm graded crushed stone aggregate as in bed block coping cells etc. all as specified for base to errect the GI pipe and Air termination all as directed and specified by Engineer-in-Charge.
Material and labour for removinng of old unservisible insulating mat and Supply and laying in substations of Auto Glow Band featured electrical insulating mat (electromat) of capacity 33 KV class “C” as per Standard - IS 15652 :2006 & IEC 61111 made from synthetic Elastomer having following technical specification:- Thickness 3 mm, width 1000 mm, length 5 meter / 10 meter roll, Surfaces : Antiskid & Textured pattern, Tensile Strength (Amp Temp range -10 to 55 deg C) 15 N/mm2 (Min), insulation resistance with water 10,00,000 Mega ohm with 500V meggar or 1,00,000 Mega ohm with 5000V meggar, Leakage Current 10mA, Di Electric Strength 65 KV, AC Proof Voltage 36 KV, Flame Retardance Extinguish with in 5s after removal of Blue flame, Aging Properties:- Acid:- Tensile Strength Shall not be less than 75% of values on unaged piece. Alkali: - Shall not be less than 75% of values on unaged piece. Marking: - BIS Marking, ISI Class, Lot No, Roll no, Manufacturer's Identity. Colour: - Blue with orange colour safety border with Auto Glow Band Testing Agency CPRI & ERDA Make: - Electromat / Safevolt or equivalent as per directed by Engineer-in-Charge.
Supplying and spreading of crushed stone gravels size 40 mm to 63 mm size around transformer plinth, two/ four pole structure and HT yard etc. Note:- (i) Contractor will do preparation / leveling of the area before spreading of gravel in such a way as to clear of all grass, weeds, roots and all other objectionable materials. (ii) A suitable chemical treatment on the switchyard ground shall be applied to arrest future growth of grass, weeds, etc. as per engineer-in-charge (iii) The first layer of lower size aggregate shall be spread uniformly and compacted to a thickness of approximately 50 mm. (iv) The second layer consists of 63 mm. and 40 mm. Size aggregates mixed in proportion of 2 : 1 by volume, which shall be spread uniformly and compacted to the thickness of approximately 100 mm. So as to furnish a total finished thickness of 150 mm of compacted gravel surfacing. (v) Aggregate shall consist of well shaped clean, arid, dense, durable granite rock fragments and shall not include elongated, flaky or laminated pieces and any other impurities or deleterious material. (iv) Rate of cleaning grass/ chemical treatment / compacting / any otherconnected material and labour is included in unit rate quoted above.
Shree Karni Electrovision
SHREE BHAGWATI ENTERPRISES
S.R.Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .