Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.0 LAccepted-AOC S 17 77 1 CHARAN NAGAR COLONY NADESAR VARANASI UTTAR PRADESH PIN 221002 | VARANASI | UTTAR PRADESH | 221002 | L1 | Accepted-AOC Being L1 Bidder | |
| 2 | L2₹20.7 L+₹75,478 (3.78%)Rejected-Finance | L2 | Rejected-Finance Being other than lowest bidder | |
| 3 | L3₹21.3 L+₹1.3 L (6.46%)Rejected-Finance PHAYANG GOMPA COMPLEX AGLING ROAD SKALZANGLING LEH LADAKH J K 194101 | LEH | LEH | LADAKH | 194101 | L3 | Rejected-Finance Being other than lowest bidder | |
| 4 | L4₹27.6 L+₹7.6 L (38.1%)Rejected-Finance HOUSE NO 251 E BLOCK ADARSH NAGAR BALLABHGARH FARIDABAD PIN 121004 HARYANA | FARIDABAD | FARIDABAD | HARYANA | 121004 | L4 | Rejected-Finance Being other than lowest bidder | |
| 5 | L5₹34.9 L+₹14.9 L (74.6%)Rejected-Finance 361 BEHIND DAV SCHOOL JAWAHAR NAGAR SRINAGAR 190008 | SRINAGAR | JAMMU AND KASHMIR | 190008 | L5 | Rejected-Finance Being other than lowest bidder |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
11 Jun 2022, 6:00 pmClosed
GE 865 EWS
GE 865 EWS, PIN-913 865 C/o 56 APO
REPAIR MAINT OF DG SETS AND CONNECTED WORKS OF SECTOR B AND ADJACENT AREA UNDER AOR OF AGE EM II OF GE 865 EWS AT LEH
2022_MES_524974_1
865/EWS(NIT-45)/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
GE 865 EWS
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE 865 EWS
₹80,000
Yes
9 Jul 2022
19 May 2022
13 Jun 2022
19 May 2022
11 Jun 2022
4 Jun 2022
Amount
M&L for PCB card controller of type ausiliary 105 suitable for PCC 3300 of digital controller panel of folllowing capacities of DG Sets Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge Make :- Kirloskar/Mico/TVS
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
M&L for repair of broken door hinges, handles of acoustic enclosure of following capacities of DG Sets Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
S&F in replacement of Fuel filter Element (Primary & Secondary) for following capacity of DG Sets Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
Repair and replacement of Dynamo for following capacity DG Sets Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
M & L for Calibration of FIP including supply & fixing in replacement plunger, DV, governor wet O-Ring, Pin roll, barrel, Pin ball bearing spring, washer and testing for following capacity of DG Set complete all as specified and directed by engr in Charge.
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
M&L for Checking, Inspection, maintanance and servicing complete including replacement of unserviceable spare parts of the DG set (comprising of Engine/ Alternator/ Control panel) of the following capacity for smooth functioning complete all as per manufacturers instructions and all as directed by Eng in Charge including the following works also: - A:(a) Checking of lubricating oil condition, (b) Checking engine for oil, water leakage and correcting the same (c) Checking of all the nut bolts of engine and alternator, (d) Checking of all belts and adjust the tension properly, (e) Cleaning of air filters, (f) Checking and readjusting the valve clearance, (g) Change of Oil/Fuel filters and engine oil if necessary, (h) Checking of starter motor battery and charger, (i) Checking of cooling system and fuel system, (j) checking of all power cables and AVR connections and mounting bolt tightnees of alternator, (k) checking the function of AVR genaral checks, (l) Checking of control panel meters and gadgets functioning, (m) Checking of all control and safety wirings. B. (a) Checking of flexible coupling of engine and alternator, (b) Cleaning of crank case ventilation pipe, (c) Checking of injectors and fuel pump, (d) Checking of alternator and carbon brushes of following capacity DG sets: - NOTE (1) Cost of Spare parts required will be measured and paid separately, (2) Servicing/routine check up carried out through authorised service centre of manufacturer, (3) Make of spare recommendation by auth service centre of manufacturer.
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
Replacement of 'V' belt for radiator/water pump suitable for following capacity DG Sets Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
S&F in replacement of Air Cleaner Assembly (inner & outer) suitable for following capacity of DG Set Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
S&F in replacement of Oil Filter Element with 'O' ring washer for DG Sets of following capacity Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge Make :- Kirloskar/Mico/TVS
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
Replacement of fuel pipe with banjo bolt at both side suitable for following capacity DG sets Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
M & L for changing /toping up of best quality of engine oil 20W40 type for various type/capacity DG sets including removing of old burnt engine oil from DG Sets complete all as specified and directed . Make Castrol/ Veedol/ Valvoline.
Supply only cotton waste for daily use for cleaning the DG sets complete all as specified and directed.
S&F replacement of auotmatic voltage regulator (AVR) 24 volt suitable for following capacity of DG Sets Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
M& L for Replacement of water pump assembly for following capacity DG sets Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
M&L for Replacement of Fan Hub assembely for following capacity of DG Set Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
M & L Cleaning of radiator for following capacity DG sets by using Keroscene oil and radiator cleaning solution (Ready to Wash) by pressure of pump and brush and removing radiator from the Gen Set including taking to work shop, making necessary welding/brazing to the leakage and Re-assembling after painting of the same complete all as directed by Engr-in-Charge.
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
S&F in Replacement of self starter for following capacity DG Set Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
Replacement of Turbo charger assy.for following capacity DG sets Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
Supply & fixing in replacement of Hose Pipe of following capacity of DG Sets Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
M & L for taking out burnt winding of exciter of following capacity of DG Sets including re-winding copper wire of super quality, of existing size, No of turns, varnishing, heating complete including testing on full load to entire satisfaction of Engr in Charge.
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
Supply & fixing in replacement of DC wiring of digital control panel of following capacity of DG Sets Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
M&L for disconnecting the U/S DC alternator of following capacity DG Set, 3 Phase of approved make & type form engine, transporting to workshop dismantling it for repairing and rewinding by taking out burnt armature winding aleading the alternator coil with existing gauge/size of super enamelled copper wire, providing new insulation, sleeves, varnishing cotton taping etc reassembling the alternator complete including aligning with engine and testing in all aspects for smooth functioning all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
Note: Re-assembling all the component of the alternator and mounting the same on the existing foundation including welding of alternator foundation plate by electric arc welding ,aligning the alternator with engine and testing on full load as specified in particular specification and as directed by Engr-in-Charge.
S&F in Replacement of lub oil pump suitable for following Capacity DG Sets Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
S&F in replacement of Synthetic Insulating mat of Size 2Mx1Mx10MM complete all as specified and as directed.
S&F in Replacement of Oil seal front and rear suitable side for following Capacity DG Sets Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
Earthing complete with galvanised iron earth plate electrode 600x600x6mm buried directly in ground (earth pit not less than 2.25mtr deep below ground level) with top edge of earth plate not less than 1.5mtr below normal ground level, connected with 25x4 mm size GI strip as earth lead, by means of bolts, nuts, check nuts and washers of galvanized iron or steel complete with 40mm dia GI light grade protection pipe, 20mm dia GI medium grade watering pipe with funnel including charcoal, dust, salt, PCC M-15, type B-1 in pit with precast RCC M-15(1:2:4), type B-1 (using 20mm graded crushed stone aggregates) in cover reinforced with XPM not less than 4.0 Kg per Sqm, test point etc. all as shown in electric plate No-3 of SSR Part-I (2009), complete with necessary earth work in any type of soil, removal to a distance not exceeding 50mtr, including testing on completion, complete all as specified and as directed by Engineer-In-Charge. Note: Earth pit chamber and RCC pit cover shall be painted with two coats of red synthetic enamel paint over one coat of primer including preparing of surfaces.
S&F in Replacement of Thermostate valve suitable for following Capacity DG Sets Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
200 KVA DG Set
160 KVA DG Set
125 KVA DG Set
100 KVA DG Set
63 KVA DG set
25 KVA DG set
Supply and lay in replacement of LT underground cable ISI marked XLPE insulated heavy duty electric cable armoured and PVC sheathed heavy duty 1100 volts grade with aluminium conductor multistranded including cable connecting lugs, glands, jointing materials etc., laid in trenches, floors, ducts and fixing with fixing material on pole, wall complete of 50 SQMM 3.5 core . Make : Finolex/ KEI/Polycab/Havells/Indoasian.
Supply and lay in replacement of LT underground cable ISI marked XLPE insulated heavy duty electric cable armoured and PVC sheathed heavy duty 1100 volts grade with aluminium conductor multistranded including cable connecting lugs, glands, jointing materials etc., laid in trenches, floors, ducts and fixing with fixing material on pole, wall complete of 150 SQMM 3.5 core. Make : Finolex/ KEI/Polycab/Havells/Indoasian.
M & L for replacement of exhaust silencer of following capacity of DG set Make Kirloskar/Cummins/Greaves complete all as specified and directed by Engr-in-Charge
400 KVA DG Set
380 KVA DG Set
320 KVA DG Set
160 KVA DG Set
125 KVA DG set
100 KVA DG set
Supply and lay in replacement of LT underground cable ISI marked XLPE insulated heavy duty electric cable armoured and PVC sheathed heavy duty 1100 volts grade with aluminium conductor multistranded including cable connecting lugs, glands, jointing materials etc., laid in trenches, floors, ducts and fixing with fixing material on pole, wall complete of 185 SQMM 3.5 core. Make : Finolex/ KEI/Polycab/Havells/Indoasian.
Supply and lay in replacement of LT underground cable ISI marked XLPE insulated heavy duty electric cable armoured and PVC sheathed heavy duty 1100 volts grade with aluminium conductor multistranded including cable connecting lugs, glands, jointing materials etc., laid in trenches, floors, ducts and fixing with fixing material on pole, wall complete of 240 SQMM 3.5 core. Make : Finolex/ KEI/Polycab/Havells/Indoasian.
S&F in Replacement of battry terminal for DG Sets complete all as specified and directed by Engr-in-Charge.
S&F in replacement battery cable assy. with copper conductor multistranded RED and BLACK colour 2mtr long 21sqmm for connection to self starter unit to Battery unit complete.
Supply and topping up of best quality antifreezing, inhabitor (Coolant) liquid for DG Set of various capacity and locations complete all as specified and directed.
Supply and topping up of best quality distilled water for batteries of DG Set of various capacity and locations complete all as specified and directed.
Supply and topping up of best quality electrolite for batteries of DG Set of various capacity and locations complete all as specified and directed.
S&F in replacement Oil pressure gauge upto 1010 KVA capacity DG sets complete all as specified and directed by Engr -in-Charge
M&L for Prepration of Old Surface of DG Sets, preparing the surface by rubbing with fine emery paper and making the surface smooth and re-painting with two coats of super quality synthetic enamel paint by spray gun fully matched with its original colour and making good entire DG Set ( Engine, Alternator, foundation ,Diesel Tank and Radiator unit with canopy) and including marking SM/MES No on DG Sets with diffrent paint maintaning colour code to the following capacity of DG Sets complete all as specified and directed by Engr in Charge .
(a) 400 KVA DG Set
(b) 380 KVA DG Set
(c) 320 KVA DG Set
(d) 160 KVA DG Set
(e) 125 KVA DG Set
(f) 100 KVA DG Set
(g) 63 KVA DG set
Note : Make of spare parts to be replaced under this work and mentioned in relevant items in this BOQ here-in-before shall be of approved make and as per the manufacturer's recommendation of DG sets and other equipments.
M/S MALIK CHAND SIRI RAM
betong construction company
national engineering
M/S TRADE LINK
PADMA ENTERPRISES
Alpha Engineers and Builders
Horizon Construction Company
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .