Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.0 LAccepted-AOC 371 21 RBL ROAD NEW HYEDERABAD COLONY LUCKNOW UTTAR PRADESH 226007 | LUCKNOW | UTTAR PRADESH | 226007 | L1 | Accepted-AOC Being L1 work Awarded to M/s Cool Control |
Tender Value
₹1.9 L
EMD Value
₹3,834
Closing Date
12 Jun 2025, 4:00 pmClosed
O/o Executive Engineer (Electrical)
O/o Executive Engineer (Electrical) BSNL Electrical Division 1ST Floor, Bhopal House, Lalbagh Lucknow
Dismantling, transportation and installation of SAC/ Ducatble AC units from TE Indira nagar/Bhadewa/ Gomtinagar and Assosiated work TE Kaiserbagh Lucknow
2025_BSNL_237772_1
17/TEDL/BSNL/2025-26, Dated 24/05/2025
Open Tender
Electrical Works
Item Rate
30 days
Lucknow
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
AO, (Cash), BSNL O/o The PGMTD, LUCKNOW
₹3,834
26 Jul 2025
7 Jun 2025
13 Jun 2025
7 Jun 2025
12 Jun 2025
7 Jun 2025
SH: Dismantling, transporation and ITC of SAC/ DAC Dismantling of 1.5TR SAC unit i/c indoor unit and outdoor unit, with accessories etc complete as reqd (Note - 01nos from Vishwas Khand Gomti Nagar and 02 nos from PCM room TE Bhadewan)
Dismantling of ducatbale AC unit i/c indoor unit and outdoor unit, with all accessories etc complete as reqd (Note - 03nos from switch room at TE Indira nagar & 01 no Utility Club Kaiserbagh)
Transportation of SAC form TE Vishwas Khand/ TE Bhadewan to TE Indira nagar/ Kiaserbagh, i/c loading, unloading etc complete as reqd Note 01nos from Vishwas Khand Gomti Nagar and 02 nos from PCM room TE Bhadewan)
Transportation of Ductable AC form TE Indira nagar to TE Kaiserbagh i/c loading, unloading etc complete as reqd
Carrying out Wet Servicing of 1.5TR Split AC unit unit i/c removing, cleaning all components and filters, de-dusting by high pressure air blower, washing condenser, evaporator i/c chemical cleaning (if required), refixing, tightening electrical connections, minor repairs, if required, testing of AC unit, recording all parameters in service report etc as reqd.)
Carrying out Wet Servicing of 3TR ductable AC unit i/c removing, cleaning all components and filters, de-dusting by high pressure air blower, washing condenser, evaporator i/c chemical cleaning (if required), refixing, tightening electrical connections, minor repairs, if required, testing of AC unit, recording all parameters in service report etc as reqd.
Installation, Testing and Commissioning of above 1.5 TR Split AC units units, suitable size of PVC insulated cord wire and PVC drain pipe. including gas charging, insulation, and making opening in wall and making good the damages etc., complete as per specifications, terms and conditions attached as required. (01nos in CSC Indira Nagar and 02 nos in PCM room TE Kaiserbagh)
Charging of refrigerant gas in split air conditioner complete with carrying out leak testing of 1.5TR/ 2 TR Split AC units with nitrogen gas including flushing the system, brazing/flaring the leak points, vacumising, purging and making the system leak proof i/c transportation of nitrogen cylinder, brazing kit & vacuum pump, supplying & charging of refrigerant gas at site, testing & commissioning etc as required.
Replacement of faulty /defective 1.5 TR capacity compressor with new Sealed compressor i/c dismantling of faulty compressor, cutting refrigerant piping, brazing & making necessary addition/alteration i/c proper mounting on base plate, connection of suction and discharge lines, Leak test i/c testing commissioning etc as reqd.(M/s Emerson/Tecumseh/SS make) (Note - The firm shall submit test certificate or documentary proof towards purchase of New/OEM factory repaired compressor.) The defective compressor shall be the property of agency & firm should consider suitable price rebate for the same while quoting. The material under replacement shall be similar to existing defective material or as per product directory)
Installation, Testing and Commissioning of above 3.0 TR Ductable Split AC units, suitable size of PVC insulated cord wire and PVC drain pipe. including MS suspension rod, fastenet for indoor/outdoor, insulation, and making opening in wall and making good the damages etc., complete as per specifications, terms and conditions attached as required. Note: 02nos PCM room at TE Kaiserbagh & 01no at NTR room at TE Indira Nagar, 01 no Trans roon Indiranagar)
Supplying and laying of refrigerant piping (both liquid and suction lines) in the existing tray for the above 3 TR ductable split AC unit along with necessary accessories like nitrile rubber insulation, clamping etc as required.
SH: Power supply and Assosiated work -Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. (a) 63 A, 16 KA,FPMCCB (HPL TAB100VX032AC4P or SS make)
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.), (a) 4 way (8 + 12), Double door
Supplying and fixing of one number PVC insulated and PVC sheathed copper Conductor armoured/ unarmoured power cable of 1.1 KV grade of following size on wall surface as required. (a) 4 X 10 Sq.mm Cu. Condr. Un Armoured Cable
(b) 4 X 4 Sq.mm Cu. Condr. unArmoured Cable (Note - Provision taken for 4 nos DAC units)
Providing Flexible Pipe for condensate Drain from indoor unit to the nearest drain point provided by you in consultatoin with site incharge (40mm dia)
Supplying and fixing MCB, 25 A “C” curve 3P MCB complete with connections, testing and commissioning etc. as required.
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .