Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹58.7 LAccepted-AOC DL 221 3 SALT LAKE SECTOR II KOLKATA 700091 WEST BENGAL | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | L1 | Accepted-AOC Accepted | |
| 2 | L2₹67.5 L+₹8.8 L (15.0%)Rejected-Finance 3 C DR JAGABANDHU LANE KOLKATA 700012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | L2 | Rejected-Finance Quoted Higher Rate | |
| 3 | L3₹69.4 L+₹10.7 L (18.3%)Rejected-Finance | L3 | Rejected-Finance Quoted Higher Rate | |
| 4 | L4₹71.5 L+₹12.8 L (21.8%)Rejected-Finance 448 MUZAFFAR AHMED STREET KOLKATA 700 016 | KOLKATA | KOLKATA | WEST BENGAL | 700016 | L4 | Rejected-Finance Quoted Higher Rate |
Tender Value
₹72.3 L
EMD Value
₹1.4 L
Closing Date
28 Apr 2025, 1:00 pmClosed
SE,KHEC,PWD
Kolkata Health Electrical Circle, P.W.Dte KIT Annex Building, 5th Floor KOLKATA
Construction of Proposed G6 Storied Building of State Drug Control and Research Laboratory , West Bengal at 2, Covent Lane , P.O - Tangra , P.S - Entally , Kolkata- 700015.-External EI Work.
2025_WBPWD_834494_1
WBPWD/SEKHEC/CKHED/eNIT01/ 25-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
90 days
State Drug Control and Research Laboratory, W. B
Please refer Tender documents.
8 documents required · 8 mandatory
₹1.4 L
Office of the SE,KHEC,PWD
18 Jun 2025
9 Apr 2025
30 Apr 2025
9 Apr 2025
28 Apr 2025
22 Apr 2025
17 Apr 2025
Amount
SUB-HEAD I : SITC OF VCB PANEL, TRANSFORMER, MAIN LT PANEL & EMERGENCY PANEL
Overhauling, Servicing, Installation, Testing & commissioning of Indoor-type, floor mounted, metal clad, single tier, fully compartmentalized, free standing, 6.0 KV 800 A VCB Panel with 3 Nos VCBs (1 Incomer + 2 Outgoing), totally enclosed and fully interlocked, horizontal drawout, horizontal / vertical isolation type breaker and as per detail specification attached as per name plate of the existing 3 panel H.T. gear are as follows, Rated voltage - 6.6 KV, Rated current - 800 A, Type - VB8A, Frequency - 50 Hz, Make - BIECCO LAWRIE LIMITED. suitable for use on 6.0 KV, 3 Phase, 50 Hz AC supply to energise TWO number 630 KVA Dry Type Transformers. As per the specifications attached.
[ Note :- Any other arrangement/apparatus/equipement or civil work if required during execution of above mention works should be provided by the bidder and no extra cost will be paid against such work ]
Overhauling, Installation, Testing & commissioning of 2 nos 630 kVA Dry Type Transformers at site (Central Combined Laboratory / Pasteur Institute, 2 convent Lane, Kolkata -15) after Servicing the same including of all releted civil work for instatallation. Incl S & Installation of 120mm x 50mm x 50mm, 6 mm thick MS "U" channel of 32 fit length for commissioning 2 nos transfermer. Which will be brought from Dr. R. Ahamed Dental College & Hospital (New Campus) to Central Combined Laboratory New sub-station building. Incl Making testing arrangement and submitting all the test reports for high voltage testing of specified voltage incl. checking & testing of all HT / LT equipments incl. earth resistance test and any other tests as desired by DOE, Govt of WB should be executed by authorized firm of Directorate of Electricity,Govt of WB and all reports should be approved by DOE , Govt of WB & commissioning the installation after obtaining the Approval of Directorate of Electricity, Govt of WB .The scope shall be also included the necessary approval from Authority also.
Note-1 : (If, Any damages occured during loading, unloading & carrying, the damage parts should be replaced by the concerned Agency with one in place of damages and no extra charges will be paid for the above.)
Note-2 : Any other arrangement/apparatus/equipement or civil work if required during execution of above mention works should be provided by the bidder and no extra cost will be paid against such work ]
SITC of floor mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve makelist attached [Incoming 1000A ACB - 2 Nos with Mechanical & Electrical Interlock, BBC 1500A 4 Bars- 2Set, BusCoupler 1000A ACB - 1 no Outgoing : a) 630A TPN SFU --2 sets b) 400 A TPN SFU --2 sets c) 315 A TPN SFU-- 3 sets d) 250 A TPN SFU -- 2sets e) 160 A TPN SFU -- 4 sets [LT MAIN PANEL IN THE SUBSTATION]
Making testing arrangement and submitting all the test reports for high voltage testing of specified voltage incl. checking & testing of all HT & LT equipments incl. earth resistance test and any other tests as desired by DOE, Govt of WB should be executed by authorized firm of Directorate of Electricity,Govt of WB and all reports should be approved by DOE , Govt of WB & commissioning the installation after obtaining the Approval of Directorate of Electricity, Govt of WB .The scope shall be also included the necessary approval from the concern Authority also.Testing Of Relay tripping timmings, synchronising & Proper tripping by primary/secondary injection set etc as required for LT panel in accordance to DOE, Govt of West Bengal and all reports should be approved by DOE , Govt of WB [ Note : If any other test/tests as desired by DOE, Govt of West Bengal which is not mentioned here , should be executed by the bidder and no extra charge will be paid against such work]Testing Of Relay tripping timmings, synchronising & Proper tripping by primary/secondary injection set etc as required for LT panel in accordance to DOE, Govt of West Bengal and all reports should be approved by DOE , Govt of WB [ Note : If any other test/tests as desired by DOE, Govt of West Bengal which is not mentioned here , should be executed by the bidder and no extra charge will be paid against such work]
SUB HEAD II - HT CABLING IN SUBSTATION
Supplying and laying of6.6KV (UE) Grade XLPE Aluminium conductor, PVC sheathed, armoured cable confirming to IS 7098 with latest ammenment of following size in the existing Masonary Open Duct as required as per makelist attached.[ From HT Gear to Consumer HT Gear and to Transformer].(Makelist attached)
3 Core x 300 Sq.mm
Making heatshrinkable joints to the ends of the following XLPE HT cable at the transformer end as well as at the VCB ends supplying with necy. jointing kits, sockets, sleeves, anti-corrossive paste, wires, solders, jointing compounds, rubber sheets etc. incl. supplying of necy. tools & tackeles for crimping the end sockets, soldering irons & making of glands at the both end of the cable as per directions of EIC
3 Core x 300 Sq.mm
SUB HEAD III - LT CABLING FROM SUBSTATION TO OUTSIDE BUILDINGS
Supplying of following size armoured PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size. (Makelist attached)
4 Core300 Sq. mm
4 Core 185 Sq. mm
4 Core 120 Sq. mm
4 Core 95 Sq. mm
4 Core 16 Sq. mm
Supply & Laying of 1.1 KV Grade 7 Core 1.5 sq.mm PVC Armoured Copper Cable from Transformer WT relay to VCB WT relay for Power & Control Supply (makelist attached)
Supplying and making end termination with Brass compression gland and Finishing the end of conductor by crimping method by aluminium lugs for the following sizes of PVC insulated and PVC sheathed aluminium conductor cable of 1.1 KV Grade as required
4 Core300 Sq. mm
4 Core 185 Sq. mm
4 Core 120 Sq. mm
4 Core 95 Sq. mm
4 Core 16 Sq. mm
Laying only Cable above 50 sqmm but not exceeding 400sqmm through existing RCC/ Hume/GI Pipe/open masonary trench for single, 2, 3, 3½ and 4 core [ Ref : F-1, 3/B]
Laying only Cable upto 50 sqmm through existing RCC/Hume/ GI Pipe/open masonary trench for single, 2, 3, 3½ & 4 core
SUB HEAD IV - EARTHING
Earthing with 80 mm dia GI pipe (ISI-Medium) x 3.0 Mts long and 1 No. 75 mm x 8 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F suitable heavy type heat shrinkable PVC sleeve to cover 75 mm x 8 mm GI flat, to an average depth of 3.65 Mts (for Transformer Neutral: - 2 x 2 Nos).
Earthing with 65 mm dia GI pipe (ISI-Medium)x 3.0 Mts. long and 1 No. 50 mm x 6 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F suitable heavy type heat shrinkable PVC sleeve to cover 75 mm x 8 mm GI flat, to an average depth of 3.65 Mts. (for HV apparatus like Transformer body - 2 x 2 Nos, HT Gear - 2 nos, LT Panel-2nos,
Excavation of soil for installation of Earth Electrode and filling & ramming. For Soft Soil. As per G.S.
Extra for treatment of soil by using salt & charcoal or coke for plate electrode. As per G.S.
Supply & fixing earth busbar of galvanized (Hot dip) MS flat 65 mm x 8 mm on wall having clearence of 6 mm from wall incl. providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. As per G.S.
Connecting the equipments body to earth busbar incl. S & F 50 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor with GI saddle as required and connection to equipments with incl. drilling holes, bolts, nuts,washers etc. As per GS.
Insulating the 65 x 8 mm M.S. flat incl. S&F black heat shrink PVC sleeves etc. The PVC tube sleeve to be inserted on the GI flat and heat shrinked by heating apparatus by skilled technician carefully without damaging the PVC sleeve as per direction of the EIC (for transformer neutral earth bus bar).
S& laying 2 x 150 sq. mm. single core multistrand PVC insulated flexible Cu wire in suitable size of PVC flexible pipe (reinforced) from nutral earth busbar to transformer point as required (for Transformer neutral earthing)
Finishing the 150 sq.mm. copper wire ends by crimping method incl. S&F copper socket tape etc. as required.
SUB HEAD - V - SAFETY EQUIPMENT
Providing & fixing danger plates made of mild steel at least 2mm thick & vitreous enameled white on both sides & with inscription in signal red colour on front side as required.
High Voltage - size 250mm x 200mm
Medium Voltage - size 200mm x 150mm
Providing and fixing carbon dioxide (CO2) type fire extinguishers conforming to IS 15222-2002 and cylinders fully charged of following capacity(4.5 Kg ) ( makelist attached)
S&F 5 Kg capacity gas pressure (DCP) fire extinguisher on wall with suitable iron bracket. ( makelist attached)
Providing of set of 9.5 litre capacity GI bucket painted in post office red colour with prior coat of red-oxide paint and written with white paint 'FIRE' and mounted on MS angle iron frame with bracket and suitable base of appropriate size & capacity incl filling sand etc.
Providing First Aid Box as by St. John Ambulance Brigade / Indian Red Cross conforming to IS 13115-1991.
Supply and fixing safety instruction chart in word duly framed with 5mm thick glass as required (approx. Front area 1.20 sqmt.)
Supply and fixing shock treatment chart duly mounted on a wooden frame with 5mm thick glass as reqd. (approximate front area 1.20 sq.metre).
Providing of rubber mat 2 mtrs Length x 1 m. wide and 12mm thick to withstand 11 KV dielectric strength as per IS 15652-2006.
Providing of rubber mat 2 mtrs Length x 1 m. wide and 6mm thick to with stand 3.3 KV dielectric strength as per IS 15652-2006.
S&F 6KV grade Rubber Hand Gloves.
SUB-HEAD VI : EXECUTION OF MISCLLENEOUS WORKS
Supply, fabrication and placing/fixing MS checkered plate made of 8mm thick incl 50mm x 50mm x 6 mm MS angle iron structure welded by fixing for insert plates at 4 sides in cable trench top with 2 nos 3/8" TMT handle rod incl gas cutting, grinding & drilling with one coat of red laid primer and one coats of synthetic enamel paint as per direction of EIC.
S&F of MS Channel of following sizes with nut, bolt, washer etc to provide overhead supporting arrangement above different LT panels, cable support at HV side of transformer incl painting as to GS for following :
150mmX 75mm X 10mm
100mmX50mmX8mm
75mmX40mmX6mm
SUB-HEAD VII-- Internal E.I. work for Sub-Station Building & Exhaust Fan Arrangement
Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire in 20mm size PVC rigid conduit 'FR' , with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall complete with 2 no. suitable size “Ph & N” copper bar incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. 175mmx100mmx65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish. As per GS.
a) Average run 10 mtr.
b) Average run 8 mtr.
Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire in 20mm size PVC rigid conduit 'FR, with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 5A 3 pin flush type plug socket & Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. painting the MS box and mending good the damages to original finish. [Ref : E-15/4]
a) On Board.
Supply & Fixing 240 V, 20A, 3 pin plug socket with separate 20 A Piano key type switch on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required [Ref : E-6/22]
Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building work (E-16/7)
a) 25 mm size.
b) 20 mm size.
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required [Ref : E-9,1]
4x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECC.
2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC
2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC.
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.(F-5,9)
Supply & laying of one cables of following size AL, XLPE Armoured on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting (F, 2D)/(NS) (Makelist attached)
a) 4 core 35 sqmm.
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below For 4 core [F4,7]
a) 4 core 35 sqmm.
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket, tapes, anticorrosive paste & jointing materials [F5,8]
a) 4 core 35 sqmm.
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (Make list attached) As per GS.
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make list attached)(D-9,13)
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection (D-6,7)
6-32A SP MCB
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection. (Make list attached) (D-5,6)
Supplying & Fixing GI Modular Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works. As per GS.
4 Module
6 Module
Supply & Fixing 240 V Modular type switch (Brand approved by EIC) on existing GI Modular type switch board having top cover plate and making necessary connections as required. As per GS.
6 A Modular
16 A Modular
Supply & Fixing 240 V, 5 pin Modular type plug socket (Brand approved by EIC), without switch & plug top, on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. As per GS.
6 A Modular
16 A Modular
Supply & Delivery of 4 feet Industrial box type Twin LED fitting including S &D of 2X20 wattt LED( Polycarbonate) with glare free light distribution with CCT (5000K-6500 K) , with minimum luminious efficacy ≥105 Lumen/watt or better. The LED Lamp and accessories shall have BEE Certification.
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length..[C-2/17]
Supply and delivery of Heavy Duty Exhaust fans complete with all accessories having the following Model / Cat No. ( Make -EPC /Crompton/Orient/havells )
15"( 225 mm ) Speed 1370 RPM
12"( 300 mm ) Speed 1420 RPM
S & D of 1200mm sweep AC ceiling fan with out regulator, complete with P2 burst proof Capacitor, Down rod, blades, canopy, rigidly connected Safty Tie wire etc. Incl. other accessories as necessary. (Make - Cromton / Usha / Orient)
Supply & Delivary of 230V , 50Hz ,400 mm sweep heavy duty full metal body wall bracket fan (Cabin fan) complete with all accessories. ( Make -EPC /Crompton/Orient/havells )
Supply & Fixing 230 V., 18" (450mm) 4 (four) Blades Industrial type Air-Circulator Pedestal Fan complete with all accessories such as Regulator, Cord and 15 Amp. 3-pin Top (Make - -EPC /Crompton/Orient/havells ).
Supplying & Fixing MS fan clamp of two piece type for RC ceiling as per approved specification, fabricated from 40 mm x 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting – (As per Drawing no. 475 of PWD Specification Book – May 1991) [29/D-14 ]
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc [ 10 / E-18 ]
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc as per GS [ 21 (a) / C-3 ]
Engraving the deptt. number with 10 mm lettering on the body as per GS [ 24 (a) / C-3 ]
Painting upto 10 letters of the engraved number with approved black /red paint as required as per GS [ 26 (a) / C-3 ]
Fixing only exhaust fan after making holes in wall as per GS
15"Exhaust [28(b)/C-4]
12" Exhaust [28(b)/C-4]
Supply & Fixing louver shutter ( Aluminum)on wall with necy. bolts & nuts (6 mm dia x 62 mm long) as per GS
15" Exhaust [ 32(a)/D-14 ]
12" Exhaust [ 32(a)/D-14 ]
Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length. [29/C-4]
SITC of timer controlled DB (for Exhaust Fan ) in MCB SS enclosure with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish.All connections should be made by suitable copper wire and socket by crimping method incl necessary connection & provision for earthing attachment & neutral link incl Ferruling & marking with S&F following Electrical accessories & front door locking arrangement as per direction of EIC: i) 4 Way MCB SS enclosure-1 No ii) 240 V , 6 A SP MCB (C- Curve, 10 KA) - 1 No ii) 110 - 240 VAC 1 C/O Base/DIN Digital Time switch-1 iii) Blank Plate as required. (For Exhaust Fan )
SUB-HEAD VIII -- SITC OF COMPOUND LIGHTING SYSTEM
Supply & delivery of 7.0 Mtr Hot Dip Galvanized (86-65 micron dry film thickness) Octagonal Pole, as per BSEN 10025; ASTM A572; IS 5986: IS 4759/2629, ASTM A123 and BSEN IS 1461 standard. The pole should be 7.0 Mtr long, bottom dia-130 mm, top dia-70 mm, thickness-4 mm, continuously tapered and shall have octagonal cross section with pole cap at top, necessary cleat attachment/hanger for arm brackets. Base-plate having dimension 220x220x12 mm and 4 nos 'J' Type foundation bolt with double nut and plate washer, bolt dia 20 mm , PCD- 200-225 mm ,bolt length- 700 mm, Projected bolt length - 100 mm( these dimention are subjected to tolerance as per IS-2102 except for bending radius). The pole will consist of a built-in loop-box having one number 32 A, 3 Phase 3 Way connector with Neutral link on porcelain insulator (for incoming/outgoingcable and luminaries connection), and 1 numbers 6 A SPMCB. The door opening shall be complete with a closefitting, vandal resistance, weatherproof door ( to IP-55 of IS:2147) , providing with a heavy duty double internal lock with special paddle key. The door opening shall be carefully designed and reinforced with welded steel section , so that the mast section at the base shall be unaffected and undue buckling of the cut portion is prevented.The Pole should be supplied with adequate templates for the purpose of construction of base foundation.The pole should have earthing terminals 02(two) nos.
Erection of upto 7 Mtr octagonal GI (Hot Dip Galvanised in single dip) pole 1.6 Km from the store to work-site with foundation of M20 grade concrete for 7.0 Mtr GI Octagonal Pole with all the materials like sand, cement, stone chips, reinforcement steel, binding wire etc as relavent IS Code. soil bearing capacity at site as 10 T/sqmtr., by PCC Base foundation having (L-1000mm x W-1000mm x H-100mm) & RCC foundation having dimention (L-500mm x W-500mm x H-1400mm) including neatly cemented finish (3mm thick) partly below and above ground level. There should be multiple alkathene pipes upto 1.2 mtrs of 50 mm dia of adequate length for distribution of incoming & outgoing cables for street light wiring as directed by EIC in the CC foundation of octagonal poles.
S&F 50 mm. dia 1.5 mtr. long detachable type G.I. Single arm bracket, suitable for pole head. The arm bracket shall be properly welded with 15 mm. thick stifner plate of pole sleeve for strengthening incl. properly fixing arrangement with the pole by bolts, nuts and washer as per direction of EIC.
S&F 50 mm. dia 1.5 mtr. long detachable type G.I. double arm bracket, suitable for pole head. The arm bracket shall be properly welded with 15 mm. thick stifner plate of pole sleeve for strengthening incl. properly fixing arrangement with the pole by bolts, nuts and washer as per direction of EIC.
S&F of 240V, 70 watt or higher , LED Street Light including IP65 protection with CCT ( 5700-6500) & minimum Luminious efficacy>= 120 Lumen/ Watt. (Make : Panasonic / Crompton/ wipro/ Jaquar/Bajaj/ Havells)
Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint [ Ref : - H-5/5]
Supplying of one number 1.1 KV Grade XLPE insulated and PVC sheathed aluminium conductor cable(Armoured ) conforming to IS: 7098 / 1988 with its latest amendment of following size [ Make:Nicco/Gloster/Polycab/Havells/RR kabel ] [NS]
4 Core 6 Sq. mm
4 Core10 Sq. mm
Laying of one No. cable above in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed. [Ref : F-2, 1/a]
Laying of cable as below, after cutting floor/pavement/wall/ and making holes incl. embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish From 2.5 sqmm to 35 sqmm at an average depth of 75 mm in floor/pavement/wall etc.[Ref F-3, 5 (i)]
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below . [Ref : F-4, 7/C]
4 Core 6 Sq. mm
4 Core10 Sq. mm
Finishing of the XLPE/PVC insulated armoured cable ends by soldering with cable sockets and insulated tapes etc., including supplying sockets, soldering materials, tapes etc.and making connection to switch, BDB and BBC etc. [Ref : F-5, 8/b]
4 Core 6 Sq. mm
4 Core10 Sq. mm
S & L of 1.1 KV grade 3 X 1.5 Sq mm FR single core multi stranded copper wire for connection from loop box to fittings through 13 mm dia polythene pipe.
Finishing of the PVC insulated wire(3 X 1.5sqmm) ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.
S & F of medium gauge G.I pipe (ISI medium) having the following diameter [32 mm Diameter] for protection of cable with necessary fitting and jointing materials as required. (For compound light, pump house)
SUB-HEAD IX - - LED GLOW SIGN BOARD
SITC of Glowsign Board (Router cutting) with liquid Acrlyic letters with adhesive on ACP Board of 3 mm Thick ( Make - Aludecor/ Alstone) of suitable size to accommodate all the matters / contains as approved by the authority to be made with 25 x25 x 4 mm M.S angle Iron, 18 S.W. G square/ Round Hollow bar , Base plate (10mm Thickness) required for fixing the necessary Nuts , Bolts , Washers , supporting angle Iron , Clamp etc. and ACP Sheet on Front sides & edges only & back side to be covered by GI Sheet (with proper ventilation arrangement),All side to be moulded unifornmly, Side fabricated by Aluminium 'L' Channel , upon which elevated or box type letter made from imported liquid acrylic will be fixed. The Thickness of Acrylic will be 5 mm (for small letters) , 8mm (for Big letters) and 10 mm (for very big letters). The Back Side of the letters is covered by 3 mm thick ACP (Make- Aludecor/Alstone). The inside of the letter Supplying and Fixing of best Quality LED Lighting arrangement of fully water proof 10 nos LED light fittings of 20 watt (100 lumen/watt). The letters are sealed by exterior grade Silicon. The back side of the Board Covered by 22 S.W.G G.I sheet with Nuts & Bolts.
Intensity : Same & smooth uniform throughout without any dark patch
Visibility : upto 250 meters for normal eyes
The complete sign board would be fixed on roof of the bulding with providing necessary CC muffing , 1 no CI water proff 200x150x100 mm loop Box, 50x50x6mm MS angel for supporting the board of required length by nuts, bolts, washers etc. After drilling hols on the frame front facia. GSB would have 2 nos hinge type doors in back side to have the inside access including mending goods the damages to original finish.
Painting of any steel/ iron surface of the above Glow sign board with no. of coats of paints as given below with ready mixed paint/primer of approved make and brand incl. preparation of surface by sand paper/emery paper, cleaning etc. for receiving fresh coat of paint
1st coat of aluminium paint over one coat of RO priming
2nd coat of aluminium paint over one coat of RO priming.
S & F 25A timer controller in double door phosphatised powder coated 2+10 way SPN DB, din rail with IP-43 protection with electrical accessories & front door locking arrangement with all connection , a)10+2 W SPN DB with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. -2 (one) no. b) 32A DP MCB (10kA, C curve)—1(one) no c) 32 A DP MCB Isolator—1(one) no d) 32 A, 240 V DP Contactor with Auxilary Contactor(1 NO-1 NC)- 1 (One) no. e) Daily & weekly programmable basis Astro time switch, ,6 yrs. Battery backup,key pad lock features- 1 (one) no f) LED Indicator Lamp-1 set g) Blank Plate as required. [ Legrand /Schneider/Seimens/ABB/ L &T ] (For Compound Light Timer )
SUB-HEAD X : DRAWING & DOCUMENTATION
Preparation of planned & as-built G.A. drawings and Single Line Diagrams (SLD) of the proposed Electrical power distribution system of and Sub-station mentioning the cable sizes at different levels and the drawings to be made in as built GA Drawing in both Hard Copy & soft copy form (latest Autocad version in CD). Hard copy of size 1.5mt X 3mt in flex covered with transparent Acrylic sheet & sides are bind with stainless steel frame as per direction of the EIC.
Terms and Condition:
The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Defect Liability period 1 (One) Year
(Rates should be Quoted inclusive of all taxes & duities and L.W.C. @ 1% as applicable)
S. A. ENTERPRISE (BID ID -6353881)
JAYBEECO (BID ID -6349428)
RASH ELECTRICAL WORKS (BID ID -6353715)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .