EE JSV Division Barsar
EE JSV Division Barsar
(SUB HEAD Supply erection of submersible pumping machinery for booster stage, centrifugal pumping machinery for 1st. stage and Providing and laying jointing and testing of MSERW pipe and laying jointing and testing GMS pipe for rising main).
2021_HPIPH_50486_1
EE-IPH-BSR-TA 21-22-7268-7318
Open Tender
Civil Works
Item Rate
90 days
Sub Division Barsar
Please refer Tender documents.
9 documents required · 9 mandatory
₹400
Yes
EE JSV Division Barsar
₹57,010
Yes
9 Dec 2021
28 Jul 2021
5 Aug 2021
28 Jul 2021
5 Aug 2021
28 Jul 2021
28 Jul 2021 - 5 Aug 2021
Amount
Booster Stage
Supply of submersible pumping set of Approved make ( As per list attached) comprising to latest relevant BIS Code. The pump should be fitted with bronze impeller of suitable alloys as per IS 8034-1979 latest suitable for raw water having greased packed bearings and shaft with wound stator on motor side and with soft protection sleeve on pump side ensuring better life for shaft coupled to a submersible squirrel cage electric induction motor (water proof type) of required HP, RPM 2900 of reputed make conforming to BIS 9238-1979 latest with upto date amendments, totally dust and water proof for submersible duty isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed lubricated bearings and provided with stainless steel thrust bearing plate to with stand non vertical loads with minimum wear and tear. It should also be fitted with a device to take up expansion of water with the heating of motor. The pump set should include water level guards, erection clamps , cable clips and depth gauge etc. and suitable for operation on data given below:-
SITE CONDITIONS:-
Location of site:- ( Gowald Khad near head works )
The altitude of place in which the motor is intended to work in ordinary service.- mtrs.
Humidity:- Humid during rainy season
Nature of atmosphere:- Normal
Detail of quality of water:- Raw water
Water free from sand or not:- Free from sand
Water corrosive or not:- Not corrosive
Turbidity:- upto 500 ppm
Type of well:- Percolation well
Inside dia of well :- 4.00 mts.
Depth of water during HFL in the well:- mtrs.
Maximum draw down:- Excepted 2.00 mtrs.
Depth of well :- Percolation well 6.00 mtrs.
Any other information if required.
OPERATING CONDITIONS
Type of current:-AC. Three phase
Operating frequency 50 Hz.
Rated voltage 400(+/-) 10% volts
System of earthing if any to be adopted Double loop earthing as per BIS: 3243-1987 latest with upto date amendments .
Speed of revolution To be quoted by tenderer
Direction of rotation : To be quoted by tenderer
No. of working hours per day. 8 hours
The maximum temperature of cooling air and water in the place in which the pump set is intended to work in ordinary service Temperature of place to be specified 20°C to 42°C.
MOTOR
Ref. to BIS code BIS 9283-1979 with upto date amendments
Type of enclosure of motor.)As per BIS-4691-1985 (Latest
Type of duty : Continuous
Mechanical output in KW: Suitable for driving submersible pumps required for duties specified against pumps. To avoid overloading of motor a margin of about 15-20% may be kept in the rated output to prime Mover.
Class of insulation Class –B
Max. Permissible temp. Rise of motor reqd. if different from that given in 8 (viii) above.To be specified by the tenderer
Particulars of test reqd. & where they are to be conducted.AS per terms and conditions attached.
Particulars as to whether voltage limiting device will be employed. Oil immersed star delta starter to be installed between bus bar and motor. Shunt capacitor is also proposed to be installed for improving the power factor at site.
Note:- Star delta starter upto 37.5 Kw.
Type of motor As per BIS 9283-1979 or latest.
Details of shaft extension required
Break way torque in terms of rated load torque and the corresponding break-way starting current which may be taken from the supply with the starting apparatus in circuit. Break way torque to be given by the tenderer but the starting current should not exceed 2.5 times of the full load current.
Nature of load and any information regarding the driven machine which has a bearing upon the torque reqd. during the accelerated period, the kinetic energy of the moving parts to be accelerated and No. of starts during a specified period. To work the pump offered
Where possible fault capacity of the system to which the motor is connected.The motor should be able to withstand initial current of 2.5 times the rated current for two minutes without suffering damages or permanent deformations.
PUMPS
Nos. of pumps required. 2 No. pumps out of which one set will work at site and one set will act as stand bye
Spare parts required.For two years normal maintenance as recommended by manufacturer.
Type of drive Electric induction motor
Optional fittings required
Pump Operating conditions
Capacity 2.80 LPS for each pump or 10.08 M3/hours
Total head in meters 40.81 metres.
Static head 31.00 metres.
Minimum depth of water - metres
Variation in water level -
Ground level to Max. water level
Ground level to delivery point
Pressure in the suction tank.
Pressure in the delivery tank
Length of rising main 250.00 mtrs
Dia of rising main 65 mm
Turbidity of water < 50 PPM
Drive type Electric driven
Limits of total head in which the pump is required to operate.(-) 15% to (+) 10% of total head
Suction/Delivery size of pump to be sepcified by the tenderer
Efficiency of pump at to be sepcified by the tenderer
a) Duty head 40.81 mtrs
b) (+) 10% head. 44.89 mtrs
c) (-) 15% head. 34.69 mtrs
Material of construction to be sepcified by the tenderer (manufactures certificate to be apptended
Supply of suitable OIl Imerssed star delta starter of MEI/Kilburn make conforming to BIS 8544-1979 latest with upto date amendments for squirrel cage induction motor (make to be specified by the tenderers) mounted on panel board with magnetic type over load release and gas-pots, time legs, under voltage release & initial oil filing of suitable capacity.
Supply of MS. Angle iron steel sheet 16 SWG fabricated floor mounting closed (Almirah type) switch board comprising and capable of mounting the following accessories and with all internal electric connections, duly painted. The drawing of panel board shall be subject to approval of Engineer-in-Charge.
ICTP switches with HRC fuses of Havells/L&T/standard /cromption make for required motor of suitable capacity and conforming to BIS: 4064-1978 latest with upto date amendments.
Bus bar chamber having 3 copper bars of suitable rating for full length of 3 phases and one bar of half the rating of full length for neutral conforming to BIS: 8084 –1976 and 11353-1985 read with 5578-1985 all latest with upto date amendments of suitable rating
MCB of suitable capacit of Havells/standard/MDS/Jyoti/Kilburn make to feed motors offered by the tenderer conforming to BIS: 2516-1985 latest with upto date amendments with neutral linked under voltage release. (Sutaible capacity )
3 phase indicator lamps complete with toggle switches for individual motors conforming ti BIS 3452 part I & II latest with up to date amendments of of suitable rating
50 mm dial Hour run meter of CEE/NEE make of suitable range as per relevant BIS specifications.
Supply of Kirloskar/Leader make dia. cast iron (PN.1.00 ) double flanged sluice valve having one dia Higher than pump size to delivery of pump and capable of with standing nominal seat pressure of 10.20 kg/cm2 as per IS :780-1984
Supply of Kirloskar/Leader make dia. cast iron (class PN 1.0 ) double flanged (swing check type ) refelux valve having by pass arrangement and having one dia Higher than pump size to delivery of pump and capable of with standing nominal seat pressure of 10.20 kg/cm2 as per IS :5312-1984
Providing and laying suitable size copper PVC insulated armoured power 3.5 core cable conforming to BIS 1554 (part-I) –1988 of latest with upto date amendments siemen/Gloster/ICC make from meter of HPSEB- to MCB and from MCB to Bus bar switch and starter (one cable carrying all three phases) including all other electrical equipment/accessories such as thimbles, flexible pipe solder, nuts and bolts, cable glands, etc. laid in pipes of trenches under floor. The type, size and make will be subject to approval of HPSEB authorities. In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer.
Supply side: Suitable Size
Motor side: Suitable Size
Supply of Kirloskar/Leader make 65mm dia cast iron (class PN 1.00 ) double flanged (swing check type ) refelux valve having bye pass arrangement and size equal to dia of rising main i.e. 65 mm capable of with standing nominal seat pressure of 10.20 kg/cm2 as per IS :52312-1984
Supply of PVC joint less flat water proof cable as per BIS: 694-1990 latest with upto date amendments suitable for the pump sets offered from MCB to motor including all other electrical equipment/accessories such as thimbles, flexible pipes solder, nuts and bolts, cable glands etc laid in pipes of trenches under floor. The type, size and make will be subject to approval of HPSEB authorities & in case of non acceptance by HPSEB authorities it shall have to be replaced by tenderer.
Providing and laying double loop earthing with G.I. wire & G.I plate complete with material such as charcoal, common salt, GI. Pipes, thimbles, nuts and bolts, digging of pits, GI. Wiring and aluminum strips of required capacity conforming to BIS: 3043-1987 latest with upto date amendments for above motors and other electrical equipments.
Supply of standard make circular dial pressure gauge 0 -11 kg/cm2 range of feibig make with all accessories such s stop cock, copper tubing etc, conforming to BIS: 3624-1987 latest with upto date amendments.
Providing and laying delivery pipe 50 mm dia. and common header 65 mm dia GMS Tubes (Medium Class) (IS:1239 - 1979) jointed with MS flanges of table-5 as per IS: 6392-1971 (upto a length of 20 mtrs ) including tappers, flanges, rubber gaskets, nuts and bolts and specials upto 5 mtrs away from the outer wall of pump houses as per layout drawings approved by Engineer-in-Charge.
Supply of floor/wall mounted power factor shunt capacitor conforming to BIS: 2834-1986 latest with upto date amendments Baja/L&T/Asian / Cromption make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually of suitable KVAR rating each including cable of siemens/ Gloster / ICC make from bus bar chamber to capacitor and also including L&T/LK/Kilburn make ICTP switches conforming to BIS –4064-1978 or latest with HRC fuses (range to be specified by the tendrerer).
Supply of suitable cable for water level guard
Supply of supporting clamps.
Supply of cable clips of required size.
Erection of all equipment from Sr No. 2 to 90 including cost of tees, bends, tapers and any other fittings required as per site conditions and as per direction of Engineer-in-charge.
IST STAGE
Providing horizontal spindle horizontal split casing/end suctions (back pull out arrangement) single/double multistage centrifugal pump or combination of pump in series of recommended Approved make ( As per list attached) as per BIS-1520-1980 with up to date amendments, read with IS: 9137-1978 or latest edition suitable for lifting clear water for under mentioned characteristics with Bronze impellers/priming funnels, casing ring and shaft sleeves of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on a MS/Cast steel base plate ( base plate to be from the manufacturers of the pumping unit only) to Squrrel cage induction motor of standard make such as Kirloskar/Crompton/ NGEF/KSB ABB/ HEL/GEC/Seimens/Jyoti and suitable for operation on 400 (+)/-) 10% volts, 50 cycles/second, 3 phase AC electric supply. The power of electric motor should be at least 10% in excess of the maximum power required by the pump in the operation range of (+) 10% and (-) 15% of the duty point head. The motor should be as per IS: 325-1978 with up to date amendments read with IS: 900-1972. It shold include the cost of bearing nuts, bolts and painting etc and should meet the following requirement.
(a)Pumps: Specifications
(i) Make
(ii) Model
(iii) No's of Stages
(iv) Material (manufacures certificate to be appended )
Performances
(i) Head (H) in
(ii) Discharge (Q) in
(iii) BHP absorbed
(iv) Efficiency (n)
(v) NPSH (K)
(b) Motors: (Specification)
(i) Make.
ii) Model
(iii) Motor rating (KW)
(iv) Speed
(v) Insulation :
(c) Coupling:
(d) Base plate.
Discahrge (Q) : -For each pump 2.80 lps or 10.08Cum/ hours
Total dynamic head :275.03 metres.
(a) LWL in sump well (h) :450.00 mtr
(b) Shaft level : 450.00 mtr
(c ) Level at discahrge point : 612.00 mtr
(d) Suction lift : 3.00 mtrs
(e) Residual head : 3.00 mtr
(f) Static head 163.00 mtrs
(i) Rising Main :
(a) Length 4350.00 mtrs
(b) Dia. :65 mm
(iv) Pumping Hours : 8 hours
(v) Altitude of installation above MSL : 850.00
(vi) Characteristics of water : clear water
(a) Temperature :
(b) Ambient temperature
(c ) Turbidity up to 50 ppm
(d) Alkalinity Mg/Ca Co3
(e) Size of the solids mm
(f) Other
Providing ICTP Main Switch Side handled operated /Change Over switches of L & T/ Crompton/ Standard/ Havells make of suitable capacity Operational rating as per IS: 4064 ( Part-II) -1978 with up to date amendments immediately after the power meter of HPSEB of suitable capacity i) Make ii) Model ii) Capacity Suitable capacity
Providing M.S. sheet, steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm, duly painted, with steel sheet of 16 gauge comprising, capable of mounting the following accessories with all internal connections:-
Panel/Switch Board:
(i) Drawing
. (ii) Layout plan.
O.C.B.of Kilburn / MEI make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516(Part-II) -1985 with up to date amendments of suitable capacity.
(i) Make
(ii) Type
(iii) Range: Suitable Capacity
ELCB of Havell/Inditec/ MDS/ L&T /Standard make as per IS: 2516(Part-II)-1985 with upto date amendment which should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape etc. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.
(i) Make
(ii) Type
(iii) Range: Suitable rating
The voltage monitor relay of L & T/AE make three phase with all protection and usual indicator and electric siren against single phasing low voltage, high voltage, reverse phasing, over loading and phase voltage difference as per IS: 3842 ( Latest edition of suitable capacity).
(i) Make
(ii) Type
(iii) Range: 380-440 volts
(i) Make
(ii) Type
(iii) Range: 0-500 V
Power factor meter of AE/ L& T make square type as per relevant IS codes with up to date amendments of suitable rating. Rate inclusibe in item No. 2 (A) above
(i) Make
(ii) Type
Frequency meter of AE/ L& T make square type as per relevant IS: Codes with up to date amendments of suitable rating.
(i) Make
(ii) Type
(iii) Range: suitable rating
Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with up to date amendments of suitable capacity .
(i) Make
(ii) Type
(iii) Range: suitable rating
ICTP switches with HRC fuses of L & T/ Crompton/ Standard/ Havells make of suitable capacity as per IS: 4064-1978 with up to date amendments.
(i) Make
(ii) Type
(iii) Range: suitable rating
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 ( P-I&II) with up to date amendments.
(i) Make
(ii) Type
(iii) Range: suitable rating
(i) Make
(ii) Type
(iii) Range: suitable
Capacitor of L & T/ Bajaj/ Assian/ Crompton make as per IS:2834-1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of suitable capacity to HP offered including cables as per relevant ISI code ( of Siemens/Glocter/IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064-1978 with upto date amendments .
(i) Make
(ii) Type
(iii) Range: suitable rating
Providing suitable star delta starter of MEI/ Kilburn /L& T make as per IS: 8544-1979 with up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling with single phase preventor as per IS 8544 ( Part-II) -1987 with up to date amendments .
Starter
i) Type
ii) Make :
Singal Phase Prevantor
Providing Hour run meter of recommended make of suitable capacity as per IS: 722 (Latest edition)
Hour Run meter
i) Type
ii) Make
iii) Range. Suitable rating.
Providing double flanged Cast iron sluice valve of Kirloskar/ Leader make of 50 mm dia for the suction pipe and capable of with standing the normal seat pressure and as per 780-1984 ( Part-I) Class PN 1.0 with upto date ammendments ..
i) Make
(ii) Class P.N.I
(iii) Seat pressure : 10.20 Kg Cm2
iv) Material C.I.
Providing double flanged Cast steel sluice valve of Kirloskar/ Leader make and size one dia higher than for the delivery line of the pump and capable of with standing the normal seat pressure and as per relevant IS 1414/ API 600 ( Class ASA- 300 with up to date amendments. .
i) Make
(ii) Class ASA-300
(iii) Seat pressure : 52.00Kg Cm2
iv) Material :C.S.
Providing double flanged (Swing type) Cast steel reflux valve of Kirloskar/ Leader make size one dia higher having bye pass arrangement on the delivery line of pump and capable of with standing normal seat pressure as 1868/ API 600 ( Class ASA- 300 with up to date amendments .
Reflux valve
i) Make
(ii) Class ASA-300
(iii) Seat pressure : 52.00Kg Cm2
iv) Material :C.S.
Providing double flanged Cast steel non return valve of Kirloskar/ Leader make and size one dia higher having bye pass arrangement for rising main 65mm dia and capable of with standing normal seat pressure as per 1868 API 600 ( Class ASA- 300 ) up to date amendments .
Non Return Valve
i) Make
(ii) Class ASA-300
(iii) Seat pressure : 52.00Kg Cm2
iv) Material :C.S.
Providing 100 mm dia. circular dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range suitable range
(i) Make
(ii) Range :0.16 Kg/cm2
Installation of all the items appearing at Serial No. 93 to 217 as per the direction and to the entire satisfaction of Engineer-in-Charge.
Providing and fixing double flanged GMS piping work layout to be approved by the Engineer-in-Charge for suction and delivery pipes suitable to pump(s) offered and common header as per the rising main respectively complete with all specials such as bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories as indicated in the drawing including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS: 1364-1983. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head stipulated under item No.1..
The size of the various components to be as under:-
(i) Suction pipe 65 mm dia Min. length = 15 mtr.
(ii) Delivery pipe 50 mm dia -do- = 5 mtr.
(iii)Common Header 65 mm dia -do- = 10 mtr.
(i) Suction pipe. GI pipe 65 mm dia ( Heavy class) flanged with M.S. flanges of Table - 5
(ii) Delivery pipe.GI pipe 50 mm dia ( Heavy class) flanged with M.S. flanges of Table - 28
And will extend up to 5 meters from the outer wall of the pump house in the direction to be jointed. (iii) Common header GI pipe 65 mm dia ( Heavy class) flanged with M.S. flanges of Table - 28
Providing and laying copper PVC insulated armoured power cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Siemens/ IEC/ICC/GICO/Grandly/National make including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.
Motor side: Suitable Size Min length = 20 mtrs.
Supply side: Suitable Size Min length = 10 mtrs.
Providing and fixing double loop earthing and G.I. plate /copper plate 600mmx600mmx3mm thick electrode complete with material such as thimbles, nuts and bolts, charcoal and common salt, 25mmx6mm G.I. strips & G.I. wire as per IS: 3043-1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
RISING MAIN
Excavation in foundation , trenches etc., in all kinds of soil such as pickwork, jumper work blasting work, in soft / hard rock, including chiseling wedging out of rocks clearance of bushes etc.including shoring, dewatering etc. in all leads and lifts stacking the excavated soil upto any lead and lift clear from the edge of excavation and then returning the stacked soil in 15cm layers when required into plinth , sides of foundation etc. consolidating each deposited layers by ramming and watering and then disposing of all surplus earth within all leads and lifts complete to the entire satisfaction as directed by the Engineer-in-charge of the site of work.
Laying,jointing and testing of galvanized mild steel tube in trenches including cost of fabrication of bends as required at site of following dia including tube fittings and to the entire satisfaction of the Engineer-in-charge as per IS:1239 (Part-I)-1979 jointed with M.S. flanges / circumferencial butt welding including welding in three layers as per IS:816-1965,gasket sheet not less than 3mm in thickness,nuts and bolts etc.and including cost of cutting of threaded ends if plain ended pipe is not avaiable complete in all respect. (Cost of excavation in trenches,M.S flanges, butt wellding and gasket sheet etc. to be measured and paid for separately)
GMS pipe 65 mm dia Heavy class- 0/0 to 250 900 to 4350
Providing, Laying, jointing and testing in trenches of mild steel electrically resistance welded pipes conforming to IS: 3183-2007 grade L-210 or A as per dimensions weight and test pressure mentioned below in a random length 4 to 7 mtrs. 95% joints shall be Butt welded joints and only 5% joints shall be flanged joint by providing and welding M.S. plate flange as per table below conforming to IS: 6392-1971 (latest upto date amendments) and welding of flanges with pipes as per IS:816-1965 with a electrode as per IS:814-1967 including required Nos. and size of M.S. nuts and bolts as per IS:1369-1967 and compressed asbestos fiber jointing gaskets sheet not less than 3mm thick as per IS:2712-1965. The welding of flanges tobe done on both faces in two layers to make the joints leak proof and to the entire satisfaction of the Engineer-in-charge. The laying of pipes should be conformed to IS:5822-1994 (earth work in trenches and M.S. flanges butt ,welding & bend to be measured and paid for seprately)The pipe and special shall have outside and inside will be Galvanized as per BIS:4736. The Galvanization is done by the manufacturing firm it self complete in all respects as per the direction of the Engineer- in-Charge
MSERW Pipe 65 mm dia 4.5mm wall thickness
Providing Circumferencial Butt welded joints by electrical are welding to below mentioned dia and wall thickness GMS /MSERW pipe welded in requisite number of weld runs so as to achieve the minimum effective throat thickness of weld conforming to IS 816-1969 specifications, by using welding electrodes of 2.5 mm to 6.3 mm of Advani Oerlikon (Adore)-CITOJET/ESAB make, conforming to IS 814-1991 including Die pentration test, at site of work complete in all respects, including manual/machanical handling of pipes in all leads and lifts to the entire satisfaction of Engineer in charge.
Butt welding MSERW / GMS Pipe 65 mm dia .
Providing welding and fixing of MS flanges at 5% of total joints, conforming to following tables as per IS 6392-1971 (Last with upto date amendments) and welding of MS flanges with GMS/ MSERW pipes in three layers on both faces i.e two layer on outer faces and one layer on inner face to make the joint leak proof (The cost of providing and laying of MSERW/GMS pipes to be measured and paid for separately). The welding of flanges should conform to IS 816-1969 with electrodes as per IS: 814-1991 and required number of nuts and bolts conforming to IS 1364. the thickness of gasket not less than 3.00 mm conforming to IS 2712-1998. The work shall be done as per entire satisfaction of engineer in charge within all leads and lifts.
GMS/ MSERW Pipe 65 mm dia from RD 0/0 to 2100 Rmt Table -28
GMS pipe 65 mm dia from RD 2100 to 3500 rmt Table -17
GMS pipe 65 mm dia from RD 3500 to 4350 rmt Table -5
Providing and fixing double flanged cast steel non return valve of 65 mm dia class ASA -150 having test pressure of 52.00 kg Cm2 of Leader/Kirloskar make as per BIS 1868/API-600 complete in all respect with in all leads and lifts including required No.of Nuts and bolts and gasket sheet not less than 4mm in thickness to the entire satisfaction of the Engineer-in-Charge .
Providing and fixing screwed type cast iron air release valve 25 mm dia (single ball type ) of Leader/ Kirloskar make as per BS 1452-90 with upto date amendments as per class PN 10.00 to with stand a seat pressure of 11.22 kg /Cm2 complete in all respects with in all leads and lifts & to the entire satisfaction of the Engineer-in-Charge .
AEC AUTOMATION
M/S ASHWANI ELECTRICAL WAORKS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .