REPAIR/MAINTENANCE OF UG HT CABLE AND OH HT LINE AT ZONE 8 TO ZONE 13 AT POWER HOUSE NO 1 AREA UNDER GE PANAGARH
2022_MES_532232_1
8799/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
PANAGARH
Pl refer Tender Documents
7 documents required · 7 mandatory
₹500
GE PANAGARH
₹50,000
Yes
20 Sept 2022
20 Jun 2022
1 Aug 2022
20 Jun 2022
30 Jul 2022
5 Jul 2022
Amount
Taking down /Taking out old Unservicable burnt/punctured/faulty Aluminium cable /HT Pilca cable /Cross linked polythene(XLPE)Insulated,sreened,PVC bedded, galvanised steel strip or wire armoured,electric power cables(heavy duty) 11000 volt grade of cross sectional area 95 sqmm x 3 core from pole /laid in trenches/ through pipe in road crossing / path/drains/ducts/floors/along poles/celling/wall/equipments etc. and relaying the same after removing the defect including the cutting making jointing, complete all as specified and as directed by Engrs- in Charge. Note : (1) Joints sand cushioning, cable protection, GI Pipe and Excavation and earth work shall be measured separately. (ii) Road cutting involved during excavation for laying of cable etc shall be made good as per existing road. Nothing extra shall be admissible on this accounts.
Taking down /Taking out old unservicable burnt/punctured/faulty Aluminium cable /HT Pilca cable /Cross linked polythene(XLPE)Insulated,sreened,PVC bedded, galvanised steel strip or wire armoured,electric power cables(heavy duty) 11000 volt grade of cross sectional area 150 sqmm x 3 core from pole /laid in trenches/through pipe in road crossing / path/drains/ducts/floors/along poles/celling/wall/equipments etc and relaying the same after removing the defect including the cutting making jointing, complete all as specified and as directed by Engrs- in Charge. Note : (1) Joints sand cushioning, cable protection, GI Pipe and Excavation and earth work shall be measured separately. (ii) Road cutting involved during excavation for laying of cable etc shall be made good as per existing road. Nothing extra shall be admissible on this accounts.
Taking down cable of any size of 11000 volts grade after excavation for laying of new cable of existing size,Complete all as specified and as directed. Note: Rate for new cable is considered in relevant items.
Supply , laying & testing of XLPE insulated, screened,HT PVC bedded, galvanized steel strip or wire armoured electric power cable (heavy duty) 11000 Volts grade (E) with aluminum conductor 3 core 150 square mm ISI marked IS: 7098-1985, laid in trenches, duct, through pipe, in floor, on pole including jointing , complete all as specified and as directed by Engrs-In-Charge. Note: PCC route indicators to be fixed on every 50m distance duly written ' HT CABLE' on each route indicator and rate to be catered in this item rate.
Supply , laying & testing of XLPE insulated, screened,HT PVC bedded, galvanized steel strip or wire armoured electric power cable (heavy duty) 11000 Volts grade (E) with aluminum conductor 3 core 120 square mm ISI marked IS: 7098-1985, laid in trenches, duct, through pipe, in floor, on pole including jointing , complete all as specified and as directed by Engrs-In-Charge. Note: PCC route indicators to be fixed on every 50m distance duly written ' HT CABLE' on each route indicator and rate to be catered in this item rate.
Supply , laying & testing of XLPE insulated, screened,HT PVC bedded, galvanized steel strip or wire armoured electric power cable (heavy duty) 11000 Volts grade (E) with aluminum conductor 3 core 95 square mm ISI marked IS: 7098-1985, laid in trenches, duct, through pipe, in floor, on pole including jointing , complete all as specified and as directed by Engrs-In-Charge. Note: PCC route indicators to be fixed on every 50m distance duly written ' HT CABLE' on each route indicator and rate to be catered in this item rate.
Testing of UG HT Cable by portable HT fault detector(11 KV line) and showing the fault/short circuit distance from either end without excavating UG cable,not exceding testing for 2 km running cable , complete all as specified and as directed by Engrs- in Charge.
Testing of ABC (Ariel Bunch Cable) HT Cable by portable HT fault detector(11 KV line) and showing the fault/short circuit distance from either end without excavating UG cable,not exceding testing for 2 km running cable , complete all as specified and as directed by Engrs- in Charge.
S&F in repair's Cable jointing kit for HT 11 kv (Earthed) cable for out door end termination, Heat shrinkable jointing kit complete with jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 70 to 95 sqmm cross sectional area including testing after jointing ,complete all as specified and as directed by Engrs- in Charge.
S&F in repair's Cable jointing kit for HT 11 kv (Earthed) cable for out door end termination, Heat shrinkable jointing kit complete with jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 120 to 185 sqmm cross sectional area including testing after jointing ,complete all as specified and as directed by Engrs- in Charge.
S&F in repair's Cable jointing kit for HT 11 kv (Earthed) cable for indoor end termination, Heat shrinkable jointing kit complete with jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 70 to 95 sqmm cross sectional area including testing after jointing , complete all as specified and as directed by Engrs- in Charge.
S&F in repair's Cable jointing kit for HT 11 kv (Earthed) cable for indoor end termination, Heat shrinkable jointing kit complete with jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 120 to 185 sqmm cross sectional area including testing after jointing, complete all as specified and as directed by Engrs- in Charge.
S&F in repair's Cable jointing kit for HT 11 kv (Earthed) cable for Straight through Heat shrinkable jointing kit complete with jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 70 to 95 sqmm cross sectional area including testing after jointing , complete all as specified and as directed by Engrs- in Charge.
S&F in repair's Cable jointing kit for HT 11 kv (Earthed) cable for Straight through Heat shrinkable jointing kit complte with jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 150 sqmm cross sectional area including testing after jointing , complete all as specified and as directed by Engrs- in Charge.
Excavation in trenches n.exc 1.5 m wide and n. Exc 1.5 m depth and getting out in hard/dense soil for cable etc. , complete all as specified and as directed by Engrs- in Charge.
Returning, filling in approved hard/dense soil including spreading, leveling, watering and well ramming in layer each n.exc 25 cm , complete all as specified and as directed by Engrs- in Charge.
Removing surplus soil to a distance n,exc 50m and depositing whre directed at a level n,exc 1.5m above the starting point , complete all as specified and as directed by Engrs- in Charge.
Supply and Laying dry river Sand cushining and cover 80mm thick before laying of cable and 150 mm thick after the cable is laid, complete all as specified and as directed by Engrs- in Charge. Note: (1) only punned thickness shall be measured.
Supply & laying unreinforced precast concrete cable cover class HV, type 1 with peak size 300mm x 180mm x 40mm , complete all as specified and as directed by Engrs- in Charge.
S&F repair's Dual ratio current transformer 100/50/5 with CT chamber (Seperate core for metering and seperate core protection (class 5P-10), 15VA burden for metering (class 1.0) including installation, testing and commissioning, complete all as specified and as directed by Engrs- in Charge.
M&L for painting of steel and two pole structure for surface such as columns, bracing gantary MS chanels,angle iron of any size and shape with one coats of synthetic enamel aluminium paint over two coats of red oxide primer after preparation of old painted surface colour code of paint shall be as approved ,complete all as specified and as directed by Engrs- in Charge.
M&L for painting of steel and four pole structure for surface such as columns, bracing gantary MS chanels,angle iron of any size and shape with one coats of synthetic enamel aluminium paint over two coats of red oxide primer after preparation of old painted surface colour code of paint shall be as approved, complete all as specified and as directed by Engrs- in Charge.
Restringing of sagged ABC (Aerial Bunch Cable) XLPE HT (11 KV) cable of size 185 sqmm 3 core with help of hydra/machinery including fixing hanging on MS clamps , complete all as specified and as directed by Engrs-In-Charge. Note: 1. ABC cable to be rolled and unrolled properly. 2. Rate of brackets, clamps,Nut Bolts to be catered in this item rate.
M&L for calibration and testing of protection relays of any make or type fitted on 11 KV VCB`s at Power house -1, (detail given below) as per IS and code of practice to ensure NO ERROR including setting for earth fault over current, phase over current with trip time delay in accrodance to feeder load and other parameters of site including synchronizing of the same with MRS outdoor VCBs settings to ensure that fault shall not be travel to nearst source feeder including minor repair, replacement of wiring etc. if required and complete all as specified and as directed by Engrs- in Charge. (a)Existing VCB ( Make- Seimens) 11 KV - 04 Nos (b)Existing VCB ( Make- ABB) 11 KV - 03 Nos NOTE :- (i) The setting shall be carried out by only qualified and prior approval shall be obtained from GE (ii) The calibration shall be carried out each job in a 06 months and relay setting shall be carried out once in a six month as per load and site conditions to avoid any fault travel to next adjacent source breaker and shall be monitored regularly. The calibration and setting must be completed and record shall be maintained by the contractor and submitted to Eng-in charge.
M&L for calibration and testing of protection relays of any make or type fitted on 11 KV RMU's/CSS in Power house -1 area as per IS and code of practice to ensure NO ERROR including setting for earth fault, over current, phase over current with trip time delay in accordance to feeder load and other parameters of site ,settings to ensure that fault shall not travel to nearst source feeder including minor repair, replacement of wiring etc. if required all as directed by by Engineer-in-charge. NOTE :- (i) The setting shall be carried out by only qualified and prior approval shall be obtained from GE (ii) The calibration shall be carried out each job in a 06 months and relay setting shall be carried out once in a six month as per load and site conditions to avoid any fault travel to next adjacent source breaker and shall be monitored regularly. The calibration and setting must be completed and record shall be maintained by the contractor and submitted to Eng-in charge.
Supply and fixing in repair's HT jumper existing two pole/4 pole structure for transformer/ termination point /isolation point etc using winding of ACSR Conductor (Weasel to mink) for 11 KV line, including two aluminium cable lugs of ACSR Conductor jumper,Nuts and bolts, washer etc, as required at site, complete all as specified and as directed by Engrs- in Charge.
Upto 90 cm long (set of three)
Upto 1.2 m long (set of three)
Upto 1.5 m long (set of three)
Supply and fixing potential transformer resin cast epoxy with protective enclosure of ratio 11KV/RT3/110V, RT3/110V/RT3 Class1.0/3p, Burden 100VA/50VA voltage factor 1.2 continuous/1.5 for 30 Seconds. ILV 12/28/75 kvp.Ins class B Ref Std IS : 3156/1992 Drawing No KE-TP02. one end earthed type with one of HRC fuse on HV Side, complete all as specified and as directed by Engrs- in Charge. Note:Primary Neutral to be solidified earthed including removing of old unserviceable pts.
Filtration of transformer oil through stream line oil filtration plant, extracting the moisture contents and carbon deposits from oil and bringing it to 50 KV dielectric strength including carrying out acidity test /dielectric test before and after filtration, complete all as specified and as directed by Engrs- in Charge.
Supply and fill transformer oil (ISI Marked ) after filtration with 50 to 60 KV dielectric strength filled in transformers / VLE Units, refixing of top cover and testing, complete all as specified and as directed by Engrs- in Charge.
Supply and fill silica gel in the transformer breather assembly, complete all as specified and as directed.
Supply only jelly for applying on OH conductors, joints etc, complete all as specified and as directed.
Repair to transformer to disconnecting of earthing lead and taking down carefully defective transformer of capacity 75 KVA to 630 KVA located at varrious location of Power House - 1 including shifting it from power house -I area of particular transformer location to workshop by using mechanical operated crane and truck and back to original position after necessary repair service including gaskit, oil inseration sheet,and filteration testing and TIt Bit maintenence and required adjustment and installing the transformer including reconnection of all electrical HT/LT cables wires and earthing connection, complete all as specified and as directed by Engrs- in Charge. Note: Oil gaskit, Silica gel will measured and paid seperately.
M&L for loading/unloading /shifting of transfrmer from one site to another site & operation of transformer cover, draining oil if any, detanking core and coil assemble, assessment and estimation for repair and replacement of parts, cleaing and washing of dust/rust and dirt from all other parts including core tanks and cooling tubes, retanking after replacement of parts/repair as required filling fresh/new filtered transformer oil taking of transformer for test and testing for all the rutine test as in case of new transformer as per relvant ISS & after satisfactory repairs & testing, marking & providing blue paint etc. loading of transformer at the contractor's works. for different size of transformer 63 KVA to 630KVA, complete all as specified and as directed by Engrs- in Charge. NOTE :- (i) Labour component required for the replcement of unserviceable parts shall be deemed to be included in the unit rate quoted against this item. (ii) Major parts (as required) shall be mesasured and paid separately under appropriate item of this Sch 'A' as supply only. (iii) Transformer oil shall be measured & paid separately under relevent item. (iv) M&L for copper coil winding shall be measured & paid separately under relevent item. (iv) T&P and minor parts will be arranged by the contractor and the cost there of shall be deemed to be included in the unit rate quoted against this item.
Supply only HT brass Bushing for transformer capacity upto 63 to 630KVA , complete all as specified and as directed by Engrs- in Charge.
Supply only LT brass Bushing for transformer capacity upto 100KVA, complete all as specified and as directed by Engrs- in Charge.
Supply only LT brass Bushing for transformer capacity upto 125 to 250 KVA, complete all as specified and as directed by Engrs- in Charge.
Supply only HT Bushing rod of brass complete with nuts, bolts, washer for transformer cap 63 to 630 KVA, complete all as specified and as directed by Engrs- in Charge.
Supply only LT Bushing rod of brass complete with nuts, bolts, washer for transformer cap 63 to 630 KVA , complete all as specified and as directed by Engrs- in Charge.
Supply only set of gaskets (Rubberised cork/ neoprene) material complete for transformer cap 63 to 630 KVA , complete all as specified and as directed by Engrs- in Charge.
Supply and fix transformer breather assembly with silica gel filled including removing the unserviceable breather suitable for transformer of capacity 63 to 250 KVA , complete all as specified and as directed by Engrs- in Charge.
Supply only Oil drain/ filter valve for sutaible size complete for transformer cap 63 to 630 KVA, complete all as specified and as directed by Engrs- in Charge.
M&L for Cleaning the body surface by scratching the old worn out/peeled off paint with the help of emery paper washing and painting with one coat on outer side with synthetic enameled Grey paint after cleaning and removing oil spot from the bodyof transformer of capacity 63 KVA to 630 KVA and painting complete with two coat of enameled grey paint over a coat of primer and writing with paint, complete all as specified and as directed by Engrs- in Charge. Note:- Unit rate quoted against this item shall be deemed to include for writing MES No and SM No on equipment with paint.
Supply and fix in repair's switch air break gang operated out door and vertical type and use in porcelain pattern.( conforming to IS specifications) 11 KV, 400 Amps capacity triple pole mechanically operated suitable for operation from ground level complete with HT insulator 12 Nos channel, GI pipe light grade/ operating rod with pad lock arrangement and out door drop-out expulsion fuse assembly with fuse carrier fitting, complete all as specified and as directed by Engrs- in Charge.
Supply and fix in repair's switch air break gang operated out door and vertical type and use in porcelain pattern ( conforming to IS specifications) 11 KV, 200 Amps capacity triple pole mechanically operated suitable for operation from ground level complete with HT insulator 12 Nos channel, GI pipe light grade/ operating rod with pad lock arrangement and out door drop-out expulsion fuse assembly with fuse carrier fitting , complete all as specified and as directed by Engrs- in Charge. Note : Use in porcelain type.
Opening and taking out the vacuum circuit breaker 11 KV 400 Amp, type VMX from panel and carry out the general maintenance such as oiling greasing the mechanical parts, motor, gear, lever spring operating rod, cleaning the female contacts, tightening of nuts and bolts, cleaning the male and female contact of panel, oiling the bus bar shutter, checking the AC/DC wiring, circuit including control fuses and circuit jack, on/off push button indicating lamp, voltmeter, ammeter, PF meter, any minor parts needs replacement should be replaced and testing after inserting the VCB in panel , complete all as specified and as directed by Engrs- in Charge. (a)Existing VCB ( Make- Seimens) 11 KV - 04 Nos (b)Existing VCB ( Make- ABB) 11 KV - 03 Nos Note:- (i) Unserviceable spare parts will be measured and paid for separately as supply only (ii) Unit rate quoted against this item also includes labour component required for replacement of unserviceable spare parts. (iii)The contractor shall be check the existing system of 11 KV VCB for installation of VCB parts. The contractor will be to take prior approval from GE.
Supply only trip catch assembly.
Supply only big gear assembly.
Supply only small gear assembly.
Supply only tripping coil 30 V DC Cat Part No IN 54450007-AB.
Supply only closing coil 30 V DC Cat Part No IN 54450007-AB.
Supply only trip shaft.
Supply only closing shaft.
Supply only holding latch assembly.
Supply only power pack 110 V input and 24 V DC.
Supply only power pack 110 V input and 30 V DC.
Supply only power pack 230 V input and 110 V DC.
Supply only power pack fuse 1 to 5 Amp as per existing sample
Supply only PT fuse 1 Amp, 11 KV as per existing sample
Supply only HRC fuse link type NSD type FA 02 Amps to 20 Apms, 500 V as per existing sample
Supply only over current relay as per existing sample
Supply only breaker control switch as per existing sample
Supply only indicator switch LED type sutaible for 11KV VCB (R,Y,B, black, green, white)
Supply only master trip relay as per existing sample
Supply only digital type ammeter sutaible for 11 KV VCB as per existing sample
Supply only digital type voltmeter sutaible for 11 KV VCB as per existing sample
Supply only spring charging motor 220 V AC/DC supply.
Supply only Roller bearing Cat Part No 1VYN 400950-077.
Supply only isolating contacts suitable for 11 KV VCB, 630 Amps rating same to match with existing complete all as directed by Engineer-in-Charge.
Supply only HT vaccum interrupted assembly with flex connection suitable for VMX type VCB 630 Amps capacity for RYB phases complete all as specified and as directed by Engineer-in-Charge.
Supply & fix insulator used in the connection of CT to bus bar for breaker of 11 KV VCB, complete all as specified and as directed by Engineer-in-Charge.
Supply & fix 100 mm bore GI tube, light grade for protection of cable, with all fitting lead in trenches /under road / with wall /in wall /under floor where required, complete all as specified and as directed by Engineer-in-Charge.
Supply & fix 80 mm bore GI tube, light grade for protection of cable , with all fitting lead in trenches /under road / with wall /in wall /under floor where required , complete all as specified and as directed by Engineer-in-Charge.
Repairing of locking arrangement devices of GOD with provision of locking arrangement including nuts, bolts, washers & strips, complete all as specified and as directed by Engineer-in-Charge.
S&F Lightening arrestors expulsion type complete with all fittings, transmission class, discharge capacity 65 Kilo Amps suitable for 11000 Volts including connecting to earth wire 4mm dia GI wire, supplied and fixed complete all as specified and as directed by Engineer-in-Charge.
Supply & fixing Danger notice plate of size 25cm x 20cm x 1.60mm thick of mild steel sheet, vitreous, enameled white, with letters, figures and conventional skull & bones in signal red colour and fixed with MS clamps made out of 25mm x 3mm MS flat iron including bolts and nuts of approved size for HT 11000 volts, complete all as specified and as directed by Engineer-in-Charge.
Supplying and laying in replacement synthetic rubber mat of 1 mtr x 2 mtr x 19 mm sutaible for 11KV at sub station , complete all as specified and as directed by Engineer-in-Charge.
M&L for Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick burried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of plate not less than 1.5 deep below normal ground level and connected to and including galvanized strip 32x6 mm by means of GI nuts, bolt, check nuts, washers thimbles, etc as shown in electrical plate No 03 SSR Part I and connection to main switch board or panel and testing on completion including excavation and earth work in any type to soil, returning fitting in and removal of surface spoil to a distance not exc 50 metre, PCC chamber (1:3:6) type C-2, charcoal and salt mixed layer 15cm thick all around the earth plate electrode, MS funnel with wire mesh, GI pipe light grade 40mm bore for watering and 20mm bore meter long GI pipe light grade for earth wire protection fixed with poles with two clamps, made from MS flat 25mm x 3mm, bolts, nuts and washers 75mm thick RCC cover 1:2:4 type B-1 shall be provided on CI frame etc, complete all as specified and as directed by Engineer-in-Charge. Note - PCC chamber shall be constructed at least 1.5m away from the earth electrode. The pipe for watering shall be provided in slanting manner.
M&L for transformer platform rendering 10mm thick on fair faces of brick work or concrete surfaces using 1:6 cement mortar , complete all as specified and as directed by Engineer-in-Charge.
M&L for NO ENTERY BOARD notice plate of size 45cm x 60cm x 1 mm thick of mild steel sheet, vitreous, enameled white, with letters, figures and conventional skull & bones in signal red colour and fixed with MS chanel made out of 100 mm x 100mm MS chanel iron including bolts and nuts of approved size, complete all as specified and as directed by Engineer-in-Charge.
M&L for graded stone coarse aggaregate size of 40mm on laying in 11 KV yard for insulation and 11/433 volt and existing sub station. The contractor shall be befor laying clean existhing aggregate i.e grass, sand etc. , complete all as specified and as directed by Engineer-in-Charge.
Repair/ maintance of unserviceable tap change for 100-630 KVA transformer 11000/433 volts,50HZ ,the auto tap changer capacity of 7 step for +7.5% to -7.5% and repair as recommended unserviceable parts, complete all as specified and as directed by Engineer-in-Charge. Note:- The contractor shall be visit of before quoting rate and all repair rate included in this item.
Supply & Fixing in repair's Glowsign Board in Blue base with white letters including frame work long 6 feet width and height 2.5 feet, 40 mm dia of GI pipe including accessories with nuts, bolts and washer complete fitting etc, including frame work complete with 0.7 mm thick GI plain sheet including errection at site at any position & testing , complete all as specified and as directed by Engineer-in-Charge. Note: Necessary nut, bolt,washers, fasner, welding etc & internal lighting and electrical wiring etc required deemed to be included into the item rate.
Cutting and cleaning the tree branches around the HT poles/over Head line upto 3 mtr from either side of pole/ over head line and clear the site and throw away the branches to a distance , complete all as specified and as directed by Engineer-in-Charge. Span - Distance between two adjacent poles
Labour only for surface excavation n.exc 30 cm deep and averaging 15 cm deep and cleaning of surrounding of out door electrical installation,2 pole/4 pole structure by cutting vegitation, tree, bushes, grass, etc, and surface dressing , complete all as specified and as directed by Engineer-in-Charge.
Supply & fixing Anti climbing device spike type fabricated out of MS flat 50mm x 6 mm in two parts with 14 Nos 230 mm long and 12mm dia spikes, sharpened ends with and including nuts, bolts & washers and welding made to shape to suit the cross section of poles including painting with two coats of aluminium point over a coat of red oxide primer , complete all as specified and as directed by Engineer-in-Charge.
M&L for Stay assembly complete comprising thick,ms galvanised stay bow 40 cm long with two nos galvanised thimbles 20mm dia of MS galvanised stay rod 180 cm long complete with & including accessories as shown in electrical plate No 1 of SSR Part-I , complete all as specified and as directed by Engineer-in-Charge. Note : loop type insulator, stay clamps, stay wire, excavation and concrete measured separately.
M&L for steel tubular swaged poles complete with cast iron base plate,finial taper plug, bolts,nuts and screws as as specified type 410 SP-55 (11.0 metres long) , complete all as specified and as directed by Engineer-in-Charge. Note : PCC and earth work shall be measured paid separately.
Re-Stretching of loosened ACSR over head conductor,GI wire(Per span consisting of any number of wire) of any size by opening the binding from insulators and re-fixing after stretching with proper sag including strengthening of ACSR conductor and re-binding the same on insulators with new binding wire of 14 gauge etc and trimming of tree branches of any size or dia for making 2.5 metre minimum clearance from over head conductor where required , complete all as specified and as directed by Engineer-in-Charge.
M&L for painting of steel tubular poles of 9m to 12m long of HT, one coat of synthetic enamel paint complete silver colour with alternative Red and Black strip up to 1.5 mtr height from top edge of coping complete including numbering of poles, complete all as specified and as directed by Engineer-in-Charge. Note : Black and Red Strip for tubelar Poles and PCC poles for 1.5 mtr height from the top edge of coping complete with coping is white wash for cement base paint.
S&F Disc type insulator Porcelain , Vitreous clay, Colour White, Brown or Green of height 145 mm x 255 mm dia for working pressure 11000 Volts ball and socket type of two in series disc assembly with tension clamp , complete all as specified and as directed by Engineer-in-Charge.
S&F Pin type, porcelain, vitreous, white, brown or green insulator of height 150 mm x 150 mm dia of 11000 Volts grade including one galvanized mild steel spindle & nut & two washers , complete all as specified and as directed by Engineer-in-Charge.
S&F Loop type insulator, porcelain, vitreous white, brown or green of size 90mm x140mm and clearance of hole 25.5 mm for stay assembly , complete all as specified and as directed by Engineer-in-Charge.
Supply only new copper wire wound coils for LT winding of transformers with super enameled copper winding wire of suitable gauge so as to match with the working capacity of transformer and all as per manufacture’s design and specification including providing Class-E insulation and fixing. HT coils in position and connecting electrically in core assembly of 63 KVA to 630 KVA , complete all as specified and as directed by Engineer-in-Charge.
Supply only new copper wire wound coils for HT winding of transformers with super enameled copper winding wire of suitable gauge so as to match with the working capacity of transformer and all as per manufacture’s design and specification including providing Class-E insulation and fixing. HT coils in position and connecting electrically in core assembly of 63 KVA to 630 KVA , complete all as specified and as directed by Engineer-in-Charge.
M&L for PCC (1:3:6) type C-1 using 20mm graded stone aggregrate as in coping of pole etc including necessary from work as required , complete all as specified and as directed by Engineer-in-Charge.
M&L for PCC (1:3:6) type C-2 using 40mm graded stone aggregrate as in foundation for stay set/pole etc including fair finish even and to exposed surface without using extra cement , complete all as specified and as directed by Engineer-in-Charge.
S&F PCC route indicator of size 600mm x 240mm x 60mm duly written in block letters"CAUTION HV MES" barricating/reflex tape of 240mm length at top of the route indicator to be fixed 300mm below GL at every 30 m during returning filling and cost for the same , complete all as specified and as directed by Engineer-in-Charge.
M&L for Plinth plateform for 200 KVA Transformer of size 1.8m x 1.6m x1.6m with brick walls in cm (1:4) platered in CM (1:4) externally with two coats of cement based paint,brick walls shall be minimum 60cm depth below GL of suitable thickness,including necessary earth work,floor 75 mm thick,over 75 mm thick (1:4:8),over 100mm thick brick hard core 63 nominal mm size,including necessary earth filling below , complete all as specified and as directed by Engineer-in-Charge.
Schedule of Credit
KMT INDUSTRIES
R. D. Industrial
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .