| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.8 LAccepted-AOC 8 TOWNSHEND ROAD KOLKATA 700025 | KOLKATA | KOLKATA | WEST BENGAL | 700025 | L1 | Accepted-AOC satishfied | |
| 2 | L2₹26.0 L+₹1.2 L (4.92%)Rejected-Finance BALTIKURI INDUSTRIAL ESTATE PLOT NO A 01 DASNAGAR HOWRAH 711113 | HOWRAH | HOWRAH | WEST BENGAL | 711113 | L2 | Rejected-Finance bidder is not L1 | |
| 3 | L3₹30.4 L+₹5.6 L (22.6%)Rejected-Finance 86 TOLLYGUNGE CIRCULAR ROAD KOLKATA WEST BENGAL 700053 | KOLKATA | KOLKATA | WEST BENGAL | 700053 | L3 | Rejected-Finance bidder is not L1 |
| Sl No | Description | Qty | Unit | Lyric International L3 | NATIONAL AIRCON L2 | SKY DECORATIONS PRIVATE LIMITED L1 |
|---|---|---|---|---|---|---|
| 1.00OUTDOOR UNITS | ||||||
| 2.00Supply, Installation, Testing & Commissioning of Modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling/heating having 100% hermetically sealed inverter type twin Rotary/Scroll Compressor(s), minimum two compressors (with individual seperate PCB) for above 14HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required. To have better efficiency condensor fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and work even at 50°C ambient temperature without tripping. The system shall be able to deliver 100% of the rated capacity upto 39 Degree Celcius. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply and BMS compatible. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability. The Indian Seasonal Energy Efficiency Ratio (ISEER) of the unit shall be as per Energy Conservation and Sustainable Building Code (ECSBC) 2024 as below and complete connections, inter connections etc. as required. (Make: O General/Mitsubishi Electric/ Hitachi/Daikin/Blue Star/Voltas) | ||||||
| 3.00For Cooling | ||||||
| 4.00 | 12 HP | 12 | Per HP | 26,500 ₹3,18,000 | 27,000 ₹3,24,000 | 20,500 ₹2,46,000 Lowest |
| 5.00 | 36 HP | 36 | Per HP | 25,500 ₹9,18,000 | 26,000 ₹9,36,000 | 20,500 ₹7,38,000 Lowest |
| 6.00INDOOR UNITS | ||||||
| 7.00Supply, Installation, Testing and Commissioning of following minimum capacity and external static pressure VRF/VRV ceiling mounted low static ductable type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration Isolators, drain pan, drain pump, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± 10%, 50 Hz complete as required. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Signals. The system shall be capable to adjust air flow as per room requirement automatically. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor). Low static ductable units (minimum 19 to 29 pascal external static pressure) (Make: O General/Mitsubishi Electric/ Hitachi/Daikin/Blue Star/Voltas) | ||||||
| 8.00 | 1 TR(=1.25 HP) | 1 | Each | 49,000 ₹49,000 | 30,000 ₹30,000 | 27,890 ₹27,890 Lowest |
| 9.00 | 1.6 TR(=2.0 HP) | 2 | Each | 52,000 ₹1,04,000 | 29,500 ₹59,000 | 27,890 ₹55,780 Lowest |
| 10.00 | 2 TR(=2.5 HP) | 19 | Each | 45,000 ₹8,55,000 | 35,000 ₹6,65,000 | 27,890 ₹5,29,910 Lowest |
Tender Value
Refer Docs
EMD Value
₹53,801
Closing Date
29 Oct 2025, 11:00 amClosed
EE-l CKHED PWD
Central Kolkata Health Electrical Division P-12, C.I.T Road(1st floor) Kolkata- 700014
Vertical Extension of State Health Transport Organisation building at 142 AJC Bose Road, Kolkata-700014 (with 10 storied foundations) proposed to be used as Directorate of Drugs Control Head Quarters, SITC of additional Air Conditioning Machines.
2025_WBPWD_911655_1
WBPWD/EE-I/CKHED/eNIT51/25-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
45 days
CENTRAL KOLKATA HEALTH ELECTRICAL DIVISION
Please refer Tender documents.
3 documents required · 3 mandatory
₹53,801
Central Kolkata Health Electrical Division
27 Aug 2026
24 Sept 2025
31 Oct 2025
24 Sept 2025
29 Oct 2025
9 Oct 2025
8 Oct 2025
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .