Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹41.1 LAccepted-AOC | L1 | Accepted-AOC lowest | |
| 2 | L2₹43.3 L+₹1.8 L (4.22%)Rejected-Finance 131 SANGAM NAGAR OPP NATIONAL SCHOOL SANGHVI PUNE 411027 | PUNE | MAHARASHTRA | 411027 | L2 | Rejected-Finance RATE HIGH | |
| 3 | L3₹44.9 L+₹3.3 L (8.00%)Rejected-Finance | L3 | Rejected-Finance RATE HIGH |
| Sl No | Description | Qty | Unit | shanti enterprises L1 | Leo Enterprises L2 | Suchit constructions L3 |
|---|---|---|---|---|---|---|
| 1.00 | S&F in replacement of 4mm thick glass of approved shade of good quality with and including aluminium anodised frame along with rubber beading and other accessories as required at site etc. complete all as directed by Engr-in-charge | 20 | Sqm | 1,000 ₹20,000 Lowest | 1,800 ₹36,000 | 1,760 ₹35,200 |
| 2.00 | Taking down old unserviceable single Headed Oblique type gun metal fire hydrant valve of 63 mm dia complete all as specified and directed. | 20 | Each | 20 ₹400 Lowest | 100 ₹2,000 | 120 ₹2,400 |
| 3.00 | S&F ISI marked single headed 63 mm dia. gun metal Hydrant Valve, flanged inlet with 63 mm female instantaneous outlet confirming to IS : 5290 on the fire wet riser / down comer including making 80 mm nominal bore pipe connection with riser fixing the landing valves in proper positions, including supply of nuts, bolts, gaskets, caps, chains etc. testing the hydrant and completing the work in all respect all as directed by Engr-in-Charge. | 20 | Each | 5,000 ₹1,00,000 Lowest | 9,000 ₹1,80,000 | 9,900 ₹1,98,000 |
| 4.00 | S&F gun metal, ISI marked, 63mm dia Instantaneous pattern short branch pipes & 12.5 mm dia. Nozzle suitable for inter connections to hose pipe coupling as required complete all as specified and directed. | 40 | Each | 1,400 ₹56,000 Lowest | 2,800 ₹1,12,000 | 2,700 ₹1,08,000 |
| 5.00 | S&F in replacement outlet nozzle cap along with chain fixed on hydrant 63mm as required complete all as specified and directed. | 45 | Each | 25 ₹1,125 Lowest | 40 ₹1,800 | 45 ₹2,025 |
| 6.00 | Taking down of female adaptor, gun metal, suitable for fire hydrant valve 63 mm dia, complete all as specified and directed. | 45 | Each | 30 ₹1,350 Lowest | 89 ₹4,005 | 72 ₹3,240 |
| 7.00 | S&F in replacement of female adaptor (Gun metal) suitable for 63 mm dia fire oblique type fire hydrant valve, complete all as specified and directed. | 45 | Each | 2,000 ₹90,000 | 90 ₹4,050 Lowest | 99 ₹4,455 |
| 8.00 | M&L for red colour painting on fire hydrant pipe of dia 80 mm / 100mm / 150 mm by scrapping the old surface and applying two coats of synthetic enamel paint on the surface and making good any disturbed surface, complete all as specified and directed. | 450 | RM | 80 ₹36,000 Lowest | 160 ₹72,000 | 153 ₹68,850 |
| 9.00 | M&L for servicing of valve any type and size by opening, greasing running part, by replacing gland fitting with new one and reassemble again complete all as specified and directed
Note- : Parts required for replacement will be measured and paid seperately as "Supply only". | 100 | Each Job | 300 ₹30,000 Lowest | 400 ₹40,000 | 420 ₹42,000 |
| 10.00 | Supply only Grease of Suitable Grade, complete all as specified and directed. | 15 | Kg | 120 ₹1,800 Lowest | 130 ₹1,950 | 136 ₹2,040 |
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
20 Oct 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE SOUTH PUNE
NO 1 GEN BHAGAT MARG PUNE 40
8746 REPAIR MAINTENANCE OF NURSE CALL PATIENT CALL SYSTEM AND OTHER MISC WORKS AT NEW CHSC AND CONNECTED AREA UNDER AGE EM II OF GE SOUTH PUNE
2025_MES_733233_1
8746 GE SOUTH PUNE
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE SOUTH PUNE
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE SOUTH PUNE
₹98,000
Yes
8 Dec 2025
29 Sept 2025
22 Oct 2025
29 Sept 2025
20 Oct 2025
13 Oct 2025
Amount
S&F in replacement of 4mm thick glass of approved shade of good quality with and including aluminium anodised frame along with rubber beading and other accessories as required at site etc. complete all as directed by Engr-in-charge
Taking down old unserviceable single Headed Oblique type gun metal fire hydrant valve of 63 mm dia complete all as specified and directed.
S&F ISI marked single headed 63 mm dia. gun metal Hydrant Valve, flanged inlet with 63 mm female instantaneous outlet confirming to IS : 5290 on the fire wet riser / down comer including making 80 mm nominal bore pipe connection with riser fixing the landing valves in proper positions, including supply of nuts, bolts, gaskets, caps, chains etc. testing the hydrant and completing the work in all respect all as directed by Engr-in-Charge.
S&F gun metal, ISI marked, 63mm dia Instantaneous pattern short branch pipes & 12.5 mm dia. Nozzle suitable for inter connections to hose pipe coupling as required complete all as specified and directed.
S&F in replacement outlet nozzle cap along with chain fixed on hydrant 63mm as required complete all as specified and directed.
Taking down of female adaptor, gun metal, suitable for fire hydrant valve 63 mm dia, complete all as specified and directed.
S&F in replacement of female adaptor (Gun metal) suitable for 63 mm dia fire oblique type fire hydrant valve, complete all as specified and directed.
M&L for red colour painting on fire hydrant pipe of dia 80 mm / 100mm / 150 mm by scrapping the old surface and applying two coats of synthetic enamel paint on the surface and making good any disturbed surface, complete all as specified and directed.
M&L for servicing of valve any type and size by opening, greasing running part, by replacing gland fitting with new one and reassemble again complete all as specified and directed Note- : Parts required for replacement will be measured and paid seperately as "Supply only".
Supply only Grease of Suitable Grade, complete all as specified and directed.
Supply only Gland of suitable size, complete all as specified and directed.
S&F brass threaded spindle yoke bolt, wedge ring, seat ring of existing size (Lathe work deemed to be included in quoted rate), complete all as specified and directed.
M&L in replacement for ISI marked RRL (IS : 636 type-II) fire hose pipe 15 meter long and 63 mm dia with ISI marked (IS : 903) gun metal male and female coupling complete as required all as specified and directed.
S&F in replacement CI butter fly valve class PN-1.6 with non- magnetic steel spindle ISI marked (IS-780 or latest revision) with flanged ends including necessary mounting nuts, bolts, washers and packing fibre gasket on both ends suitable for 150 mm nominal bore pipe, complete all as specified and directed.
S&F in replacement CI butter fly valve class PN-1.6 with non- magnetic steel spindle ISI marked (IS-780 or latest revision) with flanged ends including necessary mounting nuts, bolts, washers and packing fibre gasket on both ends suitable for 100 mm nominal bore pipe, complete all as specified and directed.
S&F in replacement CI butter fly valve class PN-1.6 with non- magnetic steel spindle ISI marked (IS-780 or latest revision) with flanged ends including necessary mounting nuts, bolts, washers and packing fibre gasket on both ends suitable for 80 mm nominal bore pipe, complete all as specified and directed.
S & F in repairs 25 mm bore stop valve, cast copper alloy, screwed down, high pressure with crutch or butterfly handle, screwed both ends for iron pipe or for unions as per site requirement complete all as specified and directed by Engr-in-charge.
S & F in repairs 40 mm bore stop valve, cast copper alloy, screwed down, high pressure with crutch or butterfly handle, screwed both ends for iron pipe or for unions as per site requirement complete all as specified and directed by Engr-in-charge.
S & F in repairs 50 mm bore stop valve, cast copper alloy, screwed down, high pressure with crutch or butterfly handle, screwed both ends for iron pipe or for unions as per site requirement complete all as specified and directed by Engr-in-charge.
M&L for discharge CO2 Gas/ Powder from Fire fighting Cylinders (CO2 type and ABC type) and Carry out for visual survey, Repair/ Overhauling, removal of CO2 Cylinder pressure directional valve/ Nozzles/ Pressure switch etc and Charging, weighing & Hydro testing and commissioning with Filling of CO2 gas/ ABC powder in each cylinder with Stamp and date of testing on each cylinder with submission of CCE approved Gas filling agency certificate complete all as specified and as directed. Note: (i) Rate quoted will deemed to be included the cost of dismantling of gas Cylinders, transportation, weighing of cylinders, Hydro testing and commissioning of the cylinders with Certificate by CCE approved agency. (ii) Cost of CO2 gas/ ABC powder will be measured and paid separately in respective item of BOQ. (iii) Quoted rate deemed to be included the cost of Minor spares ie Cylinder valve, disc, Teflon tape and other all accessories required in ground.
Refilling only CO2 Gas for filling in the existing CO2 Fire Fighting Cylinders complete all as specified and as directed.
Refilling only Dry powder for ABC type Fire Fighting Cylinders complete all as specified and as directed.
Supply only master valve for existing Cylinder for Fire Fighting complete all as specified and as directed.
S&F in replacement 150mm bore non return valve class with non- magnetic steel spindle ISI marked (IS-780 or latest revision) with flanged ends including necessary mounting nuts, bolts, washers and packing fibre gasket on both ends etc complete all as specified and directed.
S&F in replacement 100mm bore non return valve class with non- magnetic steel spindle ISI marked (IS-780 or latest revision) with flanged ends including necessary mounting nuts, bolts, washers and packing fibre gasket on both ends etc complete all as specified and directed.
S&F in replacement pressure gauge screwed to the exisiting pipe line including taking down existing one, complete all as specified and directed.
M&L in replacement weather proof standard fire hose cabinet (900 mm x 600 mm x 500 mm) outdoor type suitable for accomodating single headed hydrant valve made of not less than 16 SWG MS sheet having central opening glassed door (4 mm thick clear glass) including necessary locking arrangement with handle for housing two nos.15 meter long fire hose pipes, branch pipe and hydrant valve as required including painting (one coat primer and two coat of fire red colour). The cabinet shall be mounted on suitable raised brick masonry built in CM (1:6) platform or on MS Angle iron frame of suitable size and section complete all as specified and directed. The words "FIRE HOSE" to be painted on the box.
M & L in replacement for drum type wall mounted hose reels, swinging 180 degrees conforming to IS with ISI mark consisting of 20 mm dia x 30 m long, braided rubber hose pipe with 6.3 mm dia bronze shut off type jet nozzle, including providing 20mm dia shut off valve, fixing the hose reel with necessary anchor fastners by drilling holes in walls / RCC, making good the same complete all as directed by Engineer-in-charge.
M&L for painting weather proof standard fire hose cabinet (900 mm x 600 mm x 500 mm) outdoor type by scrapping the old surface completely and applying two coats of synthetic enamel paint (Red colour) on the surface and the words "FIRE HOSE" to be painted on the box and scrapping surface of angle iron and applying two coats of synthetic enamel paint (Black Colour) and making good any disturbed surface complete all as specified and directed by Engr-in-charge.
S&F in replacement of ISI marked M.S. pipes (Class C) and specials etc. of dia 150 mm for hydrants and sprinkler system including transportation of materials upto the worksite, cutting the pipes to required length, edge preperation, welding, fixing / erection of pipes with suitable flat/angle iron including specials i.e. bends, tees, reducers, flanges etc. in proper position including all supports as per layout, including hangers for sprinkler piping, jointing by welding, aligning the pipe line, painting with a red oxide primer coat and two coats of synthetic enamel paint fire red colour, providing tapping for pressure gauges and for other instruments etc. Hydrostatic testing of system as specified, flushing & cleaning by water etc. including taking down exisitng one complete as specified and directed.
All as per item no 30 above but 100 mm dia, complete as specified and directed.
All as per item no 30 above but 80 mm dia, complete as specified and directed.
All as per item no 30 above but 50 mm dia, complete as specified and directed.
All as per item no 30 above but 40 mm dia, complete as specified and directed.
All as per item no 30 above but 32 mm dia, complete as specified and directed.
All as per item no 30 above but 25 mm dia, complete as specified and directed.
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of pipes etc. and getting out in the Soft/Loose soil complete all as specified and as directed by the Engineer-in-Charge.
All as per item no. 37 above but Hard/ Dense soil, , complete as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers of soil not exceeding 25cm thick complete all as specified and as directed by the Engineer - in - Charge.
Removal of excavated material to a distance not exc. 50m and depositing where directed at a level not exc 1.5m above the starting point of soil where directed complete all as specified and as directed by the Engineer - in - Charge.
M&L for Disconnection of electrical and water connection of the centrifugal puimp and motor of capacity 60 HP from base plate and transport to work shop, Carfully opening and replacement of bushes, mechanical seal, ball bearing rubber gasket nut and bolt fixing the require new parts (parts such as shaft impeller, coupling, mechanical seal and bearing shall be supplied under relevant item of schedule) and completee re-fixing its in original position and making good all electrical and water connection and testing etc complete all as specified and directed. Note : Rate on account of transportation, loading, unloading of motor from the place of installation for repairing and re-installing the same on existing foundation and testing and commisioning shall be deemed to be included in unit quoted rates.
All as per item no 41 above but 50 HP, complete as specified and directed.
All as per item no 41 above but 7.5 / 10 HP, complete as specified and directed.
Supply only shaft suitable for centrifugal pumps for 60 HP capacity, complete as specified and directed.
Supply only GM impeller suitable for centrifugal pumps for 60 HP capacity, complete as specified and directed.
Supply only MS Coupling suitable for centrifugal pumps for 60 HP capacity, complete as specified and directed.
Supply only Bearing suitable for centrifugal pumps for 60 HP capacity, complete as specified and directed.
Supply only Mechanical Seal for centrifugal pumps for 60 HP Capacity, complete as specified and directed.
Supply only pump gasket fitting of suitable size for centrifugal pumps for 60 HP Capacity, complete as specified and directed.
Supply only shaft suitable for centrifugal pumps for 50 HP capacity, complete as specified and directed.
Supply only GM impeller suitable for centrifugal pumps for 50 HP capacity, complete as specified and directed.
Supply only MS Coupling suitable for centrifugal pumps for 50 HP capacity, complete as specified and directed.
Supply only Bearing suitable for centrifugal pumps for 50 HP capacity, complete as specified and directed.
Supply only Mechanical Seal for centrifugal pumps for 50 HP Capacity, complete as specified and directed.
Supply only pump gasket fitting of suitable size for centrifugal pumps for 50 HP Capacity, complete as specified and directed.
Supply only shaft suitable for centrifugal pumps for 7.5 / 10 HP capacity, complete as specified and directed.
Supply only GM impeller suitable for centrifugal pumps for 7.5 / 10 HP capacity, complete as specified and directed.
Supply only MS Coupling suitable for centrifugal pumps for 7.5/10 HP capacity, complete as specified and directed.
Supply only Bearing suitable for centrifugal pumps for 7.5 / 10 HP capacity, complete as specified and directed.
Supply only Mechanical Seal for centrifugal pumps for 7.5 / 10 HP Capacity, complete as specified and directed.
Supply only pump gasket fitting of suitable size for centrifugal pumps for 7.5 / 10 HP Capacity, complete as specified and directed.
Dismantling of existing unserviceable 60 HP motor centrifugal pump set from foundation and painting by synthetic enameled paint one coat after cleaning and preparing surface for painting, reinstalling and testing complete at site on full load complete all as specified and directed by Engr-in-Charge.
All as per item no 62 above but 50 HP, complete as specified and directed.
All as per item no 62 above but 7.5 / 10 HP, complete as specified and directed.
M&L for dismantling all connection electrically including transportation to workshop and fixing the same after removing the unservceable winding from the motor cleaning the starter slots, rewinding with appropriate size and or existing super enamelled copper winding wire and insulating to the existing class of insulation, cleaning the starter assmebly including fixing of terminal, copper lugs, insulation etc., testing and assmebling of 3 phase motor of 60 HP capacity complete as directed by Engineer-in-Charge. Note : (i) If pump motor is required on urgency (the same will be intimated by JE/Engr-in-charge) then Contractor shall provide & install a temporary pump motor on their own arrangement within the 4 hours of dismantling otherwise a penalty of Rs.1000 per day wiil be recovered from contractor's dues. (ii) Pump/Motors should be returned and fixed after repair within 3 days of intimation of unserviceable, if the same is not re-installed within the stipulated period then a penalty of Rs.1000 per day wiil be recovered from contractor's dues. (iii) Pump motor should be examined by the contractor in front of the Engr-in-Charge before transporting to the workshop and defective parts which will be replaced to be noted down.
All as per item no. 65 above but 50 HP, complete as specified and directed.
All as per item no. 65 above but 7.5 / 10 HP, complete as specified and directed.
Supply and Fix Lubricated and graphited general purpose asbestos packing on glands suitable for pump sets of diameter upto 12.5 mm complete all as directed by Engr-in-Charge.
S & F in repairs foot valve's brass assembly 150 mm dia complete all as specified and directed. Make - Normex/Zoloto/cair
S & F in repairs foot valve's brass assembly 100 mm dia complete all as specified and directed. Make - Normex/Zoloto/cair
M&L for Servicing of DG Pumps carryout inspection, checking, replacing of unserviceable parts of cylinder assembly, piston system, piping system, cylinder liners, radiator function and cleaning throughly with cleaning agents, repair any mechanical and electrical fault etc of 50/60 HP, complete all as specified and directed by Engr-in-charge. Note : - (a) The cost of spares (material) shall be measured and paid separately under respective item of BOQ as "Supply only". (b) The rates quoted against the above mentioned Items shall be deemed to be included for cost of labour, cost of T & P required and minor parts required for repair such as nut, bolts, battery terminals etc.
Supply only Diesel filter suitable for 50/60 HP DG Pump including taking down existing one, complete all as specified and directed.
Supply & toping up of engine oil of grade SAE 15 W 40 as directed in standard packings / sealed container including taking down existing one, complete all as specified and directed.
Supply and toping up of distilled water in standard packing /sealed container including taking down existing one, complete all as specified and directed.
Supply and toping up of coolant in standard packings / sealed container including taking down existing one, complete all as specified and directed.
S&F in replacement of C.P. brass sprinklers comprises of 15mm dia conventional pattern, 68 Degree Centigrade, quartzoid bulb type pendent sprinklers including suitable flexible and rigid dropping fitting etc complete all as specified and as directed.
Labour only for inspection of fault in motor panel / Engine driven panel and replacement of unserviceable electronic parts including taking down and testing complete all as directed by Engr-in -Charge. Note: 1. Spare parts of panel will be measured and paid separately under respective BOQ as "Supply only" 2. All T& P and TPT used will be deemed to be included in unit quoted rate.
Supply only Power contactor 70 Amps 3 pole 415 volts AC 3 heavy duty, complete all as specified and directed
Supply only Power contactor 40 Amps 3 pole 415 volts AC 3 heavy duty, complete all as specified and directed
Supply only Front Mounting Add-on aux. Contact Block with 2 NO + 2 NC, complete all as specified and directed
Supply only thermal over load relay suitable for existing make and capacity, complete all as specified and directed
Supply only Single phase preventor suitable for existing make and capacity, complete all as specified and directed
Supply only Electronic Timer 160-500V ,for 12-120sec, complete all as specified and directed
Supply only Digital panel volt Meter 3 phase Flush Mounting 96x96mm, Accuracy Class-I, input voltage measurement range 17-520V AC (P-P), complete all as specified and directed
Supply only Digital panel ammeter, 3 phase 5A, Flush Mounting 96x96mm, Accuracy Class-I, CT/PT Site programmable, complete all as specified and directed
Supply only Indicator lamp 3 phase, complete all as specified and directed
Supply only ON OFF push button, complete all as specified and directed
Supply only control wiring multistranded single core 1.5 sqmm, complete all as specified and directed
Supply only control wiring multistranded Single core 2.5 sqmm, complete all as specified and directed
Supply and fix MCB SP 6 to 40 Amps, C curve 415 volts complete all as specified and as directed
Supply and fix MCB TP 16 to 40 Amps, C curve 415 volts complete all as specified and as directed
Supply and fix MCB TPN 16 to 40 Amps, C curve 415 volts complete all as specified and as directed
Supply and Fix in replacement of MCCB 200 Amps, 25 KA, 3 Pole, 415V complete all as specified and directed by Engr-in-Charge. Make - Legrand/L&T/Siemens
Supply and Fix in replacement of MCCB 160 Amps, 25 KA, 3 Pole, 415V complete all as specified and directed by Engr-in-Charge. Make - Legrand/L&T/Siemens
Supply and Fix in replacement of MCCB 100 Amps, 25 KA, 3 Pole, 415V complete all as specified and directed by Engr-in-Charge. Make - Legrand/L&T/Siemens
S&F in repair for armoured copper conductor with single core, 35 sqmm, 1100 volts grade, PVC insulated, stranded copper conductor cable with lugs, ferrules etc.complete all as specified and as directed by the Engineer-in-charge.
S&F in repair for armoured copper conductor with single core, 50 sqmm, 1100 volts grade, PVC insulated, stranded copper conductor cable with lugs, ferrules etc.complete all as specified and as directed by the Engineer-in-charge.
S&F in replacement of Exit Light, self contained 6W luminarie type, U21 complete with flush mounting frame, sign label, LED & battery and with double side label EXIT complete all as specified and as directed. Make:- Prolite or equivalent as approved
S&F in replacement of Emergency Exit Beam Light LED type with twin Beam and backup upto 3 hrs complete all as specified and as directed. Make:- Prolite or equivalent as approved
Periodical / Preventive/ Comprehensive maintenance of Nurse Call and Patient Calling System by checking any type of complaints like resetting, programming of calling system, no electric supply to control panel etc. including carrying out repairs as required to make it functional by replacing necessary items / parts complete all as directed by Engr-in-Charge. (i) The entire comprehensive maintenance of Nurse calling & Patient Calling system shall be carried out through OEM (Stephan Design & Engineering Ltd) or OEM approved dealer and the defective components / parts of different system shall be replaced with original existing make only. (ii) The contractor may visit the site for inspection with Service Engineer of OEM/ Manufacturer of the system before quoting his rate and no compensation whatsoever will be paid for misunderstanding of schedule ‘A’ / BOQ description at a later stage. (iii) The contractor shall maintain proper record of repair / maintenance in a binded register duly bringing out the details of spares replaced and get it authenticated from concerned JE E/M on daily basis. The contractor shall put up the maintenance record register to Engineer-in-charge for inspection every Monday or as and when asked for. (iv) The contractor has to rectify the defects and make the defective item functional within 48 hours from the time, the list of defective item is handed over to him / his rep by the concerned JE E/M. In case the item is not made functional for whatsoever reason within the specified time limit, an amount of Rs 500.00 per such defective item per day will be recovered from contractor's dues.
S&F in replacement of Bed side unit mother board complete all as specified & directed.
S&F in replacement of 100 Amp 9 V Transformers complete all as specified & directed.
S&F in replacement of Wireless Communication Modules complete all as specified & directed.
S&F in replacement of central display Mother board complete all as specified & directed.
S&F in replacement of Corridor display PCB complete all as specified & directed.
S&F in replacement Doctor calling Unit mother board complete all as specified & directed.
S&F in replacement of 5V 2 Amp Adaptor complete all as specified & directed.
S&F in replacement of nurses station terminal monitor station with built-in LCD display and Call Console System having plug in type Single digital Module for each bed with suitable digital electronic components with three colour indication, with power supply suitable for 220 volts, 50 Hz, AC main supply with step-down transformer of appropriate rating , electronic rectifier with regulating circuits to give two numbers of DC outputs of + 12V DC through battery/panel and battery charger , all housed in powder coated sheet steel enclosure ,network interface module,power supply as per specification for Nursing station terminal, LED Type, catering to 08 beds complete all as directed by Engr-in-Charge.
All as per item no. 109 above but 16 beds, complete all a specified & directed.
All as per item no.109 above but 24 beds, complete all a specified & directed.
All as per item no.109 above but 30 beds, complete all a specified & directed.
S&F in replacement of bed side unit indication and call module recessed / wall mounted / bed head panel, Non-voice type with digital membrane,switches having three colour indication, call and cancel button (reset button) as per specifications required with remote, as per specifications enclosed complete all as directed by Engr-in-Charge.
S&F in replacement of Hand Held Wired Remote to initiate the call, whenever patient presses the button, hand set shall also have all three colours, hand held module and call and cancel button (reset button) as per required specifications complete all as directed by Engr-in-Charge.
S&F in replacement of Emergency Alert call modules for Toilet comprising call button, call status indicators with 4 colour LED lamps and water protected enclosure complete all as directed by Engr-in-Charge.
S&F in replacement of Pull Cord connected to Nurse Call station complete all as specified & directed.
S&F in replacement of Door display unit as per specifications complete all as specified & as directed.
S&F in replacement of Main Central Display Unit complete all as specified & directed.
S&F in replacement of Slave Central Display Unit complete all as specified & directed.
S&F in replacement of Room desk Unit complete all as specified & directed.
S&F in replacement of fire house reel nozal, 20mm size, made out of gun metal complete all as directed by Engr-in-Charge.
Supply & Laying of Cat 6- 4 Pair, 23, AWG, UTP Cable with cross member pair separator (For Nurse Call) complete all as directed by Engr-in-charge
S&F in replacement of Corridor door display Unit complete all as specified & directed.
Leo Enterprises (BID ID -3455867)
Suchit constructions (BID ID -3460592)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.60 MB
8746TD.pdf
Tender Documents • 0.92 MB
BOQ_820981.xls
BOQ • 0.62 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .